OUTDOOR AWNING 2751 S DIXIE HWY PINK STEAK |
RESTAURANT |
|
6/29/23 FAILED FIRE CLF |
|
THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L |
FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING |
COMMENTS: |
|
1) THERE ARE NO SPECIFICATIONS OF THE MATERIAL OR |
STRUCTURE OF THE CANOPY SUBMIT WITH THE SITE PLAN, |
AND THESE MUST MEET THE FOLLOWING CODES FROM NFPA |
13 CHAPTER 8: |
|
8.15.7* EXTERIOR PROJECTIONS. |
8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, |
8.15.7.3, OR |
8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED |
UNDER EXTERIOR |
PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH. |
8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE |
OMITTED WHERE |
THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH |
MATERIALS THAT |
ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE |
RETARDANT??? |
TREATED WOOD AS DEFINED IN NFPA 703. |
8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE |
OMITTED FROM BELOW |
THE EXTERIOR PROJECTIONS OF COMBUSTIBLE |
CONSTRUCTION, PROVIDED |
THE EXPOSED FINISH MATERIAL ON THE EXTERIOR |
PROJECTIONS ARE NONCOMBUSTIBLE, |
LIMITED-COMBUSTIBLE, OR FIRE RETARDANT???TREATED |
WOOD AS DEFINED IN NFPA 703, AND THE EXTERIOR |
PROJECTIONS CONTAIN |
ONLY SPRINKLERED CONCEALED SPACES OR ANY OF THE |
FOLLOWING |
UNSPRINKLERED COMBUSTIBLE CONCEALED SPACES: |
(1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY |
WITH NONCOMBUSTIBLE |
INSULATION |
(2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE |
NONCOMBUSTIBLE |
OR LIMITED-COMBUSTIBLE CEILINGS ARE DIRECTLY |
ATTACHED |
TO THE BOTTOM OF SOLID WOOD JOISTS SO AS TO CREATE |
ENCLOSED |
JOIST SPACES 160 FT3 (4.5 M3) OR LESS IN VOLUME, |
INCLUDING |
SPACE BELOW INSULATION THAT IS LAID DIRECTLY ON |
TOP OR WITHIN |
THE CEILING JOISTS IN AN OTHERWISE SPRINKLERED |
ATTIC [SEE |
11.2.3.1.4(4)(D)] |
(3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR |
PROJECTIONS |
NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA |
8.15.7.4 SPRINKLERS SHALL BE PERMITTED TO BE |
OMITTED FROM |
EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF |
THE CORRIDOR |
ARE AT LEAST 50 PERCENT OPEN AND WHEN THE CORRIDOR |
IS ENTIRELY |
OF NONCOMBUSTIBLE CONSTRUCTION. |
8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER |
EXTERIOR PROJECTIONS |
GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS WHERE |
COMBUSTIBLES |
ARE STORED. |
|
CAITLIN L FRANCIS |
FIRE INVESTIGATOR |
WEST PALM BEACH FIRE RESCUE |