2019-07-29 10:46:37THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE JULY
 23, 2019 SUBMITTAL PACKAGE:
  
 1. DIFFERENT VALUES PROVIDED ON THE ENGINEERING PLANS
 (1.49 FEET) AND SURVEY (1.52 FEET) FOR CONVERTING
 VERTICAL DATUMS NGVD1929 TO NAVD1988.
  
 2. IT APPEARS NEARLY ALL OF THE EXFILTRATION TRENCHES
 AND DRAINAGE STRUCTURES WILL BE BELOW THE SECOND FLOOR.
 INDICATE IF THERE IS SUFFIECENT VERTICAL CLEARANCE TO
 BE ABLE TO MAINTAIN THE DRAINAGE SYSTEM (CLEAN THE
 DRAINAGE STRUCTURES) AND TO DIG UP AND REPLACE THE
 EXFILTRATION TRENCHES WHEN THEY NO LONGER FUNCTION.
  
 3. THE ROOF DRAINAGE SYSTEM FOR THE MULTI-STORY
 BUILDING SHOULD BE DESIGNED TO AVOID CREATING
 "FOUNTAINS" ON THE GROUND LEVEL. THERE HAVE BEEN
 INSTANCES AT OTHER BUILDINGS OF MANHOLE COVERS BECOMING
 DISLODGED DURING A STORM EVENT FROM THE PRESSURE (HEAD)
 OF THE WATER IN THE ROOF DOWNSPOUTS.
  
 4. INDICATE WHERE THE OUTFALL STRUCTURE IS LOCATED.
 CCTV OF THE EXISTING DRAINAGE SYSTEM IN THE PUBLIC
 RIGHT OF WAY MAY BE REQUIRED.
  