Plan Review Details - Permit 22070110
Plan Review Stops For Permit 22070110 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2022-07-18 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-07-18 |
Time |
|
Rev Time |
0.00 |
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-07-18 09:56:01 | FIRE REVIEW COMMENTS: | | THE FIRE PUMP SUPPORTING DOCUMENTS ARE NOT PART OF THIS | | APPROVAL. | | ALL JOINTS SHALL BE INSPECTED BY THE FIRE DEPARTMENT | | PRIOR TO COVERING. | | AT TIME OF INSPECTION, THE CONTRACTOR SHALL HAVE ON | | SITE THE MANUFACTURES SPECIFICATIONS FOR UNDERGROUND | | PIPING INCLUDING TORQUE REQUIREMENTS FOR BOLT | | ASSEMBLIES. | | C. WALKER | | 561-804-4762 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2022-07-08 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-07-08 |
Time |
|
Rev Time |
|
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-07-08 12:23:30 | FIRE REVIEW COMMENTS: | | INDICATE ON THE PLAN THE DISTANCE FROM THE NEAREST FIRE | | HYDRANT TO THE FIRE DEPARTMENT CONNECTION (FDC). NFPA | | 1141 8.1.3 * (2017 EDITION) | | WHERE MUNICIPAL-TYPE WATER SYSTEMS ARE AVAILABLE, FIRE | | DEPARTMENT CONNECTIONS FOR SPRINKLER SYSTEMS DESIGNED | | TO NFPA 13 OR NFPA 13R SHALL BE LOCATED NOT MORE THAN | | 100 FT (30.5 M) ALONG AN APPROVED PATH FROM A FIRE | | HYDRANT AND SHALL BE ARRANGED SO THAT HOSE LINES CAN BE | | READILY AND CONVENIENTLY ATTACHED TO THE INLETS WITHOUT | | INTERFERENCE FROM ANY NEARBY OBJECTS, INCLUDING | | BUILDINGS, SIGNS, FENCES, POSTS, OR OTHER FIRE | | DEPARTMENT CONNECTIONS. | | PROVIDE SUPPORTING MANUFACTURERS DOCUMENTATION FOR PIPE | | SPECIFICATIONS, LISTING, BOLT TORQUE SPECIFICATIONS, | | CORROSION RESISTANCE, ETC. | | THIS PERMIT APPLIES ONLY TO THE UNDERGROUND FIRE LINE. | | THE SUPPORTING DOCUMENTS INCLUDED THE FIRE PUMP, THAT | | IS NOT PART OF THIS PERMIT. | | ALL JOINTS SHALL BE INSPECTED BY THE FIRE DEPARTMENT | | PRIOR TO COVERING. | | OTHER COMMENTS MAY BE FORTHCOMING UPON FURTHER REVIEW. | | C. WALKER | | 561-804-4762 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-07-19 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-07-19 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-07-15 |
Time |
11:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-07-11 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-07-11 |
Time |
08:57 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-07-07 |
Time |
07:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-07-19 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-07-19 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-07-19 |
Time |
11:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2022-07-11 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-07-11 |
Time |
08:56 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-07-11 |
Time |
08:56 |
Sent To |
|
|
Notes |
2022-07-11 09:00:53 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON | | RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A | | DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY | | VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE. WPB | | FBC 107.1; FS 471/481FLORIDA BUILDING CODE 2020 7TH | | EDITION | | | | |
|
|
|