Plan Review Details - Permit 16021074
Plan Review Stops For Permit 16021074
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-04 Cont ID  
Sent By vperez Date 2016-03-04 Time 09:49 Rev Time 0.00
Received By vperez Date 2016-03-04 Time 09:49 Sent To  
Notes
2016-03-04 09:49:35INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADDRESS FIRE COMMENTS FOR AN ELECTRICAL
 APPROVAL
 2. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-03 Cont ID  
Sent By vperez Date 2016-03-04 Time 09:49 Rev Time  
Received By   Date 2016-03-03 Time   Sent To E
Notes
2016-03-03 09:05:31FAIL
  
 1. PER NFPA 72 2010 EDITION 18.5.4.3.2 NOTIFICATION
 APPLIANCES MUST BE SYNCHRONIZED.
 2. PER NFPA 72 2010 EDITION 18.4.5.1 A MINIMUM OF 75
 DBA AT PILLOW TOP MUST BE ATTAINED IN ALL SLEEPING
 AREAS
 3. PER NFPA 101 FIFTH EDITION 31.3.4.3.5.1 LOCAL ALARMS
 MUST HAVE APPROVED SIGNAGE ABOVE EACH PULL STATION AND
 A MINIMUM OF ONE NOTIFICATION APPLIANCE ON THE EXTERIOR
 WALL OF THE BUILDING.
 4. PER NFPA 72 A HEAT OR SMOKE DETECTOR IS REQUIRED
 ABOVE THE FACP.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-04 Cont ID  
Sent By vperez Date 2016-03-04 Time 09:49 Rev Time 0.00
Received By vperez Date 2016-03-04 Time 09:49 Sent To FIRE
Notes
2016-03-04 09:49:553/4 TO CAROLINE