Plan Review Details - Permit 23060976
Plan Review Stops For Permit 23060976
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-07 Cont ID  
Sent By rmcdouga Date 2023-07-07 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2023-07-07 Time 13:21 Sent To  
Notes
2023-07-07 14:04:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE HEIGHT OF THE AWNING FRAME AND FABRIC
 ABOVE THE WALKWAY. FBC 3105.3.1.1 FABRIC AWNINGS AND
 FABRIC-COVERED FRAMES LOCATED OVER PUBLIC PROPERTY OR
 IN AREAS ACCESSIBLE TO THE GENERAL PUBLIC SHALL BE
 CONSTRUCTED SO THAT NO RIGID PART OF SUCH FABRIC
 AWNINGS OR FABRIC-COVERED FRAMES SHALL BE LESS THAN 7
 FEET 6 INCHES (2286 MM) FROM THE GRADE DIRECTLY BELOW,
 AND NO PART OF THE CLOTH DROP SHALL BE LESS THAN 7 FEET
 (2134 MM).
  
 2) SUBMIT TWO SETS OF DETAILED AWNING REMOVAL
 INSTRUCTIONS WITH PHOTOGRAPHS/DRAWINGS THAT SHOW HOW
 THIS IS DONE IN TERMS THAT A LAYMAN WILL UNDERSTAND.
 THESE INSTRUCTIONS ARE TO BE PROVIDED TO THE PROPERTY
 OWNER, OWNER'S REPRESENTATIVE OR LESSEE. FBC 107.2.1
  
 3) SUBMIT THE FLAME SPREAD CERTIFICATE FOR THE AWNING
 FABRIC. FBC 3105.3.4.1 FABRIC USED FOR AWNINGS OR
 FABRIC-COVERED FRAMES SHALL MEET THE FLAME PROPAGATION
 PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD
 INDEX NOT GREATER THAN 25 WHEN TESTED IN ACCORDANCE
 WITH ASTM E84 OR UL 723.
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-06-29 Cont ID  
Sent By clfranci Date 2023-06-29 Time   Rev Time 0.00
Received By clfranci Date 2023-06-29 Time   Sent To  
Notes
2023-06-29 14:37:02THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS,
 FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE NO SPECIFICATIONS OF THE MATERIAL OR
 STRUCTURE OF THE CANOPY SUBMIT WITH THE SITE PLAN, AND
 THESE MUST MEET THE FOLLOWING CODES FROM NFPA 13
 CHAPTER 8:
  
 8.15.7* EXTERIOR PROJECTIONS.
 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3,
 OR
 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER
 EXTERIOR
 PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH.
 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 WHERE
 THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS
 THAT
 ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE
 RETARDANT???
 TREATED WOOD AS DEFINED IN NFPA 703.
 8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM BELOW
 THE EXTERIOR PROJECTIONS OF COMBUSTIBLE CONSTRUCTION,
 PROVIDED
 THE EXPOSED FINISH MATERIAL ON THE EXTERIOR PROJECTIONS
 ARE NONCOMBUSTIBLE,
 LIMITED-COMBUSTIBLE, OR FIRE RETARDANT???TREATED
 WOOD AS DEFINED IN NFPA 703, AND THE EXTERIOR
 PROJECTIONS CONTAIN
 ONLY SPRINKLERED CONCEALED SPACES OR ANY OF THE
 FOLLOWING
 UNSPRINKLERED COMBUSTIBLE CONCEALED SPACES:
 (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH
 NONCOMBUSTIBLE
 INSULATION
 (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE
 NONCOMBUSTIBLE
 OR LIMITED-COMBUSTIBLE CEILINGS ARE DIRECTLY ATTACHED
 TO THE BOTTOM OF SOLID WOOD JOISTS SO AS TO CREATE
 ENCLOSED
 JOIST SPACES 160 FT3 (4.5 M3) OR LESS IN VOLUME,
 INCLUDING
 SPACE BELOW INSULATION THAT IS LAID DIRECTLY ON TOP OR
 WITHIN
 THE CEILING JOISTS IN AN OTHERWISE SPRINKLERED ATTIC
 [SEE
 11.2.3.1.4(4)(D)]
 (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR
 PROJECTIONS
 NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA
 8.15.7.4 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM
 EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF THE
 CORRIDOR
 ARE AT LEAST 50 PERCENT OPEN AND WHEN THE CORRIDOR IS
 ENTIRELY
 OF NONCOMBUSTIBLE CONSTRUCTION.
 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER EXTERIOR
 PROJECTIONS
 GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS WHERE
 COMBUSTIBLES
 ARE STORED.
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561.804.4728
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-06-21 Time 11:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-07-07 Cont ID  
Sent By rmcdouga Date 2023-07-07 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2023-07-07 Time 13:21 Sent To  
Notes
***NONE***