Plan Review Notes
Plan Review Notes For Project Z18050028
Project Number Z18050028
Review Stop STORM
Sequence Number 2
Notes
Date Text
2018-08-24 14:12:58THE FOLLOWING COIMMENTS ARE FROM THE REVIEW OF THE
 AUGUST 17, 2018 SUBMITTAL PACKAGE:
 1. PROVIDE 5 FEET MINIMUM HORIZONTAL SEPARATION BETWEEN
 THE SANITARY LATERAL AND THE EDGE OF THE EXFILTRATION
 TRENCH.
  
 2. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 3. ADD THE VERTICAL DATUM TO THE DRAINAGE CALCULATIONS
 (GRADING ASSUMPTIONS TABLE).
  
 4. PROVIDE A COPY OF THE EXFILTRATION TEST RESULTS WITH
 THE DRAINAGE CALCULATIONS.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120