2010-11-22 13:34:36 | INFORMAL SITE PLAN REVIEW NO.10-04 (Z10110009) |
| 2100 NORTH FLORIDA MANGO ROAD |
| |
| 1. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| RELOCATED EMERGENCY GENERATOR. |
| |
| 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE |
| SPRINKLER AND FIRE ALARM SYSTEM. |
| |
| 3. PLEASE INDICATE HEIGHT OF THE PORTA CACHERE. IS IT |
| TALL ENOUGH FOR FIRE AND PARAMEDICAL EQUIPMENT TO PASS |
| UNDERNEATH IT. |
| |
| 4. THE APPROPRIATE DEMOLITION PERMITS ARE TO BE |
| OBTAINED. |
| |
| 5. PLEASE INDICATE SEATING FOR THE PHYSICALLY |
| CHALLENGED IN MULTI-PURPOSE 16. |
| |
| 6. PLEASE PROVIDE MORE DETAILS ON SEATING LOCATED IN |
| MULTI-PURPOSE 16. |
| |
| 7. PLEASE INDICATE ALL HORIZONTAL AND VERTICAL FIRE |
| SEPARATIONS. |
| |
| 8. PLEASE INDICATE ALL ILLUMINATED EXIT SIGNS, |
| EMERGENCY LIGHTS AND PORTABLE FIRE EXTINGUISHER |
| LOCATIONS. |
| |
| 9. ALL EXIT DOORS SUBJECT TO AN OCCUPANCY LOAD OF 100 |
| OR MORE PERSONS SHALL BE EQUIPPED WITH PANIC HARDWARE. |
| NO OTHER LOCKS OR LATCHES ARE PERMITTED. |
| |
| 10. THE STAGE AND RAMP "NOT IN CONTRACT" IS TO BE |
| PERMITTED SEPARATELY. |
| |
| 11. SUBMIT COMPLETE PLANS DETAILING ALL ARCHITECTURAL, |
| MECHANICAL, ELECTRICAL, PLUMBING, FIRE ALARM, AND FIRE |
| SPRINKLER SYSTEMS TO THE CONSTRUCTION SERVICES |
| DEPARTMENT. |
| |
| |
| DENIED |
| |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |
|