Plan Review Notes
Plan Review Notes For Project Z21020017
Project Number Z21020017
Review Stop ENG - PPRC
Sequence Number 1
Notes
Date Text
2021-03-04 09:50:531. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
 2. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
 3. PLEASE SUBMIT PRELIMINARY UTILITY ENGINEERING PLANS.
 PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF
 ALL WATER, STORM WATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND
 PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS. CUT AND CAP UTILITIES NOT IN USE,
 AND REMOVE ANY ABANDONED UTILITY LINES LARGER THAN 2
 INCHES FROM CITY RIGHT OF WAY.
 4. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 5. SHOW PROPOSED DUMPSTER ENCLOSURE PER CURRENT CITY OF
 WPB STANDARD DETAIL GC-7.
 6. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 7. PLEASE CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA
 AND FIRE BACKFLOW PREVENTER AS DCDA.
 8. PROVIDE VERTICAL DATUM AND DATUM CONVERSION
 INFORMATION (NAVD 1988 AND NGVD 1929).
 9. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 10. IS THERE A PROPOSED SANITARY CONNECTION? IF SO
 PROVIDE CCTV VIDEO OF EXISTING SANITARY AND STORM SEWER
 ALONG ENTIRE PROJECT FRONTAGE.
 11. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS.
 12. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER
 METER AND BACKFLOW PREVENTION.
 13. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES
 OF WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS.
 14. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 15. FOR FORMAL ENGINEERING SUBMITTAL CLEARLY SHOW ROAD
 RIGHT OF WAY.
 16. FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY MAINS
 ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY
 LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT
 PARCELS.
 18. FOR FORMAL ENGINEERING SUBMITTAL, IF WATER MAINS
 ARE BEING REPLACED IN ROW, SHOW ADJACENT PARCEL
 ADDRESSES.
 19. FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO
 PROVIDE 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH
 SIDE OF PROPOSED TRENCH IN CITY MAINTAINED ROADWAY
 AREAS PER CITY OF WPB STANDARD DETAIL GC-9.
 20. PLEASE NOTE THAT A PRE-PPRC-SUBMITTAL MEETING WITH
 ENGINEERING SERVICES IS HIGHLY SUGGESTED.
 21. STANDARD DETAILS ARE ILLEGIBLE, PLEASE CONTACT
 [email protected] FOR CAD FILE VERSIONS TO USE.
 22. PLEASE RESPOND TO ALL COMMENTS IN WRITING.
  
  
  
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES, 561-822-2262
 [email protected]
  
 PLEASE RESPOND TO THE FOLLOW COMMENTS IN WRITING:
  
 -NEED ADD WATER DEMAND CALCULATIONS TO ENGINEERING
 PLAN.
  
 -ON WEST SIDE OF PROPERTY THERE IS A CHAIN LINK FENCE
 THAT GOES OFF THE PROPERTY AND ALSO EXTENDS INTO A
 MAINTENANCE EASEMENT. IS THE FENCE PREVENTING
 MAINTENANCE?
  
 -IS THE 8INCH VCP SANITARY LINE PRIVATELY-OWNED OR
 CITY-OWNED? PLEASE UPDATE LABEL SIMILARLY. IF SANITARY
 LINE IS CITY-OWNED, RELOCATE FENCE OUT OF 12FOOT
 UTILITY EASEMENT AS IT IS IMPEDING MAINTENANCE.
  
 -DEMO PLAN SAYS THERE IS A MONITORING WELL ON SITE THAT
 WILL REMAIN. WILL IT BE USED FOR SAMPLING WATER, OR
 WILL WATER BE PUMPED FOR USE ON SITE?
  
 -DRAW AND LABEL EXISTING WATER SERVICE PIPING.
  
 -VERIFY THERE WILL BE NO FIRE SPRINKLERS IN BUILDING.
  
 -IS A SEPARATE METERED IRRIGATION WATER SERVICE NEEDED?
  
 -DOES ADA SURFACE NEED TO BE ON THE SIDES OF THE
 DRIVEWAY ENTRANCE ON SIDEWALK?
  
 -WATER SERVICE STANDARD DETAILS ARE OLD REVISION AND
 NOT CLEARLY VIEWABLE. PLEASE UPDATE AND MAKE READABLE.
  
 -IS THERE A SEPARATE PEDESTRIAN GATE, OR DO ALL
 VISITORS GO THROUGH THE ROLLING DRIVEWAY GATE?
  
 -IS THE 6FOOT BLACK CHAINLINK FENCE EXISTING OR
 PROPOSED?
  
 -LABEL BACKFLOW ASSEMBLY EXISTING OR PROPOSED.
  
 -OUR RECORDS SHOW NO EXISTING WATER METER OR ACTIVE
 USAGE ACCOUNT. THERE MAY BE AN EXISTING WATER SERVICE.
 ACCOUNTS WOULD NEED SETUP AND FEES/CHARGES PAID WITH
 CITY WPB UTILITY BILLING.
  
 -WHAT IS BEING CONSTRUCTED IN PHASE II LOCATION? WOULD
 VISITORS USE THE SAME PARKING AND ENTRANCE?
  
 -BACKFLOW ASSEMBLY APPEARS TO HAVE LOCATION CONFLICT
 WITH FENCE.
  
 -MAKE SURE ROLLING GATE DOES NOT EXTEND INTO 12FOOT
 UTILITY EASEMENT OR HIT BACKFLOW ASSEMBLY.
  
 -FOR FORMAL ENGINEERING SUBMITTAL, LABEL WATER MAIN
 PIPE SIZE AND MATERIAL TYPE.
  
 -EXISTING FIRE HYDRANT MAY BE MISSING FROM ENGINEERING
 PLAN ON 27TH PL.
  
 -WHAT IS HAPPENING TO THE EXISTING CONCRETE DRIVEWAY
 APPROACH TO THE EAST OF THE PROPOSED BUILDING?
  