Miscellaneous Information / Notes |
COMMERCIAL ALTERATION |
|
|
2/1/23 CC ISSUED AND EMAILED TO JOEY ATKINSON. |
SCANNING FOR FILENET. ATTACHED IN C+. FILED UNDER |
THE LETTER P. SD |
2/1/23 SENT EMAIL TO FIRE SAYING: CAITLIN, |
PLEASE CHANGE THE P TO AN I FOR THE 1/12/23 131 |
INSPECTION IN COMMUNITY PLUS AND SCHEDULE MR. |
ATKINSON A 131 TODAY IF POSSIBLE. PLEASE |
COORDINATE WITH JOE ATKINSON. HE IS UNABLE TO |
SCHEDULE IT HIMSELF BECAUSE THERE IS A P IN THE |
SYSTEM ALREADY. JPB |
1/31/23 SENT JOE ATKINSON THIS EMAIL FROM FIRE |
(FRANCIS/LEDUC): THIS PROPERTY HAD A FEW CHANGES |
ONSITE THAT DIDN'T MATCH THE PLANS. |
I'M STILL WAITING FOR THE REVISION TO BE SUBMITTED |
IN REGARDS TO THE DOOR SWING INTO THE EXIT |
PATHWAY, AND TWO EXITS THAT WERE CHANGED FROM THE |
ORIGINAL APPROVED PLANS. |
THE CONTRACTOR WAS SUPPOSED TO HAVE THE ENGINEER |
REVIEW AND RESUBMIT. |
THEY ARE NOT READY FOR CO. JPB |
1/13/23 SENT AN EMAIL TO FRANCIS/LEDUC AND CC'D |
JOE ATKINSON, SAYING: WE CANNOT ISSUE A COC FOR |
THE PROJECT IF A REVISED SUBMITTAL IS NEEDED. |
REASON BEING IS THAT THE PROJECT WOULD BE CLOSED |
OUT AND THERE WOULD BE NOTHING TO REVISE. PLEASE |
ENSURE THAT THE CONTRACTOR IS AWARE OF THIS AND |
THEY NEED TO GET THE REVISION SUBMITTED FOR THE |
PROJECT IN ORDER TO RECEIVE A COC. THEY COULD |
RECEIVE A TCO IN THE MEANTIME IF THEY APPLIED. I |
HAVE COPIED JOE ATKINSON ON THIS EMAI, WHO IS THE |
APPLICANT. JPB |
1/13/23 SENT EMAIL TO CAITLIN FRANCIS/LEDUC |
SAYING: THERE IS A NOTE FOR THE 131, "PASS PENDING |
REVISION". I AM UNABLE TO FIND A NOTE INDICATING |
WHAT IS THE REVISION? I SEE NO REVISION PERMIT |
NUMBERS TO SEE IF IT HAS BEEN REVIEWED SO I NEED |
SOME HELP PLEASE, AS TO WHETHER THIS PROJECT IS |
READY FOR A COC? JPB |
1/10/23 SENT EMAIL TO JOE ATKINSON SAYING: THIS |
REQUEST IS DENIED FOR THE FOLLOWING DEFICIENCIES. |
PLEASE DO NOT REQUEST COC UNTIL THESE ARE |
COMPLETED AND PASSED. |
DEFICIENCIES: |
22061537 THERE HAS BEEN NO FINAL ELECTRICAL |
INSPECTION 203. NOTE THAT THE 204 AND 205 |
ELECTRICAL INSPECTIONS FAILED SO WILL NEED TO HAVE |
A PASS IN ORDER TO PRINT A COC. PLEASE SCHEDULE |
ALL THREE OF THESE INSPECTIONS. |
22020991 THERE HAS BEEN NO FINAL FIRE INSPECTION |
131. THIS PERMIT IS NOT CLOSED. JPB |
1/6/23 SENT EMAIL TO JOE ATKINSON SAYING: YOU ARE |
DEFICIENT IN THE AREAS NOTED IN THE ATTACHED |
SPREADSHEET. |
THERE ARE NO ELECTRICAL INSPECTIONS INCLUDING NO |
FINAL FOR THE FIRE ALARM PERMIT. |
THERE IS NO FIRE FINAL 131 FOR THE MASTER PERMIT. |
PLEASE SCHEDULE THESE INSPECTIONS AND PASS BEFORE |
RESUBMITTING FOR A COC. JPB |
4/18/22 REVIEWS COMPLETE, APPLICANT INVITED TO |
DOWNLOAD PLANS, PERMIT CARD UPLOADED. LEM |
4/17/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
4/15/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
RESUBMIT. LEM |
4/10/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
4/6/22REVIEWS COMPLETE,APPLICANT NEEDS TO RESUBMIT |
AO |
3/30/22, PASS FIRE, CRW, WITH PROVISO COMMENTS |
3/29/22 APPLICANT RESUBMITTED DIGITALLY,PLANS |
VERSIONED,INCOMING COMPLETE AO |
3/10/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
RESUBMIT. AO |
3/2/22 FAIL FIRE CLF |
THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L. |
FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING |
COMMENTS: |
|
1) PROVIDE DOOR AND WALL DETAILS FOR DOORS, ROLL |
UP DOORS, WALLS BEING ADDED, AND OR FILLED. |
|
1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW |
CONSTRUCTION, MODIFICATION, OR REHABILITATION, |
CONSTRUCTION DOCUMENTS AND SHOP DRAWINGS SHALL BE |
SUBMITTED, REVIEWED, AND APPROVED PRIOR TO THE |
START OF SUCH WORK AS PROVIDED IN SECTION 1.14. |
|
2) ANY REMOVAL AND/OR CONSTRUCTION OF THE |
CEILING/WALL AREAS MAY REQUIRE AN EVALUATION OR |
MODIFICATION OF THE FIRE SPRINKLER AND FIRE ALARM |
SYSTEMS FOR CODE COVERAGE AND COMPLIANCE BY |
CERTIFIED CONTRACTORS. |
|
3) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR |
FIRE ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE |
PERMITS AND SHOP DRAWINGS BY CERTIFIED |
CONTRACTORS. |
|
4) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL |
REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION |
PERIODS. |
|
5) COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY |
SHALL BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, |
TRAVEL DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END |
CORRIDORS, EXIT SIGNS, EMERGENCY LIGHTING, EXITS |
LEADING TO A PUBLIC WAY, FIRE EXTINGUISHER |
LOCATIONS, AND ALL FIRE SAFETY FEATURES AND |
EQUIPMENT. |
|
6) FOR THE RECORD PLEASE PROVIDE THE EXISTING EXIT |
SIGNS AND EMERGENCY LIGHTING FOR EVALUATION PER |
NFPA 101 CHAPTER 7. |
|
|
|
CAITLIN L. FRANCIS |
FIRE INVESTIGATOR |
561-804-4728 |
[email protected] |
|
|
|
2/23/22 PLANS UPLOADED,INCOMING COMPLETE.CD |
2/22/22 RECEIVED EXPEDITE REQUEST. LEM |
2/18/22 APPLICANT INVITED TO PAY FEES AND UPLOAD |
PLANS AO |