| Miscellaneous Information / Notes |
| RENOVATION OF EXISTING STRUCTURE AND EXPANSION |
| |
| |
| |
| 12/30/22 CUSTOMER REQUESTED TO TRANSFER CREDIT |
| FROM PERMIT 21110639 TO PAY FOR PERMIT 22121402, |
| SUBMITTED TRANSFER FORM TO LUCY. AM |
| 9/27/22 PERMIT ISSUED. LEM |
| 9/26/22 PLAN REVIEW COMPLETE, WAITING ON |
| CONTRACTOR UPDATE AO |
| 9/19/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT ENGINEERING. LEM |
| 8/29/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
| 8/4/22 REVIEWS COMPLETE, APPLICANT INVITED TO |
| RESUBMIT AO |
| 6/29/22, PASS FIRE, CRW, FIRE REVIEW PROVISO NOTE |
| (6/29/22): |
| TO ADVANCE THIS PROJECT FORWARD, THE FIRE MARSHAL |
| WILL APPROVE THE SUBMITTED LETTER FROM RBK FIRE |
| SYSTEMS DATED 6/28/2022 STATING THE SCOPE OF WORK |
| IN VERY GENERAL TERMS. THE SUBMITTED LETTER DOES |
| NOT MEET WITH THE REQUIREMENTS OF FLORIDA |
| ADMINISTRATIVE CODE, 61G15-30. |
| THE SUBMITTED LETTER LACKED SUFFICIENT DESIGN |
| CRITERIA AND WAS NOT SEALED/STAMPED. THESE ITEMS |
| MUST BE ADDRESSED AND INCLUDED UNDER THE MASTER |
| PERMIT AS WELL AS THE SEPARATE PERMIT AND SHOP |
| DRAWINGS FOR THE ENTIRE FIRE SPRINKLER SYSTEM FOR |
| THIS PROJECT. |
| |
| |
| 6/28/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
| 5/23/22 ADJUSTED VALUE FROM $691908 TO $552808 |
| ($3600 FENCE, $52K LANDSCAPING, $30K ENGINEERING, |
| $54K FURNISHINGS THAT ARE NOT PERMANENTLY |
| INSTALLED), UPLOADED COST BREAKDOWN TO FILE SH |
| 4/19/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT AO |
| 3/16/22 FAILED BY FIRE WITH COMMENTS.PML |
| 3/13/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
| 1/26/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT. LEM |
| 12/27/21, FAIL FIRE, CRW,EGRESS DOORS SERVING 100 |
| OR MORE PERSONS SHALL BE EQUIPPED WITH PANIC |
| HARDWARE. FLORIDA FIRE PREVENTION CODE 7TH |
| EDITION, LIFE SAFETY CODE, 12.2.2.2.3 |
| WHERE THE OCCUPANT LOAD EXCEEDS 100, THE ASSEMBLY |
| OCCUPANCY SHALL BE PROTECTED THROUGHOUT BY AN |
| APPROVED, SUPERVISED AUTOMATIC FIRE SPRINKLER |
| SYSTEM. FLORIDA FIRE PREVENTION CODE 7TH EDITION, |
| LIFE SAFETY CODE 12.3.5.1 |
| ON ANY STORY WITH REHABILITATION WORK AREAS |
| INVOLVING OVER 50 PERCENT OF THE AREA OF THE |
| STORY, A SPRINKLER SYSTEM SHALL BE PROVIDED |
| THROUGHOUT THE STORY IN ACCORDANCE WITH THE |
| REQUIREMENTS OF OTHER SECTIONS OF THIS CODE |
| APPLICABLE TO NEW CONSTRUCTION FOR THE OCCUPANCY. |
| FLORIDA FIRE PREVENTION CODE 7TH EDITION, LIFE |
| SAFETY CODE 43.6.4.2 |
| SHEET A101 FLOOR PLAN KEY NOTES #17 INDICATES A |
| GATE WITH ALARM. PROVIDE MORE DETAIL ON THE |
| LOCKING ARRANGEMENT FOR THIS GATE FOR COMPLIANCE |
| WITH FLORIDA FIRE PREVENTION CODE 7TH EDITION, |
| LIFE SAFETY CODE, 12.2.2 |
| |
| |
| |
| 12/13/21 PLANS CORRECTED, INCOMING COMPLETE.CD |
| 12/10/21 PLANS REJECTED,NEED TO PROPERLY NAME |
| PLANS SHEETS IN DRAWING FOLDER.CUSTOMER EMAILED TO |
| CORRECT.CD |
| 11/15/21 APPLICANT INVITED TO PAY FEES AND UPLOAD |
| PLANS / DOCUMENTS. CC |
| |