Miscellaneous Information / Notes |
MASTER 22010834 FIRE SPRINKLER UNDERGROUND |
|
|
|
|
7/19/22 REVIEWS COMPLETE, APPLICANT INVITED TO |
DOWNLOAD PLANS, PERMIT CARD UPLOADED. LEM |
7/18/22, PASS FIRE, CRW, WITH PROVISO COMMENTS |
7/15/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
7/11/22 7/11/22 PLAN REVIEW COMPLETE, CUSTOMER |
INFORMED THEY NEED TO RESUBMIT. CP |
7/8/22, FAIL FIRE, CRW, INDICATE ON THE PLAN THE |
DISTANCE FROM THE NEAREST FIRE HYDRANT TO THE FIRE |
DEPARTMENT CONNECTION (FDC). NFPA 1141 8.1.3 * |
(2017 EDITION) |
WHERE MUNICIPAL-TYPE WATER SYSTEMS ARE AVAILABLE, |
FIRE DEPARTMENT CONNECTIONS FOR SPRINKLER SYSTEMS |
DESIGNED TO NFPA 13 OR NFPA 13R SHALL BE LOCATED |
NOT MORE THAN 100 FT (30.5 M) ALONG AN APPROVED |
PATH FROM A FIRE HYDRANT AND SHALL BE ARRANGED SO |
THAT HOSE LINES CAN BE READILY AND CONVENIENTLY |
ATTACHED TO THE INLETS WITHOUT INTERFERENCE FROM |
ANY NEARBY OBJECTS, INCLUDING BUILDINGS, SIGNS, |
FENCES, POSTS, OR OTHER FIRE DEPARTMENT |
CONNECTIONS. |
PROVIDE SUPPORTING MANUFACTURERS DOCUMENTATION FOR |
PIPE SPECIFICATIONS, LISTING, BOLT TORQUE |
SPECIFICATIONS, CORROSION RESISTANCE, ETC. |
THIS PERMIT APPLIES ONLY TO THE UNDERGROUND FIRE |
LINE. THE SUPPORTING DOCUMENTS INCLUDED THE FIRE |
PUMP, THAT IS NOT PART OF THIS PERMIT. |
ALL JOINTS SHALL BE INSPECTED BY THE FIRE |
DEPARTMENT PRIOR TO COVERING. |
|
|
|
7/7/22 PLANS UPLOADED,INCOMING COMPLETE.CD |
7/5/22 APPLICANT INVITED TO PAY FEES AND UPLOAD |
PLANS AO |