2021-08-17 10:58:26 | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES |
| DEPT., 561-494-1098 [email protected] : |
| |
| 1. CONFIRM THAT A COMPLETED LOS ANALYSIS SUMMARY TABLE |
| HAS BEEN SUBMITTED DIRECTLY TO ENGINEERING (SHEET 33 OF |
| CITY OF WPB DEVELOPMENT APPLICATION). |
| 2. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY |
| SEWER ARE REQUIRED. |
| 3. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND |
| PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM |
| AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE |
| PER FAC 64E-8 FOR WATER AND PER FAC 64-E.008 FOR SEWER. |
| 4. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND |
| IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED |
| AREAS. |
| 5. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE |
| SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING |
| PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT |
| HIM AT 561-494-2262 OR [email protected] |
| 6. PLEASE SHOW PROPOSED LOCATIONS AND DIMENSIONS OF ALL |
| WATER, STORMWATER, AND SANITARY AND SEWER LINES, |
| INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND |
| SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, |
| METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE |
| SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING |
| GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, |
| ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL |
| INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER |
| LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE |
| PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN |
| VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. |
| ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND |
| PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER |
| OPTIC, ELECTRIC, GAS, AND CABLEVISION & |
| TELECOMMUNICATION FACILITIES LOCATED ON THE |
| RIGHT-OF-WAY. |
| 7. PLEASE CUT AND CAP UTILITIES NOT IN USE, AND REMOVE |
| ANY ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM |
| CITY RIGHT OF WAY. |
| 8. PLEASE LABEL DEDICATED UTILITY EASEMENTS TO ALLOW |
| ACCESS FOR CITY PERSONNEL TO PROPOSED UTILITY WATER |
| METERS. |
| 9. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED |
| LOCATION OF WATER METER AND BACKFLOW PREVENTION. |
| 10. PLEASE CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA |
| AND FIRE BACKFLOW PREVENTER AS DCDA. SPECIFY LEAD FREE |
| DESIGN ON ALL BACKFLOWS. |
| 11. FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND |
| NPDES NOI REQUIREMENTS WILL BE ENFORCED. |
| - AN NOI IS REQUIRED FOR PROJECTS THAT: |
| - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS |
| THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF |
| DEVELOPMENT OR SALE; |
| - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE |
| STATE OR TO SURFACE WATERS OF THE STATE THROUGH A |
| MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). |
| - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF |
| CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION |
| THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL |
| SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT |
| OF THE 10-2 CERTIFICATION. |
