2022-08-29 12:55:15 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| BEACH FIRE DEPARTMENT. |
| |
| THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| ARE SUBMITTED FOR PERMIT. |
| |
| THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| PROPOSED PROJECT SITE PLAN. |
| |
| WITH THE LIMIT BUIDING INFORMATION PROVIDED, THE |
| FOLLOWING COMMENTS ARE INTENDED TO PROVIDE GUIDANCE FOR |
| BUILDING PLAN SUBMITTAL. |
| |
| 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE |
| PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A |
| PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED |
| TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN |
| STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY |
| MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER |
| PROTECTION. |
| |
| 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| ALL CONSTRUCTION ACTIVITIES. |
| |
| 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM |
| ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. |
| ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND |
| AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT |
| WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| |
| 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE |
| REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE |
| ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| |
| 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY |
| WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION |
| CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE |
| CODES. |
| |
| 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE |
| OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE. |
| |
| 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE |
| LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER |
| SUPPLY IS EXISTING OR WILL BE PROVIDED. |
| |
| 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS |
| DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED |
| ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF |
| FIRE PREVENTION. |
| |
| THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL |
| BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED |
| WITH THE BUREAU OF FIRE PREVENTION. |
| |
| 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER |
| THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY |
| ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, |
| ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G |
| AND SUBMITTED WITH THE MASTER PERMIT. |
| |
| 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE |
| LOCATIONS SHALL MEET AND BE INSTALLED PER THE |
| REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH |
| THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS |
| OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING |
| AND ZONING OFFICE. |
| |
| 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL |
| BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF |
| TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY |
| LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE |
| EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES |
| AND EQUIPMENT. |
| |
| 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE |
| SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY |
| DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. |
| |
| 12. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7 |
| KEYWAY SYSTEM. |
| |
| ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S |
| EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA |
| B44, SAFETY CODE FOR ELEVATORS. |
| |
| ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN |
| WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL |
| LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET |
| MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER |
| ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN |
| AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE |
| IN THE HORIZONTAL POSITION. |
| |
| 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. |
| NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| RADIO ENHANCEMENT SERVICES. |
| 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| DETERMINED BY THE AHJ. |
| |
| CONTACT WILL NEED TO BE MADE TO MARK FILLA, PALM BEACH |
| COUNTY PUBLIC SAFETY RADIO SYSTEMS MANAGER, |
| [email protected], 561-233-0837; AS OUR RADIOS OPERATE |
| ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND |
| INSTALLATION INSTRUCTIONS. |
| |
| 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT |
| DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. |
| |
| 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING |
| PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH |
| THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
|