2010-05-28 11:14:17 | INFORMAL SITE PLAN REVIEW 10-01 |
| 2100 NORTH FLORIDA MANGO ROAD |
| Z10050014 |
| |
| 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| WITH NFPA 241. |
| |
| 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. |
| |
| 3. A KNOXBOX WILL BE REQUIRED. PLEASE GO TO |
| WWW.KNOXBOX.COM TO ORDER. |
| |
| 4. THE UPSTARIRS APPEARS TO BE DESIGNED FOR ASSEMBLY |
| PURPOSES AND NOT BUSINESS AS DECLARED ON THE PLANS. |
| |
| 5. PLEASE ILLUSTRATE ON THE PLANS ALL OF THE CODE |
| REQUIREMENTS FOR THE "AREA OF REFUGE" DECLARED ON PAGE |
| A-2. |
| |
| 6. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| FOR ALL HANDRAILS AND GUARDRAILS. |
| |
| 7. ON PAGE A-3 IN THE DEMOLITION AND ELECTRICAL |
| DEMOLITION NOTES REFERENCES ARE MADE REGARDING FIRE |
| SPRINKLER AND FIRE ALARM SYSTEMS. PLEASE PROVIDE MORE |
| DETAILS ON THESE SYSTEMS. SEPARATE PLANS AND PERMITS |
| ARE REQUIRED FOR THE FIRE SPRINKLER AND FIRE ALARM |
| SYSTEMS. |
| |
| 8. PLEASE PROVIDE A PLAN ILLUSTRATING CONSTRUCTION AND |
| NONCONSTRUCTION AREAS. |
| |
| 9. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR |
| WALLS AND CEILINGS. |
| |
| 10. BUILDING ADDRESS REQUIRED ON THE PROPER ELEVATION. |
| A MINIMUM OF AT LEAST 6" HIGH AND AT LEAST 1" WIDE |
| NUMBERS ARE REQUIRED. |
| |
| 11. PLEASE PROVIDE MORE DETAILS ON EXISTING GENERATOR. |
| |
| 12. FIRE DEPARTMENT LOCKING CAPS WILL BE REQUIRED ON |
| THE FIRE DEPARTMENT CONNECTION. PLEASE GO TO |
| WWW.KNOXBOX.COM TO ORDER. |
| |
| 13. THE FIRE SPRINKLER AND FIRE ALARM SYSTEM ARE TO BE |
| MONITORED BY A THIRD PARTY LISTED FOR CENTRAL STATION |
| SERVICE. |
| |
| 14. ELEVATOR WARNING SIGNS ARE REQUIRED. |
| |
| 15. PLEASE DISPLAT ALL FIRE RATED WALLS AND SHAFTS. |
| |
| 16. PLEASE PROVIDE FIRESTOPPING DETAILS. |
| |
| |
| DENIED |
| |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |
| (561) 804-4709 PHONE |
| (561) 804-4774 FAX |
|