Plan Review Notes
Plan Review Notes For Project Z19040019
Project Number Z19040019
Review Stop Z
Sequence Number 1
Notes
Date Text
2019-05-08 12:04:301. TWO DIFFERENT SURVEYS WERE SUBMITTED FOR THE
 PROJECT. PLEASE UPDATE SURVEY TO INDICATE CURRENT
 PROPERTY OWNERS. SURVEY SHOWS PARCEL 1 AND 2 IS OWNED
 BY RUSSO DS&. AND PARCEL 4 AND 5 IS SHOWN AS OWNED BY
 GARDENIA LLC.
 2. FOR ALL OWNERS OTHER THAN BRIGHT BLUE LLC PLEASE
 PROVIDE OWNER?S CONSENT FORM.
 3. PLEASE INDICATE THE WIDTH OF THE EXISTING SIDEWALKS
 IN THE SURVEY.
 4. SITE AREA REFLECTED ON MSA SURVEY (48,614SF) IS
 DIFFERENT THAN INDICATED IN SHEET A-0.7. PLEASE CLARIFY
 WHAT IS THE CORRECT AREA AND ADJUST DRAWINGS
 ACCORDINGLY. WALLACE SURVEY DOES NOT CONTAIN TOTAL LAND
 AREA INFORMATION.
 5. PARKING USES ALONG GARDENIA AVENUE, ABOVE THE 3RD
 STORY SHALL BE SET-BACK A MINIMUM OF 27? FROM THE BACK
 OF CURB.
 6. THE PROPOSED BUILDING MASSING SHALL BE RECONSIDERED.
 THE 24 STORY BUILDING RELATIONSHIP WITH THE SMALL
 DOUBLE HEIGHT RESIDENTIAL LOBBY AT THE CORNER OF DIXIE
 AND GARDENIA IS NOT APPROPRIATE.
 7. THE BUILDING AREA ABOVE THE RESIDENTIAL LOBBY IS NOT
 IN COMPLIANCE WITH THE MAXIMUM 35 FEET SETBACK FOR
 FLOOR 3RD TO 7TH.
 8. ACTIVE USES ALONG DIXIE HWAY ARE REQUIRED ALONG 65%
 OF GROUND FLOOR FRONTAGE. BUILDABLE LOT FRONTAGE =
 130.8, REQUIRED ACTIVE USE=85.02SF.
 9. PROJECT DOES NOT COMPLY WITH ACTIVE USE REQUIREMENTS
 ALONG DIXIE HWAY ABOVE THE SECOND STORY (RESIDENTIAL
 LOBBY COUNTED AS TWO STORIES). 60% ACTIVE USES REQUIRED
 ALONG DIXIE HWAY FRONTAGE.
 10. PHOTOGRAPHIC POLYVINYL COATED MESH IS NOT IN
 COMPLIANCE WITH THE ARCHITECTURAL TREATMENT REQUIRED
 FOR NON-ACTIVE USES.
 11. ALL NON-ACTIVE USE FACADES ARE REQUIRED TO PROVIDE
 ARCHITECTURAL TREATMENTS. PLEASE REVISE ALL GARAGE
 ELEVATION TO PROVIDE ARCHITECTURAL TREATMENT.
 12. RESIDENTIAL LOBBY DOOR ON DIXIE HWAY SHALL BE
 RECESSED TO AVOID ENCROACHMENT INTO PEDESTRIAN PATH.
 13. GARAGE AND STAIRS ELEVATION AT THE NW CORNER DOES
 NOT COMPLY WITH ARCHITECTURAL TREATMENT REQUIREMENTS.
 14. PLEASE PROVIDE AUTOTURN TO CONFIRM TRUCKS CAN
 ACCESS THE PROPOSED LOADING AREA.
 15. PLEAS EDISCUSS WITH PUBLIC WORKS THE GARBAGE PICK
 UP OPERATION.
 16. PLEASE EXPLAIN THE OPERATION OF THE EXISTING ALLEY.
 17. PARKING STALLS SHALL BE INCREASED BY ONE FOOT WHEN
 ADJACENT TO A WALL OR OTHER BUILDING OBSTRUCTION (SEC
 94-111(C)).
 18. SETBACK DIAGRAM PROVIDED IN SHEET A-0.11 SHALL
 INCLUDE INFORMATION MEASURED FROM THE BACK OF CURB. THE
 PROPERTY LINE SHALL BE INDICATED.
 19. PLEASE PROVIDE GRAPHIC INFORMATION TO CONFIRM
 COMPLIANCE WITH TRANSPARENCY REQUIREMENTS AT THE GROUND
 LEVEL.
