Plan Review Details - Project Z22080028
Plan Review Stops For Project Z22080028
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 08-25-2022 Cont ID  
Sent By scwelter Date 08-25-2022 Time 16:18 Rev Time 0.00
Received By swelter Date 02-02-2023 Time 13:55 Sent To  
Notes
2023-02-02 13:55:12 
 SITE PLAN APPROVAL DOES NOT INCLUDE APPROVAL OF ARTIST
 OR PUBLIC ART CONCEPT.
 ARTIST MUST BE IDENTIFIED AND APPROVED BEFORE BUILDING
 PERMIT SUBMITTAL.
  
2022-08-25 16:21:35PUBLIC ART IDENTIFIED ON SITE PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 09-07-2022 Cont ID  
Sent By rbrown Date 09-07-2022 Time 14:30 Rev Time 0.00
Received By rbrown Date 09-07-2022 Time 14:30 Sent To  
Notes
2022-09-07 14:34:13DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY
 LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER
 APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE
 PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE
 WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF
 FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION
 DISTANCE.
  
 4. VAN ACCESSIBLE PARKING SPACES. THE PLANS DO NOT SHOW
 A VAN ACCESSIBLE PARKING SPACE. PER SECTION 208.2.4 OF
 FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX REQUIRED
 ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING
 STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN
 ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY
 CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT
 SPACE AND VEHICULAR ACCESS ROUTE)
  
 5. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 6. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED. \
  
 7. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES
 NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO
 MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL
 BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 8. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 9. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 10. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 11. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status P Date 01-27-2023 Cont ID  
Sent By rrossano Date 01-27-2023 Time   Rev Time 0.00
Received By   Date 01-27-2023 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 12-16-2022 Cont ID  
Sent By rrossano Date 12-16-2022 Time   Rev Time 0.00
Received By rrossano Date 12-16-2022 Time   Sent To  
Notes
2022-12-16 11:11:26Z22080028 - 15TH AND LA KIRKSEY REZONING REVIEW
 12.16.22
 COMMENTS FOR CIVIL SUBMITTAL FROM RICK ROSSANO, SR.
 PROJECT COORDINATOR, ENGINEERING SERVICES AT
 561-494-1098 [email protected]
 O PROVIDE CCTV VIDEO OF EXISTING STORMWATER
 INFRASTRUCTURE ALONG ENTIRE PROJECT FRONTAGE (CONDITION
 OF SITE PLAN APPROVAL). SANITARY CCTV WAS PROVIDED IN
 12.16.22 RESUBMITTAL; NO STORMWATER CCTV OR REPORT
 FOUND.
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 08-23-2022 Cont ID  
Sent By rrossano Date 08-23-2022 Time   Rev Time 0.00
Received By rrossano Date 08-23-2022 Time   Sent To  
Notes
2022-08-23 14:03:47Z22080028 - 15TH AND LA KIRKSEY REZONING REVIEW 8.22.22
 COMMENTS FOR CIVIL SUBMITTAL FROM RICK ROSSANO, SR.
 PROJECT COORDINATOR, ENGINEERING SERVICES AT
 561-494-1098 [email protected]
 GENERAL:
 O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
 O THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK
 BELOW:
 A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP
 B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL
 L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97
 B1960045731D3658206F27451722716EF
 B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
 C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM
 BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08,
 ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU
 BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL
 O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
 O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS
 DATA.
  
 BACKFLOW ASSEMBLY AND METERS:
 O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER
 SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING
 TO THEM.
 O SHOW EXISTING AND PROPOSED DEDICATED UTILITY
 EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO
 STRUCTURES WITHIN EASEMENT.
 O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW
 PREVENTION.
 O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY
 OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER
 METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO
 PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE
 INSTALLED ABOVE-GROUND ONLY.
 O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE
 NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA.
  
 WATER/WASTEWATER PLAN:
 O PROVIDE VERTICAL DATUM AND DATUM CONVERSION
 INFORMATION (NAVD 1988 AND NGVD 1929).
 O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS.
 O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH
 PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE
 AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS,
 BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO
 BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS,
 DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS,
 ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT
 ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF
 SANITARY SEWER LINES.
 O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR
 SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW.
 O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS.
 O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL.
 O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES INCLUDING PIPE SIZE AND MATERIAL LOCATED IN
 THE RIGHT-OF-WAY.
 O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD
 DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. PLEASE
 INCLUDE FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES INCLUDING PIPE SIZE AND
 MATERIAL LOCATED IN THE RIGHT-OF-WAY.
 O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY
 TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT
 APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING
 AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE,
 MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS
 SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008
 FOR WATER.
 O PROVIDE FIRE FLOW TEST DATA.
 O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT FRONTAGE
 (CONDITION OF SITE PLAN APPROVAL).
 O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL
 BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY
 PROPOSED LENGTH IN FEET.
 O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE
 JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET.
 O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT
 STATION NUMBER.
 O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE.
 O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE
 TRAPS (IF ANY).
 O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN
 OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER.
  
 FORMAL ENGINEERING REVIEW:
 O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES
 NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS.
 O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF
 WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS.
 O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES
 ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY
 LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT
 PARCELS.
 O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE
 BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES.
 O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE
 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF
 PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER
 CITY OF WPB STANDARD DETAIL GC-8.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR
 PROPOSED IMPROVED AREAS.
  
 QUESTIONS AND COORDINATION CONTACTS:
 O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH
 CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF
 BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT
 561-822-2262 OR [email protected]
 O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES
 DEPARTMENT AT 561-494-1047 OR [email protected]
 O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING
 SERVICES DEPT. AT 561-494-1120 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 08-29-2022 Cont ID  
Sent By pleduc Date 08-29-2022 Time   Rev Time 0.00
Received By pleduc Date 08-29-2022 Time 12:53 Sent To  
Notes
2022-08-29 12:55:15THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT SITE PLAN.
  
 WITH THE LIMIT BUIDING INFORMATION PROVIDED, THE
 FOLLOWING COMMENTS ARE INTENDED TO PROVIDE GUIDANCE FOR
 BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY
 WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION
 CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE
 CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL
 BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED
 WITH THE BUREAU OF FIRE PREVENTION.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G
 AND SUBMITTED WITH THE MASTER PERMIT.
  
 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET AND BE INSTALLED PER THE
 REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH
 THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS
 OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING
 AND ZONING OFFICE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF
 TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY
 LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS.
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 CONTACT WILL NEED TO BE MADE TO MARK FILLA, PALM BEACH
 COUNTY PUBLIC SAFETY RADIO SYSTEMS MANAGER,
 [email protected], 561-233-0837; AS OUR RADIOS OPERATE
 ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND
 INSTALLATION INSTRUCTIONS.
  
 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 02-01-2023 Cont ID  
Sent By rcaranci Date 02-01-2023 Time 10:09 Rev Time 0.00
Received By rcaranci Date 02-01-2023 Time 10:08 Sent To  
Notes
2023-02-01 10:10:01FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 424 LA KIRKSEY Z22080028
 FEBRUARY 1, 2023
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON
 SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS
 SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD,
 MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS
 REPORT RATING THE CONDITION AND RELOCATION POTENTIAL
 FOR THE NATIVE TREES AND PALMS.
  
 2. SATISFIED. SHEET L-1.1, EXISTING TREES AND PALMS TO
 REMAIN OR BE RELOCATED CANNOT BE COUNTED TOWARD ANY
 MITIGATION DUE, REMOVE CREDITS FROM THE CHART AND
 PROVIDE REVISED TOTAL OF MITIGATION DUE. CONVERT ALL
 MITIGATION DUE TO SQUARE FOOTAGE.
  
 3. SATISFIED. SHEET L-1.1, MITIGATION CREDITS ARE NOT
 CORRECT, MUST USE THE CATEGORY LIST FOR TREE MITIGATION
 CREDITS. CATEGORY 1- 300 SQ FT CREDIT, CATEGORY - 150
 SQ FT CREDIT, CATEGORY 3- 100 SQ FT CREDIT, CATEGORY 4-
 50 SQ FT CREDIT. ANY SHORTFALL IN CANOPY CREDITS MUST
 BE CALCULATED FOR PAYMENT IN LIEU.
 MAKE THE FOLLOWING CORRECTIONS TO THE TREE MITIGATION
 CHART:
 ??? JACARANDA TRE#27 MITIGATION DUE IS 314 SQ FT.
 ??? TOTAL SHOULD BE 14,623 SQ FT MITIGATION DUE.
 ??? MITIGATION PROVIDED- SILVER BUTTONWOOD IS CATEGORY
 2 AT 150 SQ FT EACH.
 ??? CHANGE WAX MYRTLE TO LIGUSTRUM
 ??? TOTAL MITIGATION PROVIDED IS 9350 SQ FT
 ??? PROVIDE PAYMENT IN LIEU AMOUNT BASED ON $500.00 PER
 300 SQ FT CANOPY CREDIT.
  
 4. SATISFIED. PER SECTION 94-442(B)Q. SHOW TREES AND
 PALMS ON THE ADJACENT PROPERTIES WITHIN 10 FEET OF THE
 PROPERTY LINE.
  
 5. SATISFIED. PER SECTION 94-452, IRRIGATION MUST BE
 PROVIDED FOR THE RIGHT OF WAY LANDSCAPING. THE EXISTING
 PLANTING AREAS ALONG LA KIRKSEY WERE DESIGNED AS
 BIOSWALES TO ACCEPT STORMWATER RUNOFF. STAFF RECOMMENDS
 DESIGNING TO MAINTAIN THIS INTENT. SHADE TREES ARE
 PREFERRED TO BE ADDED TO S DIXIE RIGHT OF WAY TO
 PROVIDE SHADE FOR PEDESTRIANS.
  
 6. CONDITIONALLY SATISFIED. PROVIDE A PRELIMINARY
 APPROVAL LETTER FROM FDOT FOR THE LANDSCAPING IN THE
 RIGHT OF WAY.
  
 7. SATISFIED. TAG FOR QVR/2 IS NOT INDICATING THE
 CORRECT SYMBOL ON THE PLAN. INDICATE IF THE CURRENT
 TREE CANOPY WILL PROVIDE THE REQUIRED 14 FOOT CLEARANCE
 FOR TRAFFIC IF RELOCATED TO THE RIGHT OF WAY.
  
