2021-03-04 09:50:53 | 1. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY |
| OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC |
| RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF |
| YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE |
| MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL |
| IN THE WPB ENGINEERING SERVICES DEPARTMENT AT |
| [email protected] OR 561-494-1079 FOR FURTHER |
| ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION |
| ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD |
| SURVEY, POT-HOLING, SOFT DIGS ETC. |
| 2. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH |
| CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, |
| STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR |
| MORE INFORMATION, REFER TO THE LINK BELOW: |
| HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI |
| CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL |
| 3. PLEASE SUBMIT PRELIMINARY UTILITY ENGINEERING PLANS. |
| PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF |
| ALL WATER, STORM WATER, AND SANITARY AND SEWER LINES, |
| INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND |
| SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, |
| METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE |
| SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING |
| GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, |
| ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL |
| INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER |
| LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE |
| PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN |
| VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. |
| ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND |
| PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER |
| OPTIC, ELECTRIC, GAS, AND CABLEVISION & |
| TELECOMMUNICATION FACILITIES LOCATED ON THE |
| RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL |
| UTILITY CROSSINGS. CUT AND CAP UTILITIES NOT IN USE, |
| AND REMOVE ANY ABANDONED UTILITY LINES LARGER THAN 2 |
| INCHES FROM CITY RIGHT OF WAY. |
| 4. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE |
| DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB |
| DEVELOPMENT APPLICATION). |
| 5. SHOW PROPOSED DUMPSTER ENCLOSURE PER CURRENT CITY OF |
| WPB STANDARD DETAIL GC-7. |
| 6. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY |
| SEWER ARE REQUIRED. |
| 7. PLEASE CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA |
| AND FIRE BACKFLOW PREVENTER AS DCDA. |
| 8. PROVIDE VERTICAL DATUM AND DATUM CONVERSION |
| INFORMATION (NAVD 1988 AND NGVD 1929). |
| 9. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND |
| PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM |
| AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE |
| PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER. |
| 10. IS THERE A PROPOSED SANITARY CONNECTION? IF SO |
| PROVIDE CCTV VIDEO OF EXISTING SANITARY AND STORM SEWER |
| ALONG ENTIRE PROJECT FRONTAGE. |
| 11. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE |
| EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. |
| 12. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE |
| ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER |
| METER AND BACKFLOW PREVENTION. |
| 13. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES |
| OF WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. |
| 14. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING |
| APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT |
| SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING |
| SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED |
| LEAD-FREE DESIGN. |
| 15. FOR FORMAL ENGINEERING SUBMITTAL CLEARLY SHOW ROAD |
| RIGHT OF WAY. |
| 16. FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY MAINS |
| ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY |
| LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT |
| PARCELS. |
| 18. FOR FORMAL ENGINEERING SUBMITTAL, IF WATER MAINS |
| ARE BEING REPLACED IN ROW, SHOW ADJACENT PARCEL |
| ADDRESSES. |
| 19. FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO |
| PROVIDE 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH |
| SIDE OF PROPOSED TRENCH IN CITY MAINTAINED ROADWAY |
| AREAS PER CITY OF WPB STANDARD DETAIL GC-9. |
| 20. PLEASE NOTE THAT A PRE-PPRC-SUBMITTAL MEETING WITH |
| ENGINEERING SERVICES IS HIGHLY SUGGESTED. |
| 21. STANDARD DETAILS ARE ILLEGIBLE, PLEASE CONTACT |
| [email protected] FOR CAD FILE VERSIONS TO USE. |
| 22. PLEASE RESPOND TO ALL COMMENTS IN WRITING. |
| |
| |
| |
| |
| THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD |
| CUSTOMER SERVICE SUPERVISOR |
| CITY OF WEST PALM BEACH PUBLIC UTILITIES, 561-822-2262 |
| [email protected] |
| |
| PLEASE RESPOND TO THE FOLLOW COMMENTS IN WRITING: |
| |
| -NEED ADD WATER DEMAND CALCULATIONS TO ENGINEERING |
| PLAN. |
| |
| -ON WEST SIDE OF PROPERTY THERE IS A CHAIN LINK FENCE |
| THAT GOES OFF THE PROPERTY AND ALSO EXTENDS INTO A |
| MAINTENANCE EASEMENT. IS THE FENCE PREVENTING |
| MAINTENANCE? |
| |
| -IS THE 8INCH VCP SANITARY LINE PRIVATELY-OWNED OR |
| CITY-OWNED? PLEASE UPDATE LABEL SIMILARLY. IF SANITARY |
| LINE IS CITY-OWNED, RELOCATE FENCE OUT OF 12FOOT |
| UTILITY EASEMENT AS IT IS IMPEDING MAINTENANCE. |
| |
| -DEMO PLAN SAYS THERE IS A MONITORING WELL ON SITE THAT |
| WILL REMAIN. WILL IT BE USED FOR SAMPLING WATER, OR |
| WILL WATER BE PUMPED FOR USE ON SITE? |
| |
| -DRAW AND LABEL EXISTING WATER SERVICE PIPING. |
| |
| -VERIFY THERE WILL BE NO FIRE SPRINKLERS IN BUILDING. |
| |
| -IS A SEPARATE METERED IRRIGATION WATER SERVICE NEEDED? |
| |
| -DOES ADA SURFACE NEED TO BE ON THE SIDES OF THE |
| DRIVEWAY ENTRANCE ON SIDEWALK? |
| |
| -WATER SERVICE STANDARD DETAILS ARE OLD REVISION AND |
| NOT CLEARLY VIEWABLE. PLEASE UPDATE AND MAKE READABLE. |
| |
| -IS THERE A SEPARATE PEDESTRIAN GATE, OR DO ALL |
| VISITORS GO THROUGH THE ROLLING DRIVEWAY GATE? |
| |
| -IS THE 6FOOT BLACK CHAINLINK FENCE EXISTING OR |
| PROPOSED? |
| |
| -LABEL BACKFLOW ASSEMBLY EXISTING OR PROPOSED. |
| |
| -OUR RECORDS SHOW NO EXISTING WATER METER OR ACTIVE |
| USAGE ACCOUNT. THERE MAY BE AN EXISTING WATER SERVICE. |
| ACCOUNTS WOULD NEED SETUP AND FEES/CHARGES PAID WITH |
| CITY WPB UTILITY BILLING. |
| |
| -WHAT IS BEING CONSTRUCTED IN PHASE II LOCATION? WOULD |
| VISITORS USE THE SAME PARKING AND ENTRANCE? |
| |
| -BACKFLOW ASSEMBLY APPEARS TO HAVE LOCATION CONFLICT |
| WITH FENCE. |
| |
| -MAKE SURE ROLLING GATE DOES NOT EXTEND INTO 12FOOT |
| UTILITY EASEMENT OR HIT BACKFLOW ASSEMBLY. |
| |
| -FOR FORMAL ENGINEERING SUBMITTAL, LABEL WATER MAIN |
| PIPE SIZE AND MATERIAL TYPE. |
| |
| -EXISTING FIRE HYDRANT MAY BE MISSING FROM ENGINEERING |
| PLAN ON 27TH PL. |
| |
| -WHAT IS HAPPENING TO THE EXISTING CONCRETE DRIVEWAY |
| APPROACH TO THE EAST OF THE PROPOSED BUILDING? |
| |
|