2022-09-02 11:40:23 | PLEASE PROVIDE WRITTEN RESPONSES THE FOLLOWING: |
| -ADD LEGEND TO EACH ENGINEERING PLAN SHEET SHOWING |
| SYMBOLS AND LINES USED THAT ARE NOT OTHERWISE LABELED. |
| -SHOW UTILITY EASEMENTS ON SHEET C05. BACKFLOW |
| ASSEMBLIES SHOULD NOT BE IN UTILITY EASEMENTS. |
| -CALLOUT THE RP BACKFLOW ASSEMBLIES FOR THE PROPOSED 1 |
| INCH METERED WATER SERVICES. ENSURE LABEL HAS SIZING. |
| -SHOW AND LABEL SEWER LATERAL CLEANOUTS. |
| -IS THE 2 INCH METER FOR IRRIGATION? IF NOT, IS A |
| METERED IRRIGATION WATER SERVICE NEEDED? |
| -ON DEMO PLAN SHOW AND EXISTING METERED WATER SERVICES |
| AND LABEL WHAT IS HAPPENING TO THEM. |
| -PROVIDE CLEARANCE DISTANCE BETWEEN SOUTHERN BUSH AND |
| BACKFLOW ASSEMBLY SHOWN ON LANDSCAPING PLAN L2.0. |
| -SHOW AND LABEL FDC ON PLANS IF ANY ARE NEEDED OR |
| REQUIRED. |
| -SHOW AND LABEL ALL EXISTING UTILITY POLES, LIGHT |
| POLES, AND GUY WIRES NEAR PROPERTY ON ENGINEERING PLAN |
| SHEETS IF THEY WILL REMAIN. |
| -LABEL THE STREETS ON DEMO PLAN. |
| -ONE OF THE STORMWATER LINES ON DIXIE SHOWS IT IN CLOSE |
| PROXIMITY TO WATER MAIN. IS THAT CORRECT? |
| -VERIFY THERE IS NO UTILITY OR FPL EASEMENTS RUNNING |
| ALONG ALLEY. |
| -ON AUTOTURN EXHIBIT, PLEASE SHOW UTILITY VAC TRUCK 7 |
| FEET WIDE, 13 FEET HIGH, AND 36 FOOT LONG CAN |
| SUCCESSFULLY NAVIGATE THROUGH PROPOSED ONE WAY ALLEY |
| TURN. |
| -IF THERE WILL BE ANY GREASE TRAPS OUTSIDE BUILDING, |
| THEN SHOW AND LABEL ON PLANS. |
| -MAY HAVE TO GRANT UTILITY EASEMENT FOR PROPOSED |
| SANITARY SEWER MAIN. |
| -LABEL ADJACENT PROPERTY ADDRESSES ON ENGINEERING PLAN |
| SHEETS. |
| -SHOW EXISTING SEWER LATERALS AND LABEL WHAT IS |
| HAPPENING TO THEM. |
| RESPECTFULLY, |
| MARK HURLEY [email protected] |
| |
|