 8. SATISFIED. PROVIDE A DETAIL AND SHOW THE LOCATIONS
 OF THE REQUIRED STRUCTURAL SOIL UNDER THE ADJACENT
 SIDEWALK OR HARDSCAPE AREAS FOR THE STREETSCAPE.
  
 STRUCTURAL SOIL SHOULD ONLY BE SHOWN IN AREAS THAT ARE
 PAVED, ALL UNPAVED AREAS WILL BE SHOWN AS PLANTING
 SOIL.
 CORRECTED SHEETS SUBMITTED 2/2/23.
  
  
 9. SATISFIED. LANDSCAPE BUFFER OF 5 FEET IS REQUIRED ON
 THE EAST SIDE OF THE ACCESS ROAD FROM THE ALLEY WITH
 THE REQUIRED TREES. THIS IS TO PROVIDE PROTECTION FOR
 THE ADJACENT RESIDENTIAL. PALMS OR SMALLER TREES MAY BE
 USED AGAINST THE BUILDING TO PROVIDE ADDITIONAL
 SCREENING WITHOUT CAUSING MAINTENANCE ISSUES.
  
 10. SATISFIED. SOUTH LANDSCAPE BUFFER ALONG THE ALLEY
 HAS A LARGE GAP IN THE BUFFER TREES THAT MUST BE
 CORRECTED TO MEET THE REQUIREMENTS.
  
 11. SATISFIED. THE TERMINAL LANDSCAPE ISLANDS OUTSIDE
 THE BUILDING FOOTPRINT MUST MEET THE 8 FOOT WIDTH
 LANDSCAPE REQUIREMENT. CALCULATIONS FOR THE 75% SHADE
 TREE REQUIREMENT ARE PROVIDED, BUT DO NOT MATCH WHAT IS
 SHOWN ON THE PLAN.
  
  
 12. SATISFIED. WATER LINES COMING INTO THE BUILDING
 FROM THE WEST SIDE NEED TO BE RELOCATED TO ALLOW THE
 REQUIRED BUFFER TREES TO BE LOCATED WITHOUT CONFLICT TO
 PROVIDE PROTECTION FOR THE ADJACENT RESIDENTIAL USE.
  
  
 13. SATISFIED. PROVIDE SCREENING HEDGES FOR ALL GROUND
 MOUNTED VALVES AND EQUIPMENT CURRENTLY SHOWN ON THE
 LANDSCAPE PLAN.
  
 14. SATISFIED. SHOW THE REQUIRED D CURBS FOR ALL
 LANDSCAPE AREAS ADJACENT TO VEHICULAR USE AREAS.
  
 15. SATISFIED. WAX MYRTLES DO NOT MEET THE MINIMUM
 HEIGHT REQUIREMENT FOR TREES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE STREET TREES AND
 RIGHT OF WAY LANDSCAPING AND IRRIGATION. THIS WILL BE
 THROUGH A SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
 4. STREETSCAPE IN FDOT RIGHT OF WAY MUST RECEIVE FDOT
 PERMIT APPROVAL PRIOR TO ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY FOR THE BUILDING.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 01-13-2023 Cont ID  
Sent By rcaranci Date 01-13-2023 Time 16:20 Rev Time 0.00
Received By rcaranci Date 01-13-2023 Time 16:20 Sent To  
Notes
2023-01-13 16:21:13FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 424 LA KIRKSEY Z22080028
 JANUARY 13, 2023
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON
 SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS
 SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD,
 MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS
 REPORT RATING THE CONDITION AND RELOCATION POTENTIAL
 FOR THE NATIVE TREES AND PALMS.
  
 2. SATISFIED. SHEET L-1.1, EXISTING TREES AND PALMS TO
 REMAIN OR BE RELOCATED CANNOT BE COUNTED TOWARD ANY
 MITIGATION DUE, REMOVE CREDITS FROM THE CHART AND
 PROVIDE REVISED TOTAL OF MITIGATION DUE. CONVERT ALL
 MITIGATION DUE TO SQUARE FOOTAGE.
  
 3. PARTIALLY SATISFIED. SHEET L-1.1, MITIGATION CREDITS
 ARE NOT CORRECT, MUST USE THE CATEGORY LIST FOR TREE
 MITIGATION CREDITS. CATEGORY 1- 300 SQ FT CREDIT,
 CATEGORY - 150 SQ FT CREDIT, CATEGORY 3- 100 SQ FT
 CREDIT, CATEGORY 4- 50 SQ FT CREDIT. ANY SHORTFALL IN
 CANOPY CREDITS MUST BE CALCULATED FOR PAYMENT IN LIEU.
 MAKE THE FOLLOWING CORRECTIONS TO THE TREE MITIGATION
 CHART:
 ??? JACARANDA TRE#27 MITIGATION DUE IS 314 SQ FT.
 ??? TOTAL SHOULD BE 14,623 SQ FT MITIGATION DUE.
 ??? MITIGATION PROVIDED- SILVER BUTTONWOOD IS CATEGORY
 2 AT 150 SQ FT EACH.
 ??? CHANGE WAX MYRTLE TO LIGUSTRUM
 ??? TOTAL MITIGATION PROVIDED IS 9350 SQ FT
 ??? PROVIDE PAYMENT IN LIEU AMOUNT BASED ON $500.00 PER
 300 SQ FT CANOPY CREDIT.
  
 4. SATISFIED. PER SECTION 94-442(B)Q. SHOW TREES AND
 PALMS ON THE ADJACENT PROPERTIES WITHIN 10 FEET OF THE
 PROPERTY LINE.
  
 5. SATISFIED. PER SECTION 94-452, IRRIGATION MUST BE
 PROVIDED FOR THE RIGHT OF WAY LANDSCAPING. THE EXISTING
 PLANTING AREAS ALONG LA KIRKSEY WERE DESIGNED AS
 BIOSWALES TO ACCEPT STORMWATER RUNOFF. STAFF RECOMMENDS
 DESIGNING TO MAINTAIN THIS INTENT. SHADE TREES ARE
 PREFERRED TO BE ADDED TO S DIXIE RIGHT OF WAY TO
 PROVIDE SHADE FOR PEDESTRIANS.
  
 6. CONDITIONALLY SATISFIED. PROVIDE A PRELIMINARY
 APPROVAL LETTER FROM FDOT FOR THE LANDSCAPING IN THE
 RIGHT OF WAY.
  
 7. TAG FOR QVR/2 IS NOT INDICATING THE CORRECT SYMBOL
 ON THE PLAN. INDICATE IF THE CURRENT TREE CANOPY WILL
 PROVIDE THE REQUIRED 14 FOOT CLEARANCE FOR TRAFFIC IF
 RELOCATED TO THE RIGHT OF WAY.
  
 8. PARTIALLY SATISFIED. PROVIDE A DETAIL AND SHOW THE
 LOCATIONS OF THE REQUIRED STRUCTURAL SOIL UNDER THE
 ADJACENT SIDEWALK OR HARDSCAPE AREAS FOR THE
 STREETSCAPE.
  
 STRUCTURAL SOIL SHOULD ONLY BE SHOWN IN AREAS THAT ARE
 PAVED, ALL UNPAVED AREAS WILL BE SHOWN AS PLANTING
 SOIL.
  
  
 9. SATISFIED. LANDSCAPE BUFFER OF 5 FEET IS REQUIRED ON
 THE EAST SIDE OF THE ACCESS ROAD FROM THE ALLEY WITH
 THE REQUIRED TREES. THIS IS TO PROVIDE PROTECTION FOR
 THE ADJACENT RESIDENTIAL. PALMS OR SMALLER TREES MAY BE
 USED AGAINST THE BUILDING TO PROVIDE ADDITIONAL
 SCREENING WITHOUT CAUSING MAINTENANCE ISSUES.
  
 10. SATISFIED. SOUTH LANDSCAPE BUFFER ALONG THE ALLEY
 HAS A LARGE GAP IN THE BUFFER TREES THAT MUST BE
 CORRECTED TO MEET THE REQUIREMENTS.
  
 11. SATISFIED. THE TERMINAL LANDSCAPE ISLANDS OUTSIDE
 THE BUILDING FOOTPRINT MUST MEET THE 8 FOOT WIDTH
 LANDSCAPE REQUIREMENT. CALCULATIONS FOR THE 75% SHADE
 TREE REQUIREMENT ARE PROVIDED, BUT DO NOT MATCH WHAT IS
 SHOWN ON THE PLAN.
  
  
 12. SATISFIED. WATER LINES COMING INTO THE BUILDING
 FROM THE WEST SIDE NEED TO BE RELOCATED TO ALLOW THE
 REQUIRED BUFFER TREES TO BE LOCATED WITHOUT CONFLICT TO
 PROVIDE PROTECTION FOR THE ADJACENT RESIDENTIAL USE.
  
  
 13. SATISFIED. PROVIDE SCREENING HEDGES FOR ALL GROUND
 MOUNTED VALVES AND EQUIPMENT CURRENTLY SHOWN ON THE
 LANDSCAPE PLAN.
  
 14. SATISFIED. SHOW THE REQUIRED D CURBS FOR ALL
 LANDSCAPE AREAS ADJACENT TO VEHICULAR USE AREAS.
  
 15. SATISFIED. WAX MYRTLES DO NOT MEET THE MINIMUM
 HEIGHT REQUIREMENT FOR TREES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE STREET TREES AND
 RIGHT OF WAY LANDSCAPING AND IRRIGATION. THIS WILL BE
 THROUGH A SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
 4. STREETSCAPE IN FDOT RIGHT OF WAY MUST RECEIVE FDOT
 PERMIT APPROVAL PRIOR TO ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY FOR THE BUILDING.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 09-06-2022 Cont ID  
Sent By rcaranci Date 09-06-2022 Time 16:53 Rev Time 0.00
Received By rcaranci Date 09-06-2022 Time 16:53 Sent To  
Notes
2022-09-06 16:54:17FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 424 LA KIRKSEY Z22080028
 SEPTEMBER 6, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES AND
 PALMS IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY
 EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR
 POOR FOR RELOCATION. PROVIDE AN ARBORISTS REPORT RATING
 THE CONDITION AND RELOCATION POTENTIAL FOR THE NATIVE
 TREES AND PALMS.
  
