Miscellaneous Information / Notes |
INTERIOR DEMO & RENOVATE EXISTING SPACE |
|
|
|
3/10/23 CC ISSUED AND EMAILED TO TAYLOR HODES. |
SCANNING FOR FILENET. ATTACHMENT IN C+. FILED |
UNDER "I". JB/KP |
7/21/22 REVIEWS COMPLETE, APPLICANT INVITED TO |
DOWNLOAD PLANS, PERMIT CARD UPLOADED. LEM |
7/5/22 APPLICANT RESUBMITTED DIGITALLY,PLANS |
UPLOADED TO SIG FOLDER VERSIONED,INCOMING COMPLETE |
AO |
6/23/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
RESUBMIT. LEM |
5/23/22, PASS FIRE, CRW |
5/21/22 APPLICANT RESUBMITTED DIGITALLY,INCOMING |
COMPLETE AO |
4/5/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
RESUBMIT. LEM |
3/14/22, PASS, CRW |
3/11/22 APPLICANT RESUBMITTED DIGITALLY,INCOMING |
COMPLETE AO |
2/14/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
RESUBMIT. LEM |
1/24/22, FAIL FIRE, CRW, FIRE PROVISO NOTES: |
1.COOKING EQUIPMENT USED IN PROCESSES PRODUCING |
SMOKE OR GREASE LADEN VAPORS SHALL BE EQUIPPED |
WITH AN EXHAUST SYSTEM THAT COMPLIES WITH ALL THE |
EQUIPMENT AND PERFORMANCE REQUIREMENTS OF THIS |
STANDARD. NFPA 96, 4.1.1COOKING EQUIPMENT THAT |
PRODUCES GREASE LADEN VAPORS AND THAT MIGHT BE AA |
SOURCE OF IGNITION OF GREASE IN THE HOOD, GREASE |
REMOVAL DEVICE, OR DUCT SHALL BE PROTECTED BY |
FIRE-EXTINGUISHING EQUIPMENT. NFPA 96, 10.1.2FOR |
CLARIFICATION AND THE OFFICIAL RECORD, PROVIDE A |
DETAILED DESCRIPTION OF THE USE THE DEMONSTRATION |
KITCHEN.2.ALL FIRE SPRINKLER AND/OR FIRE ALARM |
WORK SHALL BE PERFORMED UNDER SEPARATE PERMITS AND |
SHOP DRAWINGS. THE WORK IS TO BE PERFORMED BY |
QUALIFIED, PROPERLY LICENSED CONTRACTORS.3.ANY |
IMPAIRMENTS TO THE FIRE/LIFE SAFETY SYSTEMS IN |
EXCESS OF 4 HOURS DURATION SHALL REQUIRE A FIRE |
WATCH TO BE IMPLEMENTED. |
|
|
1/7/22 PLANS UPLOADED,INCOMING COMPLETE.CD |
12/30/21 APPLICANT INVITED TO PAY FEES AND UPLOAD |
PLANS. AO |