| 12. PLEASE PROVIDE PROFILES OF WATER AND SEWER IN ROW |
| AND SHOW ANY CROSSINGS/CONFLICTS. |
| 13. WHEN SUBMITTING APPROVED MATERIALS LIST, PLEASE |
| PROVIDE MATERIAL/CUT SHEETS FOR ALL PROPOSED BACKFLOW |
| DEVICES SHOWING SPECIFIC MODEL NUMBER AND SPECIFYING |
| USC APPROVED LEAD-FREE DESIGN. |
| 14. PLEASE CLEARLY SHOW ROAD RIGHT OF WAY. |
| 15. PLEASE PROVIDE SANITARY ELEVATIONS AT MANHOLE |
| TIE-IN. |
| 16. IF SANITARY LINES ARE PROPOSED IN ROW PLEASE SHOW |
| ADJACENT SANITARY LATERAL LOCATIONS AND SHOW ADDRESSES |
| OF ADJACENT PARCELS. |
| 17. IF WATER LINES ARE BEING REPLACED IN ROW, SHOW |
| ADJACENT PARCEL ADDRESSES. |
| 18. WHEN TRENCHING IN IN CITY-MAINTAINED ROADWAY AREAS |
| ADD NOTE TO PROVIDE 50 FT. PAVEMENT RESTORATION |
| TRANSITION ON EACH SIDE OF PROPOSED TRENCH PER CITY OF |
| WPB STANDARD DETAIL GC-4. |
| 19. PLEASE ADD PROJECT ADDRESS TO COVER SHEET. |
| 20. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND |
| INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER |
| (E-XXXXXXXX). |
| |
| |
| COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE |
| SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR |
| [email protected]: |
| |
| -NORTH-SOUTH DIMENSION OF 3INCH AND 4INCH METERS LOOK |
| TOO SMALL. THERE IS A LARGE UNDERGROUND MAINTENANCE |
| BYPASS. PLEASE MAKE SURE WATER PLAN ACCURATELY DEPICTS |
| THE FOOTPRINT. MAY NEED TO ADJUST IRRIGATION SERVICE |
| SLIGHTLY SOUTH TO MAKE ROOM. |
| |
| -ON THE WATER PLANS CALLOUT SOME DISTANCES BETWEEN |
| PIPES WHERE THEY ARE CLOSE TOGETHER. IT IS HARD TO TELL |
| FROM THE SCALE. |
| |
| -LABEL THE GATE VALVES IMMEDIATELY UPSTREAM OF DCDA?S |
| AS POINT OF SERVICE. |
| |
| -SHOW AND LABEL ALL EXISTING GATE VALVES ON 16 INCH AND |
| 8 INCH WATER MAINS ON GEORGIA AVE. |
| |
| -MULTIPLE LINESTOPS OR INSERTION VALVES MAY BE REQUIRED |
| FOR THE WATER MAIN REROUTINGS. |
| |
| -ADD GATE VALVE AT SOUTH SIDE OF 16 INCH WATER MAIN |
| REROUTE BETWEEN EXISTING MAIN AND 45. ADD GATE VALVE |
| ACROSS GEORGIA AVE AT SIMILAR LOCATION FOR THE 8 INCH |
| WATER MAIN REROUTE. |
| |
| -ADD DIP TO LABELS FOR THE NEW 16 INCH AND 8 INCH WATER |
| MAINS ON GEORGIA AVE. |
| |
| -C3.2. CHECK THE DESIGN AND LABELING FOR THE FIRE AND |
| DOMESTIC ALONG THE NORTH RUN FROM EAST TO WEST. LOOKS |
| LIKE THE LINES AND BRANCHES ARE GETTING TRANSPOSED AND |
| MISLABELED. |
| |
| -SHOW THE ICONS FOR THE LARGE METER BACKFLOW ASSEMBLIES |
| SIMILARLY. THE NORTH ONE DOES NOT DEPICT THEM WELL LIKE |
| THE SOUTHERN ONES. |
| |
| -DETAIL/LABEL THE TRANSITION UPSTREAM OF THE 3 INCH |
| METERS AND DOWNSTREAM OF THE TAPPING VALVES. |
| |
| -DEMO PLAN APPEARS TO SHOW WORK ENCROACHING ON PALM |
| BEACH COUNTY PROPERTY. VERIFY THAT IS ALRIGHT. |
| |
| -LABEL WATER SERVICE PIPING UPSTREAM OF IRRIGATION |
| METER WITH PIPE SIZE AND MATERIAL TYPE. |
| |
| -ADD RP TO LABEL FOR IRRIGATION BACKFLOW. |
| |
| -C3.3 ADD RP TO LABEL FOR 2.5INCH BACKFLOW. |
| |
| -CANNOT LOCATE MANY CLEANOUTS. MAKE SURE ALL SEWER |
| LATERAL CLEANOUTS ARE SHOWN AND LABELED. SPECIFICALLY |
| CHECK THE FAR NORTHWEST BUILDING. |
| |
| -MAINTENANCE BUILDING WATER PLAN NEEDS TO BE |
| REDESIGNED. 16 INCH WATER MAIN WHERE 6 INCH FIRE MAIN |
| IS PROPOSED CANNOT BE USED. CLOSEST TAP LOCATION WOULD |