 2. SHEET L-1.1, EXISTING TREES AND PALMS TO REMAIN OR
 BE RELOCATED CANNOT BE COUNTED TOWARD ANY MITIGATION
 DUE, REMOVE CREDITS FROM THE CHART AND PROVIDE REVISED
 TOTAL OF MITIGATION DUE. CONVERT ALL MITIGATION DUE TO
 SQUARE FOOTAGE.
  
 3. SHEET L-1.1, MITIGATION CREDITS ARE NOT CORRECT,
 MUST USE THE CATEGORY LIST FOR TREE MITIGATION CREDITS.
 CATEGORY 1- 300 SQ FT CREDIT, CATEGORY - 150 SQ FT
 CREDIT, CATEGORY 3- 100 SQ FT CREDIT, CATEGORY 4- 50 SQ
 FT CREDIT. ANY SHORTFALL IN CANOPY CREDITS MUST BE
 CALCULATED FOR PAYMENT IN LIEU.
  
 4. PER SECTION 94-442(B)Q. SHOW TREES AND PALMS ON THE
 ADJACENT PROPERTIES WITHIN 10 FEET OF THE PROPERTY
 LINE.
  
 5. PER SECTION 94-452, IRRIGATION MUST BE PROVIDED FOR
 THE RIGHT OF WAY LANDSCAPING. THE EXISTING PLANTING
 AREAS ALONG LA KIRKSEY WERE DESIGNED AS BIOSWALES TO
 ACCEPT STORMWATER RUNOFF. STAFF RECOMMENDS DESIGNING TO
 MAINTAIN THIS INTENT. SHADE TREES ARE PREFERRED TO BE
 ADDED TO S DIXIE RIGHT OF WAY TO PROVIDE SHADE FOR
 PEDESTRIANS.
  
 6. PROVIDE A PRELIMINARY APPROVAL LETTER FROM FDOT FOR
 THE LANDSCAPING IN THE RIGHT OF WAY.
  
 7. TAG FOR QVR/2 IS NOT INDICATING THE CORRECT SYMBOL
 ON THE PLAN. INDICATE IF THE CURRENT TREE CANOPY WILL
 PROVIDE THE REQUIRED 14 FOOT CLEARANCE FOR TRAFFIC IF
 RELOCATED TO THE RIGHT OF WAY.
  
 8. PROVIDE A DETAIL AND SHOW THE LOCATIONS OF THE
 REQUIRED STRUCTURAL SOIL UNDER THE ADJACENT SIDEWALK OR
 HARDSCAPE AREAS FOR THE STREETSCAPE.
  
 9. LANDSCAPE BUFFER OF 5 FEET IS REQUIRED ON THE EAST
 SIDE OF THE ACCESS ROAD FROM THE ALLEY WITH THE
 REQUIRED TREES. THIS IS TO PROVIDE PROTECTION FOR THE
 ADJACENT RESIDENTIAL. PALMS OR SMALLER TREES MAY BE
 USED AGAINST THE BUILDING TO PROVIDE ADDITIONAL
 SCREENING WITHOUT CAUSING MAINTENANCE ISSUES.
  
 10. SOUTH LANDSCAPE BUFFER ALONG THE ALLEY HAS A LARGE
 GAP IN THE BUFFER TREES THAT MUST BE CORRECTED TO MEET
 THE REQUIREMENTS.
  
 11. THE TERMINAL LANDSCAPE ISLANDS OUTSIDE THE BUILDING
 FOOTPRINT MUST MEET THE 8 FOOT WIDTH LANDSCAPE
 REQUIREMENT. CALCULATIONS FOR THE 75% SHADE TREE
 REQUIREMENT ARE PROVIDED, BUT DO NOT MATCH WHAT IS
 SHOWN ON THE PLAN.
  
  
 12. WATER LINES COMING INTO THE BUILDING FROM THE WEST
 SIDE NEED TO BE RELOCATED TO ALLOW THE REQUIRED BUFFER
 TREES TO BE LOCATED WITHOUT CONFLICT TO PROVIDE
 PROTECTION FOR THE ADJACENT RESIDENTIAL USE.
  
  
 13. PROVIDE SCREENING HEDGES FOR ALL GROUND MOUNTED
 VALVES AND EQUIPMENT CURRENTLY SHOWN ON THE LANDSCAPE
 PLAN.
  
 14. SHOW THE REQUIRED D CURBS FOR ALL LANDSCAPE AREAS
 ADJACENT TO VEHICULAR USE AREAS.
  
 15. WAX MYRTLES DO NOT MEET THE MINIMUM HEIGHT
 REQUIREMENT FOR TREES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE STREET TREES AND
 RIGHT OF WAY LANDSCAPING AND IRRIGATION. THIS WILL BE
 THROUGH A SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status P Date 01-30-2023 Cont ID  
Sent By mtechnow Date 01-30-2023 Time 11:01 Rev Time 0.00
Received By mtechnow Date 01-30-2023 Time 11:01 Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 09-08-2022 Cont ID  
Sent By mtechnow Date 09-08-2022 Time 11:48 Rev Time 0.00
Received By mtechnow Date 09-08-2022 Time 11:40 Sent To  
Notes
2022-09-08 11:48:20-UTILITIES IS REVIEWING THE PROPOSED WATER SERVICE
 CONNECTIONS ON 15TH ST TO VERIFY THAT THERE IS ADEQUATE
 CAPACITY.
 -REVISE THE SERVICE CONNECTION POINT ON 14TH ST TO
 CONNECT TO THE EXISITING 8" WM ON DIXIE.

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 2 Status P Date 12-19-2022 Cont ID  
Sent By mhurley Date 12-19-2022 Time 10:14 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2022-12-19 10:13:41-LABEL FDC OR ADD SYMBOL TO LEGEND AT ENGINEERING
 DEVELOPMENT SUBMITTAL.
 -PROVIDE CLEARANCE DISTANCE BETWEEN EXISTING HYDRANT
 AND PROPOSED STORMWATER PIPE AT ENGINEERING DEVELOPMENT
 SUBMITTAL.
 -AT ENGINEERING DEVELOPMENT SUBMITTAL, UPDATE PLANS SO
 BACKFLOW ASSEMBLIES ARE NOT IN UTILITY EASEMENTS.
 -UPON FURTHER REVIEW AT ENGINEERING DEVELOPMENT
 SUBMITTAL, MAY NEED TO REMOVE EXISTING SEWER LATERALS
 AND MAY NEED TO EXPAND LIMITS OF PAVEMENT RESTORATION
 ON DIXIE.
 --AT ENGINEERING DEVELOPMENT SUBMITTAL, SHOW EXISTING
 WATER SERVICES GOING NORTH FROM WATER MAIN ON L A
 KIRKSEY.

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 1 Status F Date 09-02-2022 Cont ID  
Sent By mhurley Date 09-02-2022 Time 11:40 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2022-09-02 11:40:23PLEASE PROVIDE WRITTEN RESPONSES THE FOLLOWING:
 -ADD LEGEND TO EACH ENGINEERING PLAN SHEET SHOWING
 SYMBOLS AND LINES USED THAT ARE NOT OTHERWISE LABELED.
 -SHOW UTILITY EASEMENTS ON SHEET C05. BACKFLOW
 ASSEMBLIES SHOULD NOT BE IN UTILITY EASEMENTS.
 -CALLOUT THE RP BACKFLOW ASSEMBLIES FOR THE PROPOSED 1
 INCH METERED WATER SERVICES. ENSURE LABEL HAS SIZING.
 -SHOW AND LABEL SEWER LATERAL CLEANOUTS.
 -IS THE 2 INCH METER FOR IRRIGATION? IF NOT, IS A
 METERED IRRIGATION WATER SERVICE NEEDED?
 -ON DEMO PLAN SHOW AND EXISTING METERED WATER SERVICES
 AND LABEL WHAT IS HAPPENING TO THEM.
 -PROVIDE CLEARANCE DISTANCE BETWEEN SOUTHERN BUSH AND
 BACKFLOW ASSEMBLY SHOWN ON LANDSCAPING PLAN L2.0.
 -SHOW AND LABEL FDC ON PLANS IF ANY ARE NEEDED OR
 REQUIRED.
 -SHOW AND LABEL ALL EXISTING UTILITY POLES, LIGHT
 POLES, AND GUY WIRES NEAR PROPERTY ON ENGINEERING PLAN
 SHEETS IF THEY WILL REMAIN.
 -LABEL THE STREETS ON DEMO PLAN.
 -ONE OF THE STORMWATER LINES ON DIXIE SHOWS IT IN CLOSE
 PROXIMITY TO WATER MAIN. IS THAT CORRECT?
 -VERIFY THERE IS NO UTILITY OR FPL EASEMENTS RUNNING
 ALONG ALLEY.
 -ON AUTOTURN EXHIBIT, PLEASE SHOW UTILITY VAC TRUCK 7
 FEET WIDE, 13 FEET HIGH, AND 36 FOOT LONG CAN
 SUCCESSFULLY NAVIGATE THROUGH PROPOSED ONE WAY ALLEY
 TURN.
 -IF THERE WILL BE ANY GREASE TRAPS OUTSIDE BUILDING,
 THEN SHOW AND LABEL ON PLANS.
 -MAY HAVE TO GRANT UTILITY EASEMENT FOR PROPOSED
 SANITARY SEWER MAIN.
 -LABEL ADJACENT PROPERTY ADDRESSES ON ENGINEERING PLAN
 SHEETS.
 -SHOW EXISTING SEWER LATERALS AND LABEL WHAT IS
 HAPPENING TO THEM.
 RESPECTFULLY,
 MARK HURLEY [email protected]
  

Review Stop PW PUBLIC WORKS
Rev No 3 Status P Date 01-31-2023 Cont ID  
Sent By   Date 01-31-2023 Time   Rev Time 0.00
Received By   Date 01-31-2023 Time   Sent To  
Notes
2023-01-31 11:57:35NO FURTHER COMMENTS.

