Permit Information - Permit 16021074

Loading permit details...

Permit Information
Permit Number 16021074 Property ID 74424312030010230
Permit Desc FA Balance Due $0.00
Property Address 3171 VILLAGE BLVD Status Revoked

Permit Plan Reviews Inspections Fees Contractors All
Permit
Permit Information
Application Date 2016-02-29 Operator gdorsan
Issued Date   Operator  
Master Number   Project Number  
C.O. Number   Operator  
C.O. Issued  
C-404 Type   Usage Class PRIVATE
Applied Value 850 Units 0
Calculated Value 0 Contractor ID FL00966
Property On Permit
Property ID 74424312030010230    
Building Ext.  
Address 3171 VILLAGE BLVD
City WEST PALM BEACH
State FL
Zip Code 33409
Owner On Permit
Name MORGUARD VILLAGE CROSSING LLC
Address 551 S POMPANO PKWY
City POMPANO BEACH Type Private
State FL Zip Code 33069 3018
Miscellaneous Information / Notes
INSTALL NEW FIRE ALARM PANEL
 
3/15/23 REVOKED APP STAMPED VOID, ROUTED TO
FILENET AND DISCARDED.CD
4/18/22 RECIEVED REQUEST TO VOID PERMIT TL
 
08/01/2018 ABANDON APPLICATION EMAIL SENT, PERMIT
PACKET NEAR STATION 1; LABELED, "ABAN/EXP
PERMNITS." DE'AIRA CORIOLANT
3/8/2017 PERMIT NEVER PICKED UP, ABANDON
APPLICATION EMAIL SENT, PERMIT PACKET AT RMG DESK.
3/4/16 PLAN REVIEW COMPLETE, CUSTOMER NEEDS TO
RESUBMIT, FILED UNDER SMALL DENIED "L". CP
3/2/16 - FAIL
1. PER NFPA 72 2010 EDITION 18.5.4.3.2
NOTIFICATION APPLIANCES MUST BE SYNCHRONIZED.
 
2. PER NFPA 72 2010 EDITION 18.4.5.1 A MINIMUM OF
75 DBA AT PILLOW TOP MUST BE ATTAINED IN ALL
SLEEPING AREAS
 
3. PER NFPA 101 FIFTH EDITION 31.3.4.3.5.1 LOCAL
ALARMS MUST HAVE APPROVED SIGNAGE ABOVE EACH PULL
STATION AND A MINIMUM OF ONE NOTIFICATION
APPLIANCE ON THE EXTERIOR WALL OF THE BUILDING.
 
4. PER NFPA 72 A SMOKE OR HEAT DETECTOR IS
REQUIRED ABOVE THE FACP.
 
SENT TO ELECTRICAL. GJT