Permit Information - Permit 15071174

Loading permit details...

Permit Information
Permit Number 15071174 Property ID 74424302000003060
Permit Desc MECH Balance Due $0.00
Property Address 5851 45TH ST Status Closed

Permit Plan Reviews Inspections Fees Contractors All
Permit
Permit Information
Application Date 2015-07-30 Operator lakeisha
Issued Date 2015-08-19 Operator andrian
Master Number 15020476 Project Number  
C.O. Number   Operator  
C.O. Issued  
C-404 Type   Usage Class PRIVATE
Applied Value 0 Units 0
Calculated Value 0 Contractor ID CMC1249780
Property On Permit
Property ID 74424302000003060    
Building Ext.  
Address 5851 45TH ST
City WEST PALM BEACH
State FL
Zip Code 33407
Owner On Permit
Name COSTCO WHOLESALE CORP
Address 999 LAKE DR
City ISSAQUAH Type Private
State WA Zip Code 98027-8990
Miscellaneous Information / Notes
REFRIGERATION FOR MASTER# 15020476
 
 
 
08/19/15 P/U ASM
8/19/15- READY IN LARGE T/NOTIFIED CONTR/CC
8/19/15 - PASSED ELECTRICAL REVIEW. SENT TO
MECHANICAL. MA
8/14/15 RESUB ADDRESSING DENIED COMMENTS, MS
8/11/15 DENIED MECH PASSED WITH PROVISO/CALLED
CONTR/IN SMALL "DENIED" T (TBD)/CC:/WL
 
MECHANICAL PASSED WITH PROVISO FOR REQUIRED
VENTILATION.
PRIOR TO 1ST INSPECTION, THE ENGINEER OF RECORD
SHALL PROVIDE A CALCULATION TO CERTIFY THAT THE
AMOUNT OF AMMONIA REFRIGERANT IN POUNDS IN THE WET
ADDITION DOES NOT EXCEED THE ALLOWABLE AMOUNT PER
TABLE 1103.1 FBC-14 MECHANICAL- 0.014 PER
1000CUBIC FT.
 
1104.2 MACHINERY ROOM.
EXCEPT AS PROVIDED IN SECTIONS 1104.2.1 AND
1104.2.2, ALL COMPONENTS CONTAINING THE
REFRIGERANT SHALL BE LOCATED EITHER OUTDOORS OR IN
A MACHINERY ROOM WHERE THE QUANTITY OF REFRIGERANT
IN AN INDEPENDENT CIRCUIT OF A SYSTEM EXCEEDS THE
AMOUNTS SHOWN IN TABLE 1103.1. FOR REFRIGERANT
BLENDS NOT LISTED IN TABLE 1103.1, THE SAME
REQUIREMENT SHALL APPLY WHEN THE AMOUNT FOR ANY
BLEND COMPONENT EXCEEDS THAT INDICATED IN TABLE
1103.1 FOR THAT COMPONENT. THIS REQUIREMENT SHALL
ALSO APPLY WHEN THE COMBINED AMOUNT OF THE BLEND
COMPONENTS EXCEEDS A LIMIT OF 69,100 PARTS PER
MILLION (PPM) BY VOLUME. MACHINERY ROOMS REQUIRED
BY THIS SECTION SHALL BE CONSTRUCTED AND
MAINTAINED IN ACCORDANCE WITH SECTION 1105 FOR
GROUP A1 AND B1 REFRIGERANTS AND IN ACCORDANCE
WITH SECTIONS 1105 AND 1106 FOR GROUP A2, B2, A3
AND B3 REFRIGERANTS.
 
1106.3 AMMONIA ROOM VENTILATION.
VENTILATION SYSTEMS IN AMMONIA MACHINERY ROOMS
SHALL BE OPERATED CONTINUOUSLY AT THE EMERGENCY
VENTILATION RATE DETERMINED IN ACCORDANCE WITH
SECTION 1105.6.3.2.
 
PLEASE NOTE THAT A REVISION TO THIS PERMIT WILL BE
REQUIRED FOR ANY MODIFICATIONS TO THE THE WET
ADDITION OR EXISTING MACHINERY ROOM.
 
 
8/10/15 DENIED ELECTRICAL REVIEW. CONTRACTOR
NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "W".
MA
8/5/15- MECH DENIED/SENT TO ELECT/CC
8/5/15 CHANGED PERMIT TYPE TO MECH. NEED A
SEPARATE PERMIT APPLICATION. ORIGINALLY RECEIVED
AS A REVISION. SAK
7/30/15 REQUEST FOR EXPEDITED REVIEW RECEIVED. LWL


Account Summary | Usage Policy | Privacy Policy