Review Stop PW PUBLIC WORKS
Rev No 2 Status F Date 01-18-2023 Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date 01-18-2023 Time   Sent To  
Notes
2023-01-18 14:20:18PLEASE PROVIDE A REVISED AUTOTURN EXHIBIT, SHEET C-07,
 TO REFLECT:
 1- THE CORRECT SANITATION COLLECTION TRUCK (FRONT
 LOADER) WITH DYNAMIC ENVELOPE AND THE VEHICLE???S WHEEL
 PATH IDENTIFIED WITH DIFFERENT COLORS FOR THE
 SANITATION SERVICE, FRONT LOADER TRUCK WITH THE
 FOLLOWING SPECS:
 - DUAL AXLES
 - TRUCK LENGTH: 35 FT
 - TRUCK WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
 2- REVISE S.E. TURNING RADII TO PREVENT ANY POTENTIAL
 ENCROACHMENT FOR THE SANITATION COLLECTION TRUCK.
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 5461-822-2045

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 08-25-2022 Cont ID  
Sent By   Date 08-25-2022 Time   Rev Time 0.00
Received By   Date 08-25-2022 Time   Sent To  
Notes
2022-08-25 11:32:42PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND
 QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR)
 THAT WILL BE UTILIZED FOR THE SANITATION SERVICE.
 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE
 CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.). FOR A
 FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE
 SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST
 PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE
 STANDARD, GC-7. (LINK TO THE LATEST REVISION OF THE
 GC-7 DOCUMENT: HTTPS://WWW.WPB.ORG/HOME/SHOWPUBLISHEDDO
 CUMENT/3690/637629060422100000)
 3- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE?S
 WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER
 TRUCK WITH THE FOLLOWING SPECS:
 - DUAL AXLES
 - TRUCK LENGTH: 35 FT
 - TRUCK WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
 4- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND
 RECYCLING CONTAINERS
 5- OWNERS AND/OR OCCUPANTS OF PROPERTY THAT REQUIRE
 GREASE HAULING SERVICES SHALL ENSURE THAT THEIR GREASE
 TANKS OR CONTAINERS REMAIN CLEAN, AND ARE ENCLOSED AND
 NOT IN PUBLIC VIEW.
 6- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN
 THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF
 THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC
 WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND
 COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING
 MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE
 CAN(S).
 7- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE
 CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA
 STATUES [553.5041 F.S.].
 8- SIGNAGE PLAN. ALL STRIPING AND SIGNAGE SHALL COMPLY
 WITH THE LATEST CITY OF WEST PALM BEACH STANDARD
 DETAILS AND MEET THE M.U.T.C.D. LATEST EDITION.
 9- ALL PAVEMENT MARKING , SIGNING AND SIDEWALK DAMAGED
 DURING CONSTRUCTION SHALL BE RESTORED.
  
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 1 Status P Date 09-08-2022 Cont ID  
Sent By tward Date 09-08-2022 Time 12:58 Rev Time 0.00
Received By tward Date 09-08-2022 Time 12:59 Sent To  
Notes
2022-09-08 12:59:10SEE COMMENTS UNDER Z22080027.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 01-19-2023 Cont ID  
Sent By vnoel Date 01-19-2023 Time 06:28 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2023-01-19 06:28:09CONDITION OF REPLAT PRIOR TO C.O.
 SEE COMMENTS UNDER Z22080029

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 09-06-2022 Cont ID  
Sent By vnoel Date 09-06-2022 Time 11:22 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2022-09-06 11:22:501. REPLAT WILL BE REQUIRED.
 2. APPROVAL REQUIRED FROM FDOT FOR IMPROVEMENTS AND
 MANHOLES IN SIDEWALK.
 3. ALLEY WILL BE BY EASEMENT FOR ACCESS AND UTILITIES
 WITH MAINTENANCE OBLIGATION BY APPLICANT.
 4. CHECK DESCRIPTION OF LOT 17 ON SURVEY, S/B PLAT BOOK
 1 , PAGE 127.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date 01-31-2023 Cont ID  
Sent By   Date 01-31-2023 Time   Rev Time 0.00
Received By   Date 01-31-2023 Time   Sent To  
Notes
2023-01-31 16:17:40APPROVED WITH THE FOLLOWING CONDITIONS:
 1. PROVIDE A REVISED AUTOTURN ANALYSIS, SHOWCASING A
 LEGEND AND MITIGATING THE HIGHLIGHTED ENCROACHMENTS
 2. PROVIDE A REVISED SITE PLAN TO ADDRESS LATEST
 TRANSPORTATION COMMENTS PERTAINING SIGNAGE AND PAVEMENT
 MARKINGS
 REVISED TRANSPORTATION SITE PLAN AND AUTOTURN DRAWINGS,
 INCLUSIVE OF DETAILED CITY COMMENTS, WERE PROVIDED TO
 JOSEPH VERDONE ON 1/31/2023 VIA EMAIL.
  
 PAST TRAFFIC COMMENTS
 1) SATISFIED. PROVIDE A FULL DETAILED TRAFFIC STUDY
 2) SATISFIED. PROVIDE COUNTY TPS LETTER
 3) SATISFIED. DEPENDING ON THE OUTCOME OF THE TRAFFIC
 ANALYSIS, TRANSPORTATION DEMAND MANAGEMENT (TDM)
 MEASURES MAY BE REQUIRED
 4) SATISFIED. THE TRAFFIC ANALYSIS FOR THE LUPA
 APPLICATION HAS SIGNIFICANT TRIP GENERATION DIFFERENCES
 AND RESULTS WITH RESPECT TO THE LATEST TRAFFIC STUDY.
 PLEASE CORRECT, REVISE, AND RE-SUBMIT BOTH DOCUMENTS
 FOR SAKE OF CONSISTENCY
 5) SATISFIED. PROVIDE A CLEAN TRANSPORTATION SPECIFIC
 SITE PLAN FOR THE GROUND FLOOR. SHOWCASING
 TRANSPORTATION RELATED FEATURES (E.G. ROADWAY WIDTHS,
 DRIVING AISLES, PARKING STALLS, SIDEWALK, CURB, GUTTER,
 DRIVEWAY, GATES, CROSSWALKS, VISIBILITY TRIANGLE,
 CORNER & DRIVEWAY SEPARATION DISTANCES, SLOPES, ETC.)
 PROPERLY LABELED AND DIMENSIONED. THE SITE PLAN SHOULD
 BE NAMED T-1.0. PROVIDE TRAVEL LANE(S) DIMENSION FOR
 14TH AND 15TH STREETS AT THE INTERSECTION WITH DIXIE
 HWY
 6) SATISFIED. IN THE T-1.0 SITE PLAN, PLEASE SHOWCASE
 BASIC CURB DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT
 MARKINGS, PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF
 THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT. SEVERAL
 PAVEMENT MARKINGS ALONG THE NORTHERN SIDE OF 15TH ST
 ARE MISSING
 7) SATISFIED. PROVIDE A SIGNAGE AND PAVEMENT MARKING
 PLAN. INCLUSIVE OF ALL FEATURES WITHIN THE PROPOSED
 DEVELOPMENT AND ALONG ALL ROADS FRONTING THE SITE. THE
 SITE PLAN IS PART OF THE TRANSPORTATION REVIEW AND
 SHOULD BE NAMED ACCORDINGLY (E.G. T-1.1 OR T-2.0)
 8) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND
 WHEEL PATHS CLEARLY DISTINCT AND DEFINED IN DIFFERENT
 COLORS. SITE PLAN(S) CONTAINING THE ANALYSIS ARE PART
 OF THE TRANSPORTATION REVIEW AND SHOULD BE NAMED
 ACCORDINGLY (E.G. T1.2, T-3.0)
 9) SATISFIED. PROVIDE ENGINEERING REFERENCE AND SPECS
 SHEETS FOR EACH OF THE PROPOSED TRANSPORTATION FEATURES
 (E.G. CURB, RAMP, GATE, SIGNAGE, PAVEMENT MARKING,
 SIGNAL, ETC.)
 10) SATISFIED. IN THE PAVEMENT, MARKING & SIGN PLAN,
 PROVIDE A TABLE SHOWCASING THE NUMBER OF EXISTING AND
 PROPOSED ON-STREET PARKING STALLS. PROVIDE THE NUMBER
 OF METERED STALLS THAT ARE BEING REMOVED OR RELOCATED,
 IF ANY
 11) SATISFIED. ARE THERE ANY GATES PROPOSED? IF SO,
 CLEARLY SHOWCASE THE REQUIRED 20 FEET SETBACK DISTANCE
 FROM THE BACK OF THE SIDEWALK
 12) SATISFIED. FOR SAFETY AND OPERATIONAL PURPOSES, NO
 NEW ON-STREET PARKING STALLS ADJACENT TO THE BIKE LANE
 AND IN THE PROXIMITY OF AN INTERSECTION SHALL BE
 ALLOWED. PLEASE REVISE THE SITE PLANS ACCORDINGLY
 13) SATISFIED. PLEASE PROVIDE A COMPLETE PARKING TABLE,
 SHOWCASING THE NUMBER OF REQUIRED AND PROVIDED PARKING
 STALLS, INCLUSIVE OF ADA AND BICYCLE ONES. PROVIDE CITY
 CODE REFERENCE FOR THE CALCULATION
 14) SATISFIED. THE PROPOSED FULL-ACCESS DRIVEWAY ON
 15TH ST SHOULD BE EXIT-ONLY, WHILE CONVERTING THE
 PROPOSED WESTERN EXIT-ONLY DRIVEWAY TO A FULL-ACCESS
 ONE. MOREOVER, THE EASTERN DRIVEWAY NEEDS TO BE 125
 FEET AWAY FROM THE INTERSECTION, PER FDOT CORNER
 CLEARANCE REQUIREMENT. PLEASE SHOWCASE SUCH DISTANCE IN
 THE TRANSPORTATION PLAN. LATEST RESUBMISSION DOES NOT
 SHOW THE REQUIRED (AND REQUESTED) 125 FEET CORNER
 CLEARANCE DISTANCE
 15) SATISFIED. THE ALLEY MUST BE DESIGNATED ONE-WAY
 ONLY. CORRESPONDING SIGNAGE AND PAVEMENT MARKING
 INSTALLED AND SHOWN ON THE PLANS. PLEASE COORDINATE
 WITH PUBLIC WORKS PERTAINING THE DIRECTIONALITY AND
 NOTIFY TRAFFIC ENGINEERING ABOUT THE FINAL DECISION.
 PLEASE DESIGNATE THE ALLEY EAST/SOUTHBOUND, AND PROVIDE
 ACKNOWLEDGMENT THAT IT WILL BE RE-PAVED, PAVEMENT
 MARKED, AND SIGNED ACCORDINGLY THROUGHOUT
 16) SATISFIED. PROPOSED ON-STREET PARKING STALLS ON
 14TH ST MAY NOT MEET CORNER CLEARANCE REQUIREMENT (125
 FEET). PLEASE SHOWCASE SUCH DISTANCE IN THE
 TRANSPORTATION PLAN
 17) PARTIALLY SATISFIED. PROVIDE AUTOTURN SHOWCASING AN
 SUV SIZED VEHICLE TRAVERSING THE ALLEYWAY, SO TO VERIFY
 THE FEASIBILITY OF ITS RE-ALIGNMENT (I.E. TURNING
 POINT)
 18) SATISFIED. PLEASE VERIFY DIMENSIONS AND
 CONFIGURATION OF THE WESTERN LEG AT THE 15TH AND DIXIE
 HWY INTERSECTION. EXISTING PAVEMENT MARKINGS ARE
 SHOWING A SLIGHT KINK TO ACCOMMODATE 10-FEET TRAVEL
 LANES. PROPOSED SITE PLANS SHOW A STRAIGHTENING OF THE
 DOUBLE-YELLOW LINES, WHICH MAY NOT BE FEASIBLE DUE TO
 GEOMETRIC AND DRAINAGE CONSTRAINTS
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 09-07-2022 Cont ID  
Sent By   Date 09-07-2022 Time   Rev Time 0.00
Received By   Date 09-07-2022 Time   Sent To  
Notes
2022-09-07 23:34:51TRAFFIC COMMENTS
 1) PROVIDE A FULL DETAILED TRAFFIC STUDY
 2) PROVIDE COUNTY TPS LETTER
 3) DEPENDING ON THE OUTCOME OF THE TRAFFIC ANALYSIS,
 TRANSPORTATION DEMAND MANAGEMENT (TDM) MEASURES MAY BE
 REQUIRED
  
