2018-06-04 13:04:54 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| COMMENTS: |
| |
| 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| |
| 2. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE |
| RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD |
| ZONE AE, WITH A BASE FLOOD ELEVATION OF 12.7 FT NAVD. |
| THE FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED |
| MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL |
| BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD |
| ELEVATION. |
| |
| 3. ACCESSIBLE ROUTE. COMMENT ADDRESSED BY REVISED SITE |
| PLAN LAYOUT C-5, REVISION 1 - THE PLANS NOW SHOW AN |
| ACCESSIBLE WHEELCHAIR AND PEDESTRIAN ROUTE FROM THE |
| PUBLIC RIGHT-OF-WAY COMPLYING WITH SECTIONS 206.2 AND |
| 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE PUBLIC |
| RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR FACILITY |
| ENTRANCES. |
| |
| 4. NUMBER OF ACCESSIBLE PARKING SPACES. COMMENT |
| ADDRESSED BY REVISED SITE PLAN LAYOUT C-5, REVISION 1 - |
| THE PLANS NOW SHOW 2 ACCESSIBLE PARKING SPACES AS |
| REQUIRED TO COMPLY WITH SECTION 208.2 OF FLORIDA |
| ACCESSIBILITY CODE. |
| |
| 5. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| FLORIDA BUILDING CODE. |
| |
| 6. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE |
| REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M |
| SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS |
| AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL: |
| [email protected] |
| |
| 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, |
| FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, |
| GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, |
| SITE IRRIGATION, ETC. |
| |
| |
| ROBERT BROWN |
| BUILDING OFFICIAL |
| TEL: 561 805 6652 |
| EMAIL: [email protected] |
| |
|