2021-10-22 13:45:51 | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE |
| SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR |
| [email protected]: |
| |
| PASSED WITH PROVISOS: |
| -SMALL METERED IRRIGATION WATER SERVICE IS NOW MISSING |
| FROM SHEET C3.0. IS IT NOT NEEDED ANYMORE? |
| -THE METERS AND BACKFLOWS IN DETAIL AREA A SHEET C3.0 |
| ARE NOT MATCHING UP CORRECTLY WITH THE LABELS. THEY ARE |
| SWITCHED. PLEASE CORRECT. |
| NO COMMENTS FROM TRACY WARD, SR. STORMWATER ENG., |
| ENGINEERING SERVICES, [email protected] 561-494-1120. |
| |
| COMMENTS FROM MIKE TECHNOW, PUBLIC UTILITIES ENGINEER, |
| [email protected], 561-494-1047: |
| |
| -SHEET C3.2 PRINTING IS TOO LIGHT AND NOT LEGIBLE. |
| PLEASE DARKEN A LITTLE. |
| -SHEET C3.2 CALL FOR 18? BETWEEN TAPPING TEES. |
| -SHEET C6.3 ONLY NEED 12? VERTICAL SEPARATION WHEN THE |
| WM CROSSES UNDER. |
| -CHANGE ?BROWARD? TO CITY OF WEST PALM IN ALL GENERAL |
| NOTE SECTIONS. |
| -ADD NOTE THAT CONNECTION WILL BE MADE AFTER APPROVAL |
| AND FDOH RELEASE. |
| |
| COMMENTS FOR THE MAINTENANCE BUILDING ON SHEETS C3.4 |
| AND C3.5: |
| -SHOW PROFILE OF WM FROM TAP TO POINT OF SERVICE. SHOW |
| UTILITY CROSSINGS ON PROFILE (GAS MAIN). |
| -CALL OUT SIZE AND MATERIAL OF EXISTING WM TO BE TAPPED |
| ON GREGORY ROAD. |
| -CALL OUT MINIMUM DISTANCE BETWEEN FEC RIGHT OF WAY AND |
| 6? WM. |
| -LABEL FEC RIGHT OF WAY. |
| -ADD NOTE TO RESTORE GRAVEL ROAD. |
| -CALL OUT 6? FIRE LINE AND 2? WM AS ?PRIVATE?. |
| -REMOVE ?BROWARD? FROM NOTES. |
| -ADD NOTE THAT PRESSURE AND LEAKAGE TEST MAY BE DONE ON |
| A MAXIMUM OF 1500 LF OF PIPE. |
| -NOTE THAT FAC CALLS FOR A MAXIMUM DISTANCE OF 1,200 LF |
| FOR SAMPLE POINTS/BAC?T. |
| - REFER TO THE LATEST REVISION OF PRESSURE PIPE DETAIL |
| P6 AND P6.1 |
| |
|