 SITE COMMENTS
 4) PROVIDE A CLEAN TRANSPORTATION SPECIFIC SITE PLAN
 FOR THE GROUND FLOOR. SHOWCASING TRANSPORTATION RELATED
 FEATURES (E.G. ROADWAY WIDTHS, DRIVING AISLES, PARKING
 STALLS, SIDEWALK, CURB, GUTTER, DRIVEWAY, GATES,
 CROSSWALKS, VISIBILITY TRIANGLE, CORNER & DRIVEWAY
 SEPARATION DISTANCES, SLOPES, ETC.) PROPERLY LABELED
 AND DIMENSIONED. THE SITE PLAN SHOULD BE NAMED T-1.0
 5) IN THE T-1.0 SITE PLAN, PLEASE SHOWCASE BASIC CURB
 DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT MARKINGS,
 PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF THE ROADS
 SURROUNDING THE PROPOSED DEVELOPMENT
 6) PROVIDE A SIGNAGE AND PAVEMENT MARKING PLAN.
 INCLUSIVE OF ALL FEATURES WITHIN THE PROPOSED
 DEVELOPMENT AND ALONG ALL ROADS FRONTING THE SITE. THE
 SITE PLAN IS PART OF THE TRANSPORTATION REVIEW AND
 SHOULD BE NAMED ACCORDINGLY (E.G. T-1.1 OR T-2.0)
 7) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR
 SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED
 DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL
 PATHS CLEARLY DISTINCT AND DEFINED IN DIFFERENT COLORS.
 SITE PLAN(S) CONTAINING THE ANALYSIS ARE PART OF THE
 TRANSPORTATION REVIEW AND SHOULD BE NAMED ACCORDINGLY
 (E.G. T1.2, T-3.0)
 8) PROVIDE ENGINEERING REFERENCE AND SPECS SHEETS FOR
 EACH OF THE PROPOSED TRANSPORTATION FEATURES (E.G.
 CURB, RAMP, GATE, SIGNAGE, PAVEMENT MARKING, SIGNAL,
 ETC.)
 9) IN THE PAVEMENT, MARKING & SIGN PLAN, PROVIDE A
 TABLE SHOWCASING THE NUMBER OF EXISTING AND PROPOSED
 ON-STREET PARKING STALLS. PROVIDE THE NUMBER OF METERED
 STALLS THAT ARE BEING REMOVED OR RELOCATED, IF ANY
 10) ARE THERE ANY GATES PROPOSED? IF SO, CLEARLY
 SHOWCASE THE REQUIRED 20 FEET SETBACK DISTANCE FROM THE
 BACK OF THE SIDEWALK
 11) FOR SAFETY AND OPERATIONAL PURPOSES, NO NEW
 ON-STREET PARKING STALLS ADJACENT TO THE BIKE LANE AND
 IN THE PROXIMITY OF AN INTERSECTION SHALL BE ALLOWED.
 PLEASE REVISE THE SITE PLANS ACCORDINGLY
 12) PLEASE PROVIDE A COMPLETE PARKING TABLE, SHOWCASING
 THE NUMBER OF REQUIRED AND PROVIDED PARKING STALLS,
 INCLUSIVE OF ADA AND BICYCLE ONES. PROVIDE CITY CODE
 REFERENCE FOR THE CALCULATION
 13) THE PROPOSED FULL-ACCESS DRIVEWAY ON 15TH ST SHOULD
 BE EXIT-ONLY, WHILE CONVERTING THE PROPOSED WESTERN
 EXIT-ONLY DRIVEWAY TO A FULL-ACCESS ONE. MOREOVER, THE
 EASTERN DRIVEWAY NEEDS TO BE 125 FEET AWAY FROM THE
 INTERSECTION, PER FDOT CORNER CLEARANCE REQUIREMENT.
 PLEASE SHOWCASE SUCH DISTANCE IN THE TRANSPORTATION
 PLAN
 14) THE ALLEY MUST BE DESIGNATED ONE-WAY ONLY.
 CORRESPONDING SIGNAGE AND PAVEMENT MARKING INSTALLED
 AND SHOWN ON THE PLANS. PLEASE COORDINATE WITH PUBLIC
 WORKS PERTAINING THE DIRECTIONALITY AND NOTIFY TRAFFIC
 ENGINEERING ABOUT THE FINAL DECISION
 15) PROPOSED ON-STREET PARKING STALLS ON 14TH ST MAY
 NOT MEET CORNER CLEARANCE REQUIREMENT (125 FEET).
 PLEASE SHOWCASE SUCH DISTANCE IN THE TRANSPORTATION
 PLAN
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 02-02-2023 Cont ID  
Sent By kdefranc Date 02-02-2023 Time 14:07 Rev Time 0.00
Received By kdefranc Date 02-02-2023 Time 14:05 Sent To  
Notes
2023-02-02 14:06:272/2/23 ??? FAILED
  
  
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF
 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED
 AFTER THE FIRST RESUBMITTAL.
  
 REQUIRED MATERIALS MUST BE PROVIDED:
 F. PLEASE PROVIDE CONFIRMATION LETTERS FROM PUBLIC
 UTILITIES (AT&T TELECOMMUNICATION, FLORIDA PUBLIC
 UTILITIES, AND COMCAST CABLE COMMUNICATIONS) CONFIRMING
 THAT THE PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR
 EASEMENTS OR OTHERWISE INTERFERE WITH THE PROVISIONS OF
 THEIR SERVICES. [SATISFIED]
 G. PLEASE PROVIDE EVIDENCE OF THE UNIFIED CONTROL OF
 THE ENTIRE AREA. [SATISFIED]
 H. PLEASE PROVIDE THE AGREEMENTS, PROVISIONS OR
 COVENANTS WHICH GOVERN THE USE, MAINTENANCE AND
 CONTINUED PROTECTION OF THE PD AND ANY OF ITS COMMON
 AREAS OR FACILITIES. [SATISFIED SUBJECT TO THIS BE
 PROVIDED PRIOR TO BUILDING PERMIT APPLICATION]
 I. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW
 COMMENTS BELOW. [PARTIALLY SATISFIED]
 J. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT
 INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED
 MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL.
 [NOT SATISFIED]
 K. PLEASE PROVIDE COMPLETED PUBLIC NOTICE MAILER
 AFFIDAVITS WHEN MAILERS HAVE BEEN SENT OUT. [SATISFIED
 SUBJECT TO THESE BE PROVIDED PRIOR TO THE DEADLINES FOR
 THE PLANNING BOARD AND CITY COMMISSION MEETINGS]
 L. PLEASE PROVIDE COMPLETED SIGN POSTING AFFIDAVITS
 WHEN SIGNS HAVE BEEN PUT UP. [SATISFIED SUBJECT TO
 THESE BE PROVIDED PRIOR TO THE DEADLINES FOR THE
 PLANNING BOARD AND CITY COMMISSION MEETINGS]
  