 20. SITE PLAN SHALL INCLUDE INFORMATION INDICATING THE
 LOCATIONS OF THE EXISTING BUILDINGS ON THE NORTH SIDE
 OF THE ALLEY.
 21. PLEASE PROVIDE COLORED ELEVATIONS WITH CALL OUT
 MATERIALS AND IMAGES WITH MATERIALS REFERENCES.
 22. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH PLANAR BREAK REQUIREMENTS.
 23. PLEASE PROVIDE A SUMMARY TABLE INCLUDING, LOT AREA,
 FAR PERMITTED BY RIGHT, ADDITIONAL FAR WITH INCENTIVES,
 TOTAL GROSS BUILDING AREA PROPOSED PER FLOOR AND TOTAL.
 IN THE FLOOR PLANS ASSOCIATED WITH THE GROSS BUILDING
 AREA INFORMATION, PLEASE LABEL THE SPACES TO CLEARLY
 IDENTIFY THOSE AREAS EXCLUDED FROM THE GBA NUMBERS.
 PLEASE USE THE GBA DEFINITION IN SECTION 94-109.
 24. PLEASE PROVIDE A BREAKDOWN OF HOTEL ROOMS AND
 RESIDENTIAL UNITS TO CONFIRM COMPLIANCE WITH MINIMUM
 UNIT SIZE, AND AVERAGE UNIT SIZE REQUIRED BY CODE SEC
 94-109 FULL SERVICE HOTEL DEFINITION AND DWELLING UNIT
 DEFINITION.
 25. PLEASE PROVIDE GRAPHICS INDICATING THE AREA
 CALCULATED TO COMPLY WITH THE PUBLIC OPEN SPACE AND THE
 PRIVATE OPEN SPACE REQUIREMENTS AND CONFIRM COMPLIANCE
 WITH EACH OF THE REQUIREMENTS FOR EACH OPEN SPACE TYPE.
 26. PUBLIC OPEN SPACE AT GROUND LEVEL DOES NOT SEEM TO
 COMPLY WITH MINIMUM PROPORTIONS REQUIRED BY THE CODE.
 27. PLEASE PROVIDE PHOTOMETRICS TO CONFIRM COMPLIANCE
 WITH ILLUMINATION ON THE PUBLIC RIGHT OF WAY. STANDARD
 DECORATIVE STREET LIGHT FIXTURES AND POLES SHALL BE
 PROVIDED ALONG THE STREET FRONTAGES TO MEET MINIMUM 0.6
 FOOTCANDLES AT ONE FOOT ABOVE THE SIDEWALK LEVEL NEXT
 TO THE CURB. FIXTURE AND POLE SHALL MEET APPROVED CITY
 STANDARD.
 28. EXISTING UNDERGROUND ELECTRIC CONFLICTS WITH
 PROPOSED STREET TREES ALONG GARDENIA. PLEASE DETERMINE
 THE POSSIBILITY FOR RELOCATION.
 29. SIDEWALK ELEVATION SHALL BE MAINTAINED ACROSS THE
 PARKING GARAGE DRIVEWAY. PLEASE INCLUDE A NOTE AND
 SECTION WITHIN THE CIVIL DRAWINGS TO ENSURE COMPLIANCE.
 30. PLEASE VERIFY RENDERINGS ACCURATELY REFLECT THE
 BUILDING DESIGN, PROPOSED MATERIALS AND LANDSCAPE.
 RENDERINGS WILL BE PART OF THE APPROVAL SET.
 31. QUADRILLE BLVD IS AN FDOT RIGHT OF WAY. PLEASE
 CONFIRM PROPOSED LANDSCAPE COMPLIES WITH FDOT
 STANDARDS.
 32. PLEASE INDICATE THE LOCATION OF SECURED BIKE
 PARKIGN FOR RESIDENTIAL TENANTS(1/15 REQUIRED PARKIGN
 SPACES), AND THE LOCATION OF REQUIRED PULBIC BIKE
 PARKIGN ALONG THE STREET FRONTAGES 1/100 FEET OF STREET
 FRONTAGE).
  
 PLEASE RE-SUBMIT DRAWINGS ADDRESSING THE COMMENTS FROM
 ALL THE DISCIPLINES, AND INCLUDE A RESPONSE LETTER WITH
 ANSWERS TO EACH COMMENT.
 PROJECT WOULD BE REQUIRED TO OBTAIN DAC APPROVAL FOR
 SPECIAL REVIEW, AND THE TRANSFER OF DEVELOPMENT RIGHTS.
 FOR ADDTIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  
  