2019-04-30 14:49:14 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| BEACH FIRE RESCUE. |
| |
| THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| ARE SUBMITTED FOR PERMIT. |
| |
| THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| PROPOSED PROJECT. |
| |
| THE FOLLOWING COMMENTS MAY PERTAIN MORE TOWARDS |
| BUILDING CONSTRUCTION PLAN REVIEW: |
| |
| 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE |
| PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A |
| PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED |
| TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN |
| STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY |
| MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER |
| PROTECTION. |
| |
| 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| ALL CONSTRUCTION ACTIVITIES. |
| |
| 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM |
| ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. |
| ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND |
| AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT |
| WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| |
| 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE |
| REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE |
| ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| |
| 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH |
| THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, |
| INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. |
| |
| 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A, |
| PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE, |
| INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE |
| OCCUPANCIES (PARKING STRUCTURES) |
| |
| 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA |
| 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS |
| STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE |
| BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE |
| BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED |
| TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE |
| PREVENTION BUREAU PRIOR TO ANY INSTALLATION. |
| |
| IT IS REQUESTED THAT HIGH RISES HAVE TWO SEPARATE FDC |
| LOCATIONS FOR FIREGROUND FIREFIGHTER OPERATIONS. THERE |
| APPEARS TO BE AN EXISTING FIRE HYDRANT ON THE SOUTHEAST |
| CORNER OF GARDENIA AND DIXIE. A FDC LOCATED ON THE |
| DIXIE SIDE WOULD BE ACCEPTABLE. |
| |
| 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED |
| NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE |
| HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY. |
| |
| 18.3 WATER SUPPLIES. |
| |
| 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING |
| THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE |
| PROVIDED TO ALL PREMISES UPON WHICH FACILITIES, |
| BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER |
| CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE |
| APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH |
| SECTION 18.4. |
| |
| PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| PRE-ENGINEERED SYSTEMS. |
| |
| |
| 7A) FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE |
| PRIMARY AND SECONDARY POWER SOURCES? |
| |
| 7B) THE LOCATION OF THE FIRE LINE DDCV SHALL BE CLOSELY |
| COORDINATED THROUGH AND WITH THE OFFICES OF THE CITY |
| URBAN DESIGNER, THE LANDSCAPE PLANNER AND FIRE MARSHAL. |
| |
| 8. A CLASS ?A? NFPA 72 COMPLIANT MONITORED FIRE ALARM |
| SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP |
| DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND |
| APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY |
| INSTALLATION. |
| |
| 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7 |
| KEYWAY SYSTEM. |
| |
| ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S |
| EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA |
| B44, SAFETY CODE FOR ELEVATORS. |
| |
| ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN |
| WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL |
| LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET |
| MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER |
| ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN |
| AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE |
| IN THE HORIZONTAL POSITION. |
| |
| 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL |
| BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, |
| EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A |
| PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE |
| SAFETY FEATURES AND EQUIPMENT. |
| |
| 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS |
| DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED |
| ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF |
| FIRE PREVENTION. |
| |
| ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS |
| DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE |
| BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND |
| FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET |
| OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER |
| ARRIVING EMERGENCY VEHICLES. |
| |
| 12. COMMAND ROOM |
| |
| THE LOCATION OF THE COMMAND ROOM IS STRONLY ENCOURAGED |
| TO HAVE ACCESS FROM THE EXTERIOR OF THE BUILDING. A |
| DOOR PLACED TO ENTER THE INTERIOR WOULD BE ACCPETABLE; |
| HOWEVER, ACCESS FROM THE OUTSIDE IS OPTIMUM FOR |
| FIREGROUND OPERATIONAL EFFICIENCY, AS WELL AS, FOR |
| EVACUATION PURPOSES. |
| |
| WOULD IT BE POSSIBLE TO MOVE THE LOCATION OF THE |
| COMMAND ROOM OR SWAPPING POSTIONS WITH THE TRASH ROOM, |
| OR IT AND ENGINEERING ROOMS..? PLEASE COORDINATE WITH |
| THE OFFICE OF THE FIRE MARSHAL. |
| |
| THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, |
| CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN |
| THE FOLLOWING FEATURES: |
| |