 PREVIOUS REVIEW COMMENTS MUST BE ADDRESSED:
 1. IN ACCORDANCE WITH THE CITY???S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR) SUBSECTION
 94-207(B)(9)(A)(1), PLEASE IDENTIFY/INDICATE THE NAME
 OF THE DEVELOPER ON THE ???COVER??? SHEET NUMBER A-0
 AND/OR ???SITE PLAN??? SHEET NUMBER A-1. [SATISFIED]
 2. THE PROPOSAL DEMONSTRATED IS NOT IN COMPLIANCE WITH
 THE (VISIBILITY TRIANGLE AT INTERSECTIONS REQUIREMENT)
 ZLDR SUBSECTION 94-207(B)(6), THEREFORE, PLEASE REVISE
 THE DIFFERENT PLANS, ELEVATIONS, AND SECTION,
 ACCORDINGLY. [SATISFIED]
 3. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING
 AND PROPOSED EASEMENTS ON THE DIFFERENT PLANS.
 [PARTIALLY SATISFIED]
 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING
 AND PROPOSED FIRE HYDRANTS (OR OPERATIONAL EQUIVALENTS)
 WITHIN 250 FEET OF THE PROPOSED STRUCTURE(S) ON THE
 ???SITE PLAN??? SHEET NUMBER A-1. [SATISFIED]
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 ANY SPECIAL UTILITY STRUCTURES SUCH AS VALVES, METERS,
 BACKFLOW CONNECTIONS, PUMP STATIONS, TRANSFORMERS, AND
 ALL ABOVE GROUND APPURTENANCES ON THE ???SITE PLAN???
 SHEET NUMBER A-1. [SATISFIED]
 6. THE PROPOSED LOADING SPACES ARE NOT IN COMPLIANCE
 WITH THE MINIMUM LOADING SPACE DIMENSIONAL REQUIREMENTS
 OF THE ZLDR SUBSECTION 94-485(P), THEREFORE PLEASE
 REVISE THE DIFFERENT PLANS, ACCORDINGLY. [NOT SATISFIED
 - HOWEVER, WAIVER REQUEST ACKNOWLEDGED]
 7. PLEASE FURTHER EXPLAIN/CLARIFY/CONFIRM WHETHER THE
 PROPOSED LOADING SPACES ARE FOR THE PROPOSED
 SELF-STORAGE USE OR FOR ALL THE PROPOSED USES.
 [RESPONSE PROVIDED]
 8. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-485(Q),
 PLEASE IDENTIFY/INDICATE THE REQUIRED AND PROPOSED
 NUMBER OF BICYCLE PARKING SPACES IN THE ???PARKING???
 TABLE ON THE ???SITE PLAN??? SHEET NUMBER A-1.
 [SATISFIED]
 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING
 BIKE LANE (TO REMAIN) ALONG LA KIRKSEY/15TH STREET ON
 THE ???BOUNDARY SURVEY??? AND ???SITE PLAN??? SHEET
 NUMBER A-1. [SATISFIED]
 10. IN ACCORDANCE WITH THE ZLDR SUBSECTION
 94-207(B)(9)(A)(7), PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF PROPOSED
 MASS TRANSIT FACILITIES ON THE ???SITE PLAN??? SHEET
 NUMBER A-1. [RESPONSE PROVIDED]
 11. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE CURB
 CUTS/CONCRETE DRIVE ACCESSES REMOVED ALONG DIXIE
 HIGHWAY ON THE DIFFERENT PLANS, ACCORDINGLY, SIMILAR TO
 THE INFORMATION DISPLAYED ON THE ???SITE PLAN??? SHEET
 NUMBER C-02, ???DEMOLITION PLAN??? SHEET NUMBER C-03,
 AND ???PAVING, GRADING, AND DRAINAGE PLANS??? SHEET
 NUMBER C-04. [SATISFIED]
 12. PLEASE DEMONSTRATE HOW THE CITY???S SANITATION
 SERVICE TRUCKS WILL ACCESS/COLLECT THE TRASH FROM THE
 PROPOSED TRASH AREA TO THE SOUTH ON THE ???AUTOTURN
 EXHIBIT??? SHEET NUMBER C-07. [SATISFIED]
 13. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-443,
 PLEASE REVISE THE DIFFERENT PLANS AND ELEVATIONS,
 ACCORDINGLY, TO IDENTIFY/INDICATE/DEMONSTRATE THE
 REQUIRED PROTECTIVE SCREEN WALL ALONG THE WEST PROPERTY
 LINE ADJACENT TO THE RESIDENTIAL PROPERTY/RESIDENTIAL
 ZONING DISTRICT. [SATISFIED]
 14. IT HAS BEEN IDENTIFIED THAT THERE ARE
 INCONSISTENCIES BETWEEN THE PLANS AND ELEVATIONS
 REGARDING THE PROPOSED FIVE-FOOT-HIGH SECURITY/ALUMINUM
 FENCE, THEREFORE PLEASE REVISE, ACCORDINGLY.
 [SATISFIED]
 15. PLEASE PROVIDE AN
 ILLUMINATION/LIGHTING/PHOTOMETRICS PLAN DEMONSTRATING
 COMPLIANCE WITH THE ZLDR SUBSECTION 94-207(D)(8).
 [SATISFIED]
 16. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-409,
 PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE PROPOSED
 BUILDING FA??ADE SIZE, PERCENT SIGNAGE PERMITTED, AND
 PERMITTED SIGN SIZE FOR THE PROPOSED WALL MOUNTED SIGNS
 ON THE ???COLOR ELEVATIONS??? SHEET NUMBERS A-3 TO A-4.
 [PARTIALLY SATISFIED]
 17. THE PROPOSED ???WEST ELEVATION??? WALL MOUNTED SIGN
 IS NOT IN COMPLIANCE WITH THE ZLDR SUBSECTION
 94-402(B)(2)(7), THEREFORE PLEASE REVISE THE ???COLOR
 ELEVATION??? SHEET NUMBER A-4, ACCORDINGLY. [SATISFIED]
 18. PLEASE PROVIDE THE STANDARD CITY DETAILS OF
 VEHICLE/BICYCLE PARKING (STANDARD, COMPACT, ADA),
 LOADING, ADA RAMPS, DRIVEWAYS, DUMPSTERS AND SIGNS.
 [SATISFIED]
 19. PLEASE UPDATE THE ???SITE DATA??? ON THE ???SITE
 PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE
 CORRESPONDING DATA FOR THE ???ALLOWED??? INFORMATION
 WITHIN THE EXISTING MF14 AND GC ZONING DISTRICTS.
 [PARTIALLY SATISFIED]
 20. PLEASE UPDATE THE ???SITE DATA??? ON THE ???SITE
 PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE
 MAXIMUM AND PROPOSED LOT COVERAGE BY BUILDINGS AND
 IMPERMEABLE SURFACE ACCORDING TO THE ZLDR SECTIONS
 94-241 AND 94-243. [SATISFIED]
 21. PLEASE CORRECT THE ???SITE DATA??? ON THE ???SITE
 PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE
 MAXIMUM BUILDING HEIGHTS (???ALLOWED???) INFORMATION
 ACCORDING TO THE ZLDR SUBSECTIONS 94-241 AND 94-243 FOR
 THE EXISTING MF14 AND GC ZONING DISTRICTS AND ADD THE
 PROPOSED HEIGHT ???TO THE TOP OF THE PARAPET???
 INFORMATION TO REFLECT THE SAME INFORMATION
 DEMONSTRATED IN THE ELEVATIONS. [PARTIALLY SATISFIED]
 22. PLEASE CORRECT THE ???SITE DATA??? ON THE ???SITE
 PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE
 PROPOSED ???FRONT (EAST SIDE)??? SETBACK TO REFLECT THE
 SAME INFORMATION DEMONSTRATED IN THE GRAPHIC/PLAN.
 [SATISFIED]
 23. PLEASE CORRECT THE ???PARKING??? TABLE ON THE
 ???SITE PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE
 THE PROPOSED NUMBER OF PARKING SPACES IN WHOLE NUMBERS
 ACCORDING TO THE ZLDR SUBSECTION 94-485(H); TO
 IDENTIFY/INDICATE CORRECT INFORMATION FOR THE MINIMUM
 NUMBER OF REQUIRED ???STORAGE OFFICE??? PARKING SPACES
 ACCORDING TO THE ZLDR SECTION 94-486; TO
 IDENTIFY/INDICATE THE CORRECT INFORMATION FOR THE TOTAL
 MINIMUM NUMBER OF REQUIRED PARKING SPACES; AND TO
 IDENTIFY/INDICATE THE MINIMUM REQUIRED NUMBER OF
 ???H.C. (INCLUSIVE)??? PARKING SPACES ACCORDING TO THE
 ZLDR SUBSECTION 94-485(O). [PARTIALLY SATISFIED]
 24. PLEASE CORRECT THE ???LOADING??? TABLE ON THE
 ???SITE PLAN??? SHEET NUMBER A-1 TO INDICATE THE
 MINIMUM LOADING SPACE DIMENSIONAL REQUIREMENTS
 ACCORDING TO THE ZLDR SUBSECTION 94-485(P). [SATISFIED]
 25. IT HAS BEEN IDENTIFIED THAT THERE ARE
 INCONSISTENCIES BETWEEN THE ???SITEPLAN??? SHEET NUMBER
 A-1, ???SITE PLAN??? SHEET NUMBER C-02, AND
 ???LANDSCAPE PLAN??? SHEET NUMBER L-2.0 REGARDING THE
 SITE DATA INFORMATION, THEREFORE PLEASE REVISE,
 ACCORDINGLY. [PARTIALLY SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS MUST BE ADDRESSED:
 26. IN REFERENCE TO REQUIRED MATERIALS COMMENT F.,
 PLEASE PROVIDE THE CONFIRMATION LETTER FROM FLORIDA
 PUBLIC UTILITIES. [SATISFIED]
 27. IN REFERENCE TO PREVIOUS REVIEW COMMENT 3., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT PROPOSED
 EASEMENTS ON SHEET NUMBERS A-1, C-02, AND L-2.0. [NOT
 SATISFIED]
 28. IN REFERENCE TO PREVIOUS REVIEW COMMENT 5., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE ALL ABOVE GROUND
 APPURTENANCES ON SHEET NUMBER A-1. [SATISFIED]
 29. IN REFERENCE TO PREVIOUS REVIEW COMMENT 11., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE THE CURB CUTS/CONCRETE
 DRIVE ACCESSES REMOVED ALONG DIXIE HIGHWAY ON SHEET
 NUMBER A-1. [SATISFIED]
 30. IN REFERENCE TO PREVIOUS REVIEW COMMENT 15., PLEASE
 PROVIDE EXPLANATION/CLARIFICATION ON THE DIFFERENCE
 BETWEEN THE HORIZONTAL PL AND THE VERTICAL PL PROVIDED.
 THE VERTICAL PL IDENTIFIES/INDICATES/DEMONSTRATES
 INFORMATION THAT IS NOT IN COMPLIANCE WITH THE ZLDR
 SUBSECTION 94-207(D)(8), PRIMARILY ALONG THE SOUTH
 PROPERTY LINE, THEREFORE, REVISE ACCORDINGLY.
 [SATISFIED]
 31. IN REFERENCE TO PREVIOUS REVIEW COMMENT 16., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE THE DIMENSIONS OF THE
 PROPOSED SIGNAGE ON THE EAST AND NORTH ELEVATIONS AND
 CORRECT THE ???MAX SIGNAGE AREAS??? ON THE EAST AND
 NORTH ELEVATIONS. [PARTIALLY SATISFIED]
 32. IN REFERENCE TO PREVIOUS REVIEW COMMENT 19., PLEASE
 IDENTIFY/INDICATE THE CORRESPONDING DATA FOR THE
 ???ALLOWED??? INFORMATION WITHIN THE EXISTING MF14
 ZONING DISTRICT ON SHEET NUMBER A-1. [PARTIALLY
 SATISFIED]
 33. IN REFERENCE TO PREVIOUS REVIEW COMMENT 20., PLEASE
 IDENTIFY/INDICATE THE MAXIMUM AND PROPOSED LOT COVERAGE
 BY IMPERMEABLE SURFACE ON SHEET NUMBER A-1. [SATISFIED]
 34. IN REFERENCE TO PREVIOUS REVIEW COMMENT 21., PLEASE
 IDENTIFY/INDICATE THE MAXIMUM BUILDING HEIGHT
 ???ALLOWED??? INFORMATION FOR THE EXISTING MF14 ZONING
 DISTRICT AND ADD THE PROPOSED HEIGHT ???TO THE TOP OF
 THE PARAPET??? INFORMATION, TO REFLECT THE SAME
 INFORMATION DEMONSTRATED IN THE ELEVATIONS, ON SHEET
 NUMBER A-1. [PARTIALLY SATISFIED]
 35. IN REFERENCE TO PREVIOUS REVIEW COMMENT 23., PLEASE
 CORRECT THE ???PARKING??? TABLE ON SHEET NUMBER A-1 TO
 IDENTIFY/INDICATE CORRECT INFORMATION FOR THE MINIMUM
 NUMBER OF REQUIRED ???STORAGE OFFICE??? PARKING SPACES
 ACCORDING TO THE ZLDR SECTION 94-486 AND TO
 IDENTIFY/INDICATE THE CORRECT INFORMATION FOR THE TOTAL
 MINIMUM NUMBER OF REQUIRED PARKING SPACES. [PARTIALLY
 SATISFIED]
 36. IN REFERENCE TO PREVIOUS REVIEW COMMENT 25., PLEASE
 IDENTIFY/INDICATE THE IMPERVIOUS AND PERVIOUS
 INFORMATION ON SHEET NUMBER A-1, AS REFLECTED ON SHEET
 NUMBER C-02. [PARTIALLY SATISFIED]
 37. IT HAS BEEN CONFIRMED BY THE CITY???S SENIOR
 LANDSCAPE PLANNER, RAY CARANCI, THAT THE MINIMUM
 LANDSCAPE AREA REQUIREMENT WITHIN THE GC PDD IS 15%.
 THE LANDSCAPE AREA PROPOSED EXCEEDS THAT MINIMUM
 REQUIREMENT. THEREFORE, THE WAIVER REQUEST FROM THE
 MINIMUM LANDSCAPE AREA REQUIREMENT IS NOT NEEDED.
  
