Plan Review Notes For Project Z18040017
Project Number Z18040017
Review Stop TRAFFIC
Sequence Number 2
Notes
Date Text
2018-06-08 11:59:57DEL TACO RESUBMITTAL 2018-05-25 (Z18040017)
  
 - PROVIDE SUFFICIENT SIGHT DISTANCE AT THE
 DRIVE-THROUGH EXITS. AT THE EXIT AT THE DRIVE-THROUGH
 BEND, SIGHT DISTANCE LOOKING NORTH IS BLOCKED BY THE
 DUMPSTER. AT THE EXIT AT THE END OF THE DRIVE-THROUGH
 AISLE, SIGHT DISTANCE LOOKING WEST MAY BE BLOCKED BY
 THE RETAINING WALL DEPENDING ON THE HEIGHT OF THE WALL.
 - AT THE EXIT AT THE DRIVE-THROUGH BEND, IT APPEARS THE
 RADIUS IS STILL VERY TIGHT FOR A PASSENGER CAR TO MAKE
 A RIGHT-TURN. PLEASE REVISE AND VERIFY BY SHOWING
 AUTOTURN PATH FOR THIS MOVEMENT.
 - PROPOSED SIDEWALK FROM BELVEDERE IS SHOWN AS 4' WIDE.
 SIDEWALK MUST BE 5' WIDE.
 - CHECK IF HANDRAIL IS REQUIRED FOR SIDEWALK NEXT TO
 RETENTION AREA DUE TO DROP OFF.
  