Plan Review Details - Permit 22070110
Plan Review Stops For Permit 22070110
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-07-18 Cont ID  
Sent By cwalker Date 2022-07-18 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-07-18 09:56:01FIRE REVIEW COMMENTS:
 THE FIRE PUMP SUPPORTING DOCUMENTS ARE NOT PART OF THIS
 APPROVAL.
 ALL JOINTS SHALL BE INSPECTED BY THE FIRE DEPARTMENT
 PRIOR TO COVERING.
 AT TIME OF INSPECTION, THE CONTRACTOR SHALL HAVE ON
 SITE THE MANUFACTURES SPECIFICATIONS FOR UNDERGROUND
 PIPING INCLUDING TORQUE REQUIREMENTS FOR BOLT
 ASSEMBLIES.
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-07-08 Cont ID  
Sent By cwalker Date 2022-07-08 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-07-08 12:23:30FIRE REVIEW COMMENTS:
 INDICATE ON THE PLAN THE DISTANCE FROM THE NEAREST FIRE
 HYDRANT TO THE FIRE DEPARTMENT CONNECTION (FDC). NFPA
 1141 8.1.3 * (2017 EDITION)
 WHERE MUNICIPAL-TYPE WATER SYSTEMS ARE AVAILABLE, FIRE
 DEPARTMENT CONNECTIONS FOR SPRINKLER SYSTEMS DESIGNED
 TO NFPA 13 OR NFPA 13R SHALL BE LOCATED NOT MORE THAN
 100 FT (30.5 M) ALONG AN APPROVED PATH FROM A FIRE
 HYDRANT AND SHALL BE ARRANGED SO THAT HOSE LINES CAN BE
 READILY AND CONVENIENTLY ATTACHED TO THE INLETS WITHOUT
 INTERFERENCE FROM ANY NEARBY OBJECTS, INCLUDING
 BUILDINGS, SIGNS, FENCES, POSTS, OR OTHER FIRE
 DEPARTMENT CONNECTIONS.
 PROVIDE SUPPORTING MANUFACTURERS DOCUMENTATION FOR PIPE
 SPECIFICATIONS, LISTING, BOLT TORQUE SPECIFICATIONS,
 CORROSION RESISTANCE, ETC.
 THIS PERMIT APPLIES ONLY TO THE UNDERGROUND FIRE LINE.
 THE SUPPORTING DOCUMENTS INCLUDED THE FIRE PUMP, THAT
 IS NOT PART OF THIS PERMIT.
 ALL JOINTS SHALL BE INSPECTED BY THE FIRE DEPARTMENT
 PRIOR TO COVERING.
 OTHER COMMENTS MAY BE FORTHCOMING UPON FURTHER REVIEW.
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-19 Cont ID  
Sent By mpeterso Date 2022-07-19 Time 11:23 Rev Time 0.00
Received By mpeterso Date 2022-07-15 Time 11:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-11 Cont ID  
Sent By jleahy Date 2022-07-11 Time 08:57 Rev Time 0.00
Received By jleahy Date 2022-07-07 Time 07:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-19 Cont ID  
Sent By mpeterso Date 2022-07-19 Time 11:23 Rev Time 0.00
Received By mpeterso Date 2022-07-19 Time 11:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-11 Cont ID  
Sent By jleahy Date 2022-07-11 Time 08:56 Rev Time 0.00
Received By jleahy Date 2022-07-11 Time 08:56 Sent To  
Notes
2022-07-11 09:00:53FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE. WPB
 FBC 107.1; FS 471/481FLORIDA BUILDING CODE 2020 7TH
 EDITION
  
  