| BE GREGORY/GEORGIA FOR ADDITIONAL WATER SERVICES. FIRE |
| HYDRANT NEAR BUILDING WOULD BE PRIVATE AND DOWNSTREAM |
| OF A DCDA. WATER METERS WOULD BE ADJACENT |
| GEORGIA/GREGORY |
| |
| |
| COULD NOT FIND RESPONSES FOR PRIOR PPRC REVIEW |
| COMMENTS: |
| |
| -THERE IS NOT MUCH INFORMATION ON THE TWO 400 SF |
| RESTROOM BUILDINGS IN THE MIDDLE OF THE GOLF COURSE. |
| PLEASE PROVIDE AT LEAST THE FOLLOWING INFORMATION: 1) |
| WILL THEY BE PERMANENT STRUCTURES? 2) HOW WILL WATER |
| AND SEWER UTILITY FOR THEM BE TAKEN CARE OF? |
| |
| -IS THE EXISTING GRAVEL AND DIRT MAINTENANCE ROAD |
| SUFFICIENT FOR THE VEHICLE TRAFFIC TO THE PROPOSED |
| MAINTENANCE BUILDING? WILL IT ALSO BE OPEN ACCESS AT |
| GREGORY RD WITH NO GATES/FENCES? |
| |
| -WILL THE MAINTENANCE BUILDING HAVE ANY FIRE |
| SPRINKLERS? IS ANY OTHER FIRE PROTECTION WATER SUCH AS |
| FIRE HYDRANTS NEEDED AROUND THAT AREA OF THE PROPERTY? |
| |
| COMMENTS FROM TRACY WARD, SR. STORMWATER ENG., |
| ENGINEERING SERVICES, [email protected] 561-494-1120: |
| |
| SHEET C1.0 |
| 1. SHOULD THERE BE A YIELD LINE AT THE YIELD SIGN(S)? |
| 2. ARE A STOP SIGN AND STOP BAR NEEDED AT EAST END OF |
| THE 7 SPACE PARKING LOT EAST OF CART STORAGE AND/OR FOR |
| WEST BOUND TRAVEL LANE GOING TOWARD THE CART BARN? |
| 3. SHOW THE 2? LANDSCAPE OVERHANG LINE FOR THE PARKING |
| SPACES DESIGNED WITH THE OVERHANG. |
| |
| SHEET C2.0 |
| 1. PRB?S NOT NECESSARILY NEEDED IN DRAINAGE STRUCTURES |
| NOT CONNECTED TO EXFILTRATION TRENCH SUCH AS CI#12 AND |
| CI#13. |
| 2. REVIEW THE PARKING LOT GRADES SHOWN ON SECTIONS A-A |
| AND B-B AND THE FFE ON SECTION C-C VS. THE PLAN GRADE |
| ELEVATIONS. |
| |
| SHEET C2.3 |
| 1. NUMBER THE DRAINAGE STRUCTURES |
| 2. PIPE INVERT ELEVATION (24.00 FT NAVD) IN |
| EXFILTRATION TRENCH DETAIL DOES NOT MATCH THE PLAN VIEW |
| INVERT ELEVATIONS AT THE CATCH BASINS (26.00 FT NAVD). |
| 3. THERE MAY BE INSUFFICIENT COVER OVER THE |
| EXFILTRATION TRENCH AT THE NORTH CB. |
| 4. PROVIDE CROSS SECTION OF THE PROPOSED ROAD TO THE |
| PERFORMANCE BUILDING. WILL IT BE A SHED SECTION SLOPING |
| TO THE SOUTH? |
| |
| SHEET C2.4 |
| 1. IT APPEARS THERE IS A WATER MAIN CROSSING BOTH |
| EXFILTRATION TRENCHES. |
| 2. SUGGEST ADDING PRB?S TO THE DRAINAGE STRUCTURES TO |
| EXTEND THE LIFE OF THE EXFILTRATION TRENCHES. |
| 3. WHERE DOES THE WATER GO AFTER IT LEAVES (BUBBLES |
| UP?) THE CONTROL STRUCTURE CB#4? |
| |
| SHEET C4 |
| 1. HOW DOES THE CONTRACTOR KNOW WHICH EXFILTRATION |
| TRENCH DETAIL TO USE? |
| |
| SHEETS ESC.3 AND D.3 |
| 1. PROVIDE SILT FENCE AROUND DEMOLITION AREA TO CONTROL |
| SEDIMENT MIGRATION. |
| |
| THE SFWMD ERP FOR THE DEVELOPMENT WILL NEED TO BE |
| PROVIDED. |
| |
| 8-18-21 - COMMENTS FROM LAURA LE, PUBLIC UTILITIES |
| ENG., [email protected], 561-494-1093: |
| |
| SHEET 3.3: |
| MANHOLE ELEVATIONS ARE ILLEGIBLE ON OUR PLAN SETS. |
| PLEASE REVISE. |
| PLEASE ADD NOTE TO CAP/GROUT ANY UNUSED EXISTING |
| SANITARY LATERALS GOING TO EXISTING MANHOLES. |
| PLEASE PROVIDE CCTV FROM ONSITE MANHOLE TO PARKER AVE. |
| |
| |
| FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| CONCERNS, THANKS. |
| RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES |
| DEPARTMENT (561) 494-1098 [email protected] |
| |
|