2021-10-22 13:45:51COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR
 [email protected]:
  
 PASSED WITH PROVISOS:
 -SMALL METERED IRRIGATION WATER SERVICE IS NOW MISSING
 FROM SHEET C3.0. IS IT NOT NEEDED ANYMORE?
 -THE METERS AND BACKFLOWS IN DETAIL AREA A SHEET C3.0
 ARE NOT MATCHING UP CORRECTLY WITH THE LABELS. THEY ARE
 SWITCHED. PLEASE CORRECT.
 NO COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120.
  
 COMMENTS FROM MIKE TECHNOW, PUBLIC UTILITIES ENGINEER,
 [email protected], 561-494-1047:
  
 -SHEET C3.2 PRINTING IS TOO LIGHT AND NOT LEGIBLE.
 PLEASE DARKEN A LITTLE.
 -SHEET C3.2 CALL FOR 18? BETWEEN TAPPING TEES.
 -SHEET C6.3 ONLY NEED 12? VERTICAL SEPARATION WHEN THE
 WM CROSSES UNDER.
 -CHANGE ?BROWARD? TO CITY OF WEST PALM IN ALL GENERAL
 NOTE SECTIONS.
 -ADD NOTE THAT CONNECTION WILL BE MADE AFTER APPROVAL
 AND FDOH RELEASE.
  
 COMMENTS FOR THE MAINTENANCE BUILDING ON SHEETS C3.4
 AND C3.5:
 -SHOW PROFILE OF WM FROM TAP TO POINT OF SERVICE. SHOW
 UTILITY CROSSINGS ON PROFILE (GAS MAIN).
 -CALL OUT SIZE AND MATERIAL OF EXISTING WM TO BE TAPPED
 ON GREGORY ROAD.
 -CALL OUT MINIMUM DISTANCE BETWEEN FEC RIGHT OF WAY AND
 6? WM.
 -LABEL FEC RIGHT OF WAY.
 -ADD NOTE TO RESTORE GRAVEL ROAD.
 -CALL OUT 6? FIRE LINE AND 2? WM AS ?PRIVATE?.
 -REMOVE ?BROWARD? FROM NOTES.
 -ADD NOTE THAT PRESSURE AND LEAKAGE TEST MAY BE DONE ON
 A MAXIMUM OF 1500 LF OF PIPE.
 -NOTE THAT FAC CALLS FOR A MAXIMUM DISTANCE OF 1,200 LF
 FOR SAMPLE POINTS/BAC?T.
 - REFER TO THE LATEST REVISION OF PRESSURE PIPE DETAIL
 P6 AND P6.1
  