 CONDITION OF APPROVAL: (IN ADDITION TO THE OTHER CITY
 STAFF REVIEWERS??? CONDITIONS OF APPROVAL)
 1. PRIOR TO STAFF SCHEDULING THE SUBJECT CASE FOR CITY
 COMMISSION, REVISED PLANS
 IDENTIFYING/INDICATING/DEMONSTRATING CONSISTENT
 INFORMATION AND CORRECTED SITE DATA INFORMATION SHALL
 BE PROVIDED.
  
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 2 Status F Date 01-10-2023 Cont ID  
Sent By kdefranc Date 01-10-2023 Time 10:02 Rev Time 0.00
Received By kdefranc Date 01-10-2023 Time 10:01 Sent To  
Notes
2023-01-10 10:02:041/10/23 ??? FAILED
  
  
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF
 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED
 AFTER THE FIRST RESUBMITTAL.
  
 REQUIRED MATERIALS MUST BE PROVIDED:
 F. PLEASE PROVIDE CONFIRMATION LETTERS FROM PUBLIC
 UTILITIES (AT&T TELECOMMUNICATION, FLORIDA PUBLIC
 UTILITIES, AND COMCAST CABLE COMMUNICATIONS) CONFIRMING
 THAT THE PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR
 EASEMENTS OR OTHERWISE INTERFERE WITH THE PROVISIONS OF
 THEIR SERVICES. [PARTIALLY SATISFIED]
 G. PLEASE PROVIDE EVIDENCE OF THE UNIFIED CONTROL OF
 THE ENTIRE AREA. [SATISFIED]
 H. PLEASE PROVIDE THE AGREEMENTS, PROVISIONS OR
 COVENANTS WHICH GOVERN THE USE, MAINTENANCE AND
 CONTINUED PROTECTION OF THE PD AND ANY OF ITS COMMON
 AREAS OR FACILITIES. [SATISFIED SUBJECT TO THIS BE
 PROVIDED PRIOR TO BUILDING PERMIT APPLICATION]
 I. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW
 COMMENTS BELOW. [PARTIALLY SATISFIED]
 J. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT
 INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED
 MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL.
 [NOT SATISFIED]
 K. PLEASE PROVIDE COMPLETED PUBLIC NOTICE MAILER
 AFFIDAVITS WHEN MAILERS HAVE BEEN SENT OUT. [SATISFIED
 SUBJECT TO THESE BE PROVIDED PRIOR TO THE DEADLINES FOR
 THE PLANNING BOARD AND CITY COMMISSION MEETINGS]
 L. PLEASE PROVIDE COMPLETED SIGN POSTING AFFIDAVITS
 WHEN SIGNS HAVE BEEN PUT UP. [SATISFIED SUBJECT TO
 THESE BE PROVIDED PRIOR TO THE DEADLINES FOR THE
 PLANNING BOARD AND CITY COMMISSION MEETINGS]
  
