Plan Review Notes
Plan Review Notes For Project Z22080028
Project Number Z22080028
Review Stop PU-CS
Sequence Number 1
Notes
Date Text
2022-09-02 11:40:23PLEASE PROVIDE WRITTEN RESPONSES THE FOLLOWING:
 -ADD LEGEND TO EACH ENGINEERING PLAN SHEET SHOWING
 SYMBOLS AND LINES USED THAT ARE NOT OTHERWISE LABELED.
 -SHOW UTILITY EASEMENTS ON SHEET C05. BACKFLOW
 ASSEMBLIES SHOULD NOT BE IN UTILITY EASEMENTS.
 -CALLOUT THE RP BACKFLOW ASSEMBLIES FOR THE PROPOSED 1
 INCH METERED WATER SERVICES. ENSURE LABEL HAS SIZING.
 -SHOW AND LABEL SEWER LATERAL CLEANOUTS.
 -IS THE 2 INCH METER FOR IRRIGATION? IF NOT, IS A
 METERED IRRIGATION WATER SERVICE NEEDED?
 -ON DEMO PLAN SHOW AND EXISTING METERED WATER SERVICES
 AND LABEL WHAT IS HAPPENING TO THEM.
 -PROVIDE CLEARANCE DISTANCE BETWEEN SOUTHERN BUSH AND
 BACKFLOW ASSEMBLY SHOWN ON LANDSCAPING PLAN L2.0.
 -SHOW AND LABEL FDC ON PLANS IF ANY ARE NEEDED OR
 REQUIRED.
 -SHOW AND LABEL ALL EXISTING UTILITY POLES, LIGHT
 POLES, AND GUY WIRES NEAR PROPERTY ON ENGINEERING PLAN
 SHEETS IF THEY WILL REMAIN.
 -LABEL THE STREETS ON DEMO PLAN.
 -ONE OF THE STORMWATER LINES ON DIXIE SHOWS IT IN CLOSE
 PROXIMITY TO WATER MAIN. IS THAT CORRECT?
 -VERIFY THERE IS NO UTILITY OR FPL EASEMENTS RUNNING
 ALONG ALLEY.
 -ON AUTOTURN EXHIBIT, PLEASE SHOW UTILITY VAC TRUCK 7
 FEET WIDE, 13 FEET HIGH, AND 36 FOOT LONG CAN
 SUCCESSFULLY NAVIGATE THROUGH PROPOSED ONE WAY ALLEY
 TURN.
 -IF THERE WILL BE ANY GREASE TRAPS OUTSIDE BUILDING,
 THEN SHOW AND LABEL ON PLANS.
 -MAY HAVE TO GRANT UTILITY EASEMENT FOR PROPOSED
 SANITARY SEWER MAIN.
 -LABEL ADJACENT PROPERTY ADDRESSES ON ENGINEERING PLAN
 SHEETS.
 -SHOW EXISTING SEWER LATERALS AND LABEL WHAT IS
 HAPPENING TO THEM.
 RESPECTFULLY,
 MARK HURLEY [email protected]
  