2019-05-06 20:32:18 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| COMMENTS: |
| |
| 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| |
| 2. DEMOLITION OF THE EXISTING BUILDINGS. AN ASBESTOS |
| SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT |
| REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH |
| COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, |
| OR BY EMAIL: [email protected] |
| |
| 3. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY |
| LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER |
| APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE |
| PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE |
| WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF |
| FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION |
| DISTANCE. |
| |
| 4. EXIT STAIRS NOT DISCHARGING TO THE EXTERIOR OF THE |
| BUILDING. GROUND FLOOR PLAN, SHEET A-1.1, SHOWS STAIR |
| #1, #3 AND #4 ALL DISCHARGING INTERNAL TO THE BUILDING. |
| SECTION 1028.1 OF FLORIDA BUILDING CODE, BUILDING, |
| STATES THAT AT LEAST 50% OF THE REQUIRED EXITS SHALL |
| DISCHARGE TO THE EXTERIOR OF THE BUILDING. THE ROUTE |
| FROM STAIR #4 IS NOT CURRENTLY SHOWN AS A PROTECTED |
| EXIT PASSAGEWAY. |
| |
| 5. LOCATION OF ACCESSIBLE PARKING SPACES. PER FAIR |
| HOUSING ACT AND SECTION 208.3 OF FLORIDA ACCESSIBILITY |
| CODE, ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON |
| THE SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT |
| PARKING TO AN ACCESSIBLE ENTRANCE. THE DESIGN OF |
| ACCESSIBLE PARKING SPACES SHALL COMPLY WITH SECTION 502 |
| OF FLORIDA ACCESSIBILITY CODE. THE FOLLOWING ACCESSIBLE |
| PARKING SPACES ARE EITHER NOT USEABLE OR NOT LOCATED AS |
| THE CLOSEST SPACE TO THE BUILDING ENTANCE: |
| - SHEET A-1.2 ACCESSIBLE PARKING SPACE #61 IS NOT |
| USABLE BECAUSE IT DOES NOT HAVE ACCESS TO ELEVATORS AS |
| THE ELEVATORS ARE NO SHOW TO STOP ON THE 2ND LEVEL. |
| - SHEET A-1.3 ACCESSIBLE PARKING SPACE #89 IS NOT |
| USABLE BECAUSE THE ROUTE TO THE ELEVATOR GOES ACROSS |
| THE STAIR LANDING AND THE LANDING DOORS DO NOT HAVE THE |
| REQUIRED 48 INCH DOOR SWING SEPARATION REQUIRED BY |
| SECTION 404.2.6 OF FLORIDA ACCESSIBILITY CODE. |
| - SHEET A-1.4 ACCESSIBLE PARKING SPACE #171 IS NOT |
| USABLE BECAUSE THE USER WOULD BE REQUIRED TO TRAVEL IN |
| THE VEHICULAR DRIVE LANE TO GET TO THE ELEVATORS. |
| - SHEET A-1.5 ACCESSIBLE PARKING SPACE #255 IS NOT |
| USABLE BECAUSE THE ROUTE TO THE ELEVATOR GOES ACROSS |
| THE STAIR LANDING AND THE LANDING DOORS DO NOT HAVE THE |
| REQUIRED 48 INCH DOOR SWING SEPARATION REQUIRED BY |
| SECTION 404.2.6 OF FLORIDA ACCESSIBILITY CODE. |
| - SHEET A-1.4 ACCESSIBLE PARKING SPACE #320 IS NOT |
| USABLE BECAUSE THE USER WOULD BE REQUIRED TO TRAVEL IN |
| THE VEHICULAR DRIVE LANE TO GET TO THE ELEVATORS. |
| - SHEET A-1.5 ACCESSIBLE PARKING SPACE #372 IS NOT |
| USABLE BECAUSE THE ROUTE TO THE ELEVATOR GOES ACROSS |
| THE STAIR LANDING AND THE LANDING DOORS DO NOT HAVE THE |
| REQUIRED 48 INCH DOOR SWING SEPARATION REQUIRED BY |
| SECTION 404.2.6 OF FLORIDA ACCESSIBILITY CODE. |
| |
| 6. VAN ACCESSIBLE PARKING SPACES. THE BUILDING DATA |
| TABLE ON SHEET A-1.0 STATES THAT TWO VAN ACCESSIBLE |
| PARKING SPACES ARE BEING PROVIDED BUT THE LOCATION OF |
| THE TWO SPACES IS NOT SHOWN ON THE PLANS. PER SECTION |
| 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX |
| REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING |
| STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN |
| ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY |
| CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT |
| SPACE AND VEHICULAR ACCESS ROUTE) |
| |
| 7. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| FLORIDA BUILDING CODE. |
| |
| 8. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| OTHER APPROVED METHODS. |
| |
| 9. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE |
| REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M |
| SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS |
| AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL: |
| [email protected] |
| |
| 10. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| |
| 11. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT |
| WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL |
| HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT |
| MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 |
| 1080, OR BY EMAIL: [email protected] |
| |
| 12. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT |
| TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE |
| ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP |
| ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC |
| PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| [email protected] |
| |
| ROBERT BROWN |
| BUILDING OFFICIAL |
| TEL: 561 805 6652 |
| EMAIL: [email protected] |
| |
|