| A. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM |
| DIMENSION OF 10 FT. |
| B. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. |
| C. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| D. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION |
| OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| BARRIERS AND SMOKE PARTITIONS |
| E. A WORK TABLE. |
| F. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN |
| FOR THE BUILDING. |
| G. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| CONTROL UNIT. |
| H. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF |
| THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| I. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION |
| SYSTEMS. |
| J. CONTROLS FOR UNLOCKING STAIRWAY DOORS SIMULTANEOUSLY |
| K. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY |
| PANELS |
| L. EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| M. FIRE PUMP STATUS INDICATORS |
| N. GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| TRANSFER FEATURES. |
| O. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| BY OTHER SECTIONS OF THIS CODE |
| P. CONTROLS REQUIRED FOR SMOKE CONTROL |
| Q. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| A17.1. |
| R. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR |
| SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS |
| PROVIDED |
| |
| NFPA 101, CHAPTER 11 |
| |
| 11.8.6* EMERGENCY COMMAND CENTER. |
| 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED |
| IN A |
| LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE |
| FOLLOWING: |
| (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS |
| (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION |
| SERVICE |
| PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION |
| OF THIS |
| CODE |
| (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| PANELS |
| (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS |
| (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS |
| (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE |
| PROVIDED |
| IN ACCORDANCE WITH ASME A17.1/CSA B44 |
| (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS |
| (8) EMERGENCY GENERATOR STATUS INDICATORS |
| (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING |
| SYSTEM |
| (10) FIRE PUMP STATUS INDICATORS |
| (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| ACCESS TO THE |
| PUBLIC TELEPHONE SYSTEM |
| (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| 11.8.8 |
| |
| 13. RADIO |
| |
| NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| RADIO ENHANCEMENT SERVICES. |
| |
| 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| DETERMINED BY THE AHJ. |
| NFPA 72, 24.5.2* TWO-WAY RADIO COMMUNICATIONS |
| ENHANCEMENT SYSTEMS. |
| 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE |
| PROVIDED THROUGHOUT THE BUILDING AS A PERCENTAGE OF |
| FLOOR AREA AS SPECIFIED IN 24.5.2.2.1 THROUGH |
| 24.5.2.2.3. |
| 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE |
| EMERGENCY COMMAND CENTER(S), THE FIRE PUMP ROOM(S), |
| EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR LOBBIES, |
| STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE |
| LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE |
| AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH |
| 99 PERCENT FLOOR AREA RADIO COVERAGE. |
| 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING |
| AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA |
| RADIO COVERAGE. |
| 24.5.2.3 SIGNAL STRENGTH. |
| 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH |
| OF -95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE |
| AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED |
| THROUGHOUT THE COVERAGE AREA. |
| 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH |
| OF -95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH |
| AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION, SHALL |
| BE PROVIDED FROM THE COVERAGE AREA. |
| |
| THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL |
| STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST |
| PALM BEACH FIRE RESCUE. TESTING SHALL BE BY AN |
| ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES |
| NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE |
| PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A |
| BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH |
| A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP. |
| |
| 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS |
| BUILDING. |
| |
| ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS, |
| PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. |
| |
| 15. THE SMOKE CONTROL SYSTEM SHALL COMPLY WITH NFPA |
| 101, CHAPTER 9, BUILDING SERVICE AND FIRE PROTECTION |
| EQUIPMENT, INCLUDING: |
| |
| THE SMOKE CONTROL SYSTEMS SHALL BE INSTALLED, |
| INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH |
| NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204, |
| STANDARD FOR SMOKE AND HEAT VENTING; OR NATIONALLY |
| RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR |
| RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY |
| HAVING JURISDICTION. |
| |
| THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE |
| INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE |
| APPROPRIATENESS OF THE METHOD USED, AND THE REQUIRED |
| MEANS OF INSPECTING, TESTING, AND MAINTAINING THE |
| SYSTEM. |
| ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL |
| INSPECTOR IN ACCORDANCE WITH SECTION 9.9. |
| |
| 16. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT |
| DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. |
| |
| 17. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING |
| PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH |
| THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
|