2009-11-12 07:26:01 | PROJECT HAS BEEN REVIEWED: STATUS IS FAILED DUE TO THE |
| FOLLOWING. |
| #1 REVISE COST ESTIMATE TO REFLECT ELEMENTS ON THE |
| PLAN. |
| MISSING COPPER PIPING, MISSING FIRELINE, MISSING SAMPLE |
| POINTS |
| (ONCE REVISED COST ESTIMATE MUST BE ACCEPTED BY BRIAN |
| MOREE) |
| #2 COLLECTION OF FEES BASED ON MIN $1,750 OR 5.5% OF |
| COST ESTIMATE (*BASED ON ENGINEERING FEE DIRECTORY) |
| (FEE HAS BEEN ACCEPTED) |
| #3 BASED ON COST ESTIMATE POST A SURETY FOR THE UTILITY |
| WORK IN TOPB, 110% OF THE UTILITY COST, PLUS THE BOND |
| ADMINISTRATION FEE $128.75. |
| #4 REVIEW CUSTOMER SERVICE METER QUOTE TO SEE IF |
| FEASIBLE RELOCATING METER. |
| (QUOTE HAS BEEN PROVIDED AND DISCUSSED WITH EOR) |
| #5 FUTURE CONDUITS MUST TERMINATE ON-SITE (THIS REVIEW |
| ONLY COVERS WATER ELEMENTS) |
| (A SEPARATE REQUEST MUST BE SENT IN IN WRITING TO ESD |
| REQUESTING PERMISSION TO CROSS CITY OF WPB WATERMAIN |
| WITH PRIVATE UTILITIES - IT IS ENCOURAGED THAT AN |
| EXHIBIT BE SUBMITTED) |
| #6 BACTEES WILL BE REQUIRED BY OUR DEPARTMENT BEFORE |
| SETTING METER DUE TO LENGTH OF SERVICE. |
| #7 PLANS ARE REQUIRED TO BE ON 24X36, PLEASE BE |
| PREPARED TO CHANGE TO THIS STANDARD AT THE NEXT PHASE. |
| #8 TAPPING VALVE WAS SHOW AT WRONG LOCATION. |
| #9 EXISTING FIREHYDRANT WAS NOT SHOWN, IT MUST BE 150' |
| MIN FROM THE FDC LOCATION. |
| #10 FDC LOCATION WAS NOT SHOWN, PLEASE SHOW. |
| REDLINED PLANS AND CERTIFIED CONSTRUCTION COST ESTIMATE |
| WHERE RETURNED TO EOR FOR REVISION 11/12/09. |
| MANUEL JULIAN GONZALEZ |
| ENGINEERING PROJECT COORDINATOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET, 4TH FLOOR |
| WEST PALM BEACH, FL 33401 |
| (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| MAIN PHONE: (561) 822-1200 |
| DIRECT: (561) 494-1085 |
| FAX: (561) 494-1116 |
| MOBILE: (561) 644-7301 |
| EMAIL: [email protected] |
| WWW.WPB.ORG/ENGINEERING |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
|
Print |