 PREVIOUS REVIEW COMMENTS MUST BE ADDRESSED:
 1. IN ACCORDANCE WITH THE CITY???S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR) SUBSECTION
 94-207(B)(9)(A)(1), PLEASE IDENTIFY/INDICATE THE NAME
 OF THE DEVELOPER ON THE ???COVER??? SHEET NUMBER A-0
 AND/OR ???SITE PLAN??? SHEET NUMBER A-1. [SATISFIED]
 2. THE PROPOSAL DEMONSTRATED IS NOT IN COMPLIANCE WITH
 THE (VISIBILITY TRIANGLE AT INTERSECTIONS REQUIREMENT)
 ZLDR SUBSECTION 94-207(B)(6), THEREFORE, PLEASE REVISE
 THE DIFFERENT PLANS, ELEVATIONS, AND SECTION,
 ACCORDINGLY. [SATISFIED]
 3. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING
 AND PROPOSED EASEMENTS ON THE DIFFERENT PLANS.
 [PARTIALLY SATISFIED]
 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING
 AND PROPOSED FIRE HYDRANTS (OR OPERATIONAL EQUIVALENTS)
 WITHIN 250 FEET OF THE PROPOSED STRUCTURE(S) ON THE
 ???SITE PLAN??? SHEET NUMBER A-1. [SATISFIED]
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 ANY SPECIAL UTILITY STRUCTURES SUCH AS VALVES, METERS,
 BACKFLOW CONNECTIONS, PUMP STATIONS, TRANSFORMERS, AND
 ALL ABOVE GROUND APPURTENANCES ON THE ???SITE PLAN???
 SHEET NUMBER A-1. [PARTIALLY SATISFIED]
 6. THE PROPOSED LOADING SPACES ARE NOT IN COMPLIANCE
 WITH THE MINIMUM LOADING SPACE DIMENSIONAL REQUIREMENTS
 OF THE ZLDR SUBSECTION 94-485(P), THEREFORE PLEASE
 REVISE THE DIFFERENT PLANS, ACCORDINGLY. [NOT SATISFIED
 - HOWEVER, WAIVER REQUEST ACKNOWLEDGED]
 7. PLEASE FURTHER EXPLAIN/CLARIFY/CONFIRM WHETHER THE
 PROPOSED LOADING SPACES ARE FOR THE PROPOSED
 SELF-STORAGE USE OR FOR ALL THE PROPOSED USES.
 [RESPONSE PROVIDED]
 8. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-485(Q),
 PLEASE IDENTIFY/INDICATE THE REQUIRED AND PROPOSED
 NUMBER OF BICYCLE PARKING SPACES IN THE ???PARKING???
 TABLE ON THE ???SITE PLAN??? SHEET NUMBER A-1. [NOT
 SATISFIED]
 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING
 BIKE LANE (TO REMAIN) ALONG LA KIRKSEY/15TH STREET ON
 THE ???BOUNDARY SURVEY??? AND ???SITE PLAN??? SHEET
 NUMBER A-1. [SATISFIED]
 10. IN ACCORDANCE WITH THE ZLDR SUBSECTION
 94-207(B)(9)(A)(7), PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF PROPOSED
 MASS TRANSIT FACILITIES ON THE ???SITE PLAN??? SHEET
 NUMBER A-1. [RESPONSE PROVIDED]
 11. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE CURB
 CUTS/CONCRETE DRIVE ACCESSES REMOVED ALONG DIXIE
 HIGHWAY ON THE DIFFERENT PLANS, ACCORDINGLY, SIMILAR TO
 THE INFORMATION DISPLAYED ON THE ???SITE PLAN??? SHEET
 NUMBER C-02, ???DEMOLITION PLAN??? SHEET NUMBER C-03,
 AND ???PAVING, GRADING, AND DRAINAGE PLANS??? SHEET
 NUMBER C-04. [NOT SATISFIED]
 12. PLEASE DEMONSTRATE HOW THE CITY???S SANITATION
 SERVICE TRUCKS WILL ACCESS/COLLECT THE TRASH FROM THE
 PROPOSED TRASH AREA TO THE SOUTH ON THE ???AUTOTURN
 EXHIBIT??? SHEET NUMBER C-07. [SATISFIED]
 13. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-443,
 PLEASE REVISE THE DIFFERENT PLANS AND ELEVATIONS,
 ACCORDINGLY, TO IDENTIFY/INDICATE/DEMONSTRATE THE
 REQUIRED PROTECTIVE SCREEN WALL ALONG THE WEST PROPERTY
 LINE ADJACENT TO THE RESIDENTIAL PROPERTY/RESIDENTIAL
 ZONING DISTRICT. [SATISFIED]
 14. IT HAS BEEN IDENTIFIED THAT THERE ARE
 INCONSISTENCIES BETWEEN THE PLANS AND ELEVATIONS
 REGARDING THE PROPOSED FIVE-FOOT-HIGH SECURITY/ALUMINUM
 FENCE, THEREFORE PLEASE REVISE, ACCORDINGLY.
 [SATISFIED]
 15. PLEASE PROVIDE AN
 ILLUMINATION/LIGHTING/PHOTOMETRICS PLAN DEMONSTRATING
 COMPLIANCE WITH THE ZLDR SUBSECTION 94-207(D)(8).
 [PARTIALLY SATISFIED]
 16. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-409,
 PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE PROPOSED
 BUILDING FA??ADE SIZE, PERCENT SIGNAGE PERMITTED, AND
 PERMITTED SIGN SIZE FOR THE PROPOSED WALL MOUNTED SIGNS
 ON THE ???COLOR ELEVATIONS??? SHEET NUMBERS A-3 TO A-4.
 [PARTIALLY SATISFIED]
 17. THE PROPOSED ???WEST ELEVATION??? WALL MOUNTED SIGN
 IS NOT IN COMPLIANCE WITH THE ZLDR SUBSECTION
 94-402(B)(2)(7), THEREFORE PLEASE REVISE THE ???COLOR
 ELEVATION??? SHEET NUMBER A-4, ACCORDINGLY. [SATISFIED]
 18. PLEASE PROVIDE THE STANDARD CITY DETAILS OF
 VEHICLE/BICYCLE PARKING (STANDARD, COMPACT, ADA),
 LOADING, ADA RAMPS, DRIVEWAYS, DUMPSTERS AND SIGNS.
 [SATISFIED]
 19. PLEASE UPDATE THE ???SITE DATA??? ON THE ???SITE
 PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE
 CORRESPONDING DATA FOR THE ???ALLOWED??? INFORMATION
 WITHIN THE EXISTING MF14 AND GC ZONING DISTRICTS.
 [PARTIALLY SATISFIED]
 20. PLEASE UPDATE THE ???SITE DATA??? ON THE ???SITE
 PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE
 MAXIMUM AND PROPOSED LOT COVERAGE BY BUILDINGS AND
 IMPERMEABLE SURFACE ACCORDING TO THE ZLDR SECTIONS
 94-241 AND 94-243. [PARTIALLY SATISFIED]
 21. PLEASE CORRECT THE ???SITE DATA??? ON THE ???SITE
 PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE
 MAXIMUM BUILDING HEIGHTS (???ALLOWED???) INFORMATION
 ACCORDING TO THE ZLDR SUBSECTIONS 94-241 AND 94-243 FOR
 THE EXISTING MF14 AND GC ZONING DISTRICTS AND ADD THE
 PROPOSED HEIGHT ???TO THE TOP OF THE PARAPET???
 INFORMATION TO REFLECT THE SAME INFORMATION
 DEMONSTRATED IN THE ELEVATIONS. [PARTIALLY SATISFIED]
 22. PLEASE CORRECT THE ???SITE DATA??? ON THE ???SITE
 PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE
 PROPOSED ???FRONT (EAST SIDE)??? SETBACK TO REFLECT THE
 SAME INFORMATION DEMONSTRATED IN THE GRAPHIC/PLAN.
 [SATISFIED]
 23. PLEASE CORRECT THE ???PARKING??? TABLE ON THE
 ???SITE PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE
 THE PROPOSED NUMBER OF PARKING SPACES IN WHOLE NUMBERS
 ACCORDING TO THE ZLDR SUBSECTION 94-485(H); TO
 IDENTIFY/INDICATE CORRECT INFORMATION FOR THE MINIMUM
 NUMBER OF REQUIRED ???STORAGE OFFICE??? PARKING SPACES
 ACCORDING TO THE ZLDR SECTION 94-486; TO
 IDENTIFY/INDICATE THE CORRECT INFORMATION FOR THE TOTAL
 MINIMUM NUMBER OF REQUIRED PARKING SPACES; AND TO
 IDENTIFY/INDICATE THE MINIMUM REQUIRED NUMBER OF
 ???H.C. (INCLUSIVE)??? PARKING SPACES ACCORDING TO THE
 ZLDR SUBSECTION 94-485(O). [PARTIALLY SATISFIED]
 24. PLEASE CORRECT THE ???LOADING??? TABLE ON THE
 ???SITE PLAN??? SHEET NUMBER A-1 TO INDICATE THE
 MINIMUM LOADING SPACE DIMENSIONAL REQUIREMENTS
 ACCORDING TO THE ZLDR SUBSECTION 94-485(P). [SATISFIED]
 25. IT HAS BEEN IDENTIFIED THAT THERE ARE
 INCONSISTENCIES BETWEEN THE ???SITEPLAN??? SHEET NUMBER
 A-1, ???SITE PLAN??? SHEET NUMBER C-02, AND
 ???LANDSCAPE PLAN??? SHEET NUMBER L-2.0 REGARDING THE
 SITE DATA INFORMATION, THEREFORE PLEASE REVISE,
 ACCORDINGLY. [PARTIALLY SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS MUST BE ADDRESSED:
 26. IN REFERENCE TO REQUIRED MATERIALS COMMENT F.,
 PLEASE PROVIDE THE CONFIRMATION LETTER FROM FLORIDA
 PUBLIC UTILITIES.
 27. IN REFERENCE TO PREVIOUS REVIEW COMMENT 3., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT PROPOSED
 EASEMENTS ON SHEET NUMBERS A-1, C-02, AND L-2.0.
 28. IN REFERENCE TO PREVIOUS REVIEW COMMENT 5., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE ALL ABOVE GROUND
 APPURTENANCES ON SHEET NUMBER A-1.
 29. IN REFERENCE TO PREVIOUS REVIEW COMMENT 11., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE THE CURB CUTS/CONCRETE
 DRIVE ACCESSES REMOVED ALONG DIXIE HIGHWAY ON SHEET
 NUMBER A-1.
 30. IN REFERENCE TO PREVIOUS REVIEW COMMENT 15., PLEASE
 PROVIDE EXPLANATION/CLARIFICATION ON THE DIFFERENCE
 BETWEEN THE HORIZONTAL PL AND THE VERTICAL PL PROVIDED.
 THE VERTICAL PL IDENTIFIES/INDICATES/DEMONSTRATES
 INFORMATION THAT IS NOT IN COMPLIANCE WITH THE ZLDR
 SUBSECTION 94-207(D)(8), PRIMARILY ALONG THE SOUTH
 PROPERTY LINE, THEREFORE, REVISE ACCORDINGLY.
 31. IN REFERENCE TO PREVIOUS REVIEW COMMENT 16., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE THE DIMENSIONS OF THE
 PROPOSED SIGNAGE ON THE EAST AND NORTH ELEVATIONS AND
 CORRECT THE ???MAX SIGNAGE AREAS??? ON THE EAST AND
 NORTH ELEVATIONS.
 32. IN REFERENCE TO PREVIOUS REVIEW COMMENT 19., PLEASE
 IDENTIFY/INDICATE THE CORRESPONDING DATA FOR THE
 ???ALLOWED??? INFORMATION WITHIN THE EXISTING MF14
 ZONING DISTRICT ON SHEET NUMBER A-1.
 33. IN REFERENCE TO PREVIOUS REVIEW COMMENT 20., PLEASE
 IDENTIFY/INDICATE THE MAXIMUM AND PROPOSED LOT COVERAGE
 BY IMPERMEABLE SURFACE ON SHEET NUMBER A-1.
 34. IN REFERENCE TO PREVIOUS REVIEW COMMENT 21., PLEASE
 IDENTIFY/INDICATE THE MAXIMUM BUILDING HEIGHT
 ???ALLOWED??? INFORMATION FOR THE EXISTING MF14 ZONING
 DISTRICT AND ADD THE PROPOSED HEIGHT ???TO THE TOP OF
 THE PARAPET??? INFORMATION, TO REFLECT THE SAME
 INFORMATION DEMONSTRATED IN THE ELEVATIONS, ON SHEET
 NUMBER A-1.
 35. IN REFERENCE TO PREVIOUS REVIEW COMMENT 23., PLEASE
 CORRECT THE ???PARKING??? TABLE ON SHEET NUMBER A-1 TO
 IDENTIFY/INDICATE CORRECT INFORMATION FOR THE MINIMUM
 NUMBER OF REQUIRED ???STORAGE OFFICE??? PARKING SPACES
 ACCORDING TO THE ZLDR SECTION 94-486 AND TO
 IDENTIFY/INDICATE THE CORRECT INFORMATION FOR THE TOTAL
 MINIMUM NUMBER OF REQUIRED PARKING SPACES.
 36. IN REFERENCE TO PREVIOUS REVIEW COMMENT 25., PLEASE
 IDENTIFY/INDICATE THE IMPERVIOUS AND PERVIOUS
 INFORMATION ON SHEET NUMBER A-1, AS REFLECTED ON SHEET
 NUMBER C-02.
  
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 1 Status F Date 09-06-2022 Cont ID  
Sent By kdefranc Date 09-06-2022 Time 15:29 Rev Time 0.00
Received By kdefranc Date 09-06-2022 Time 15:28 Sent To  
Notes
2022-09-06 15:29:299/6/22 ? FAILED
  
  
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF
 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED
 AFTER THE FIRST RESUBMITTAL.
  
 REQUIRED MATERIALS MUST BE PROVIDED:
 F. PLEASE PROVIDE CONFIRMATION LETTERS FROM PUBLIC
 UTILITIES (AT&T TELECOMMUNICATION, FLORIDA PUBLIC
 UTILITIES, AND COMCAST CABLE COMMUNICATIONS) CONFIRMING
 THAT THE PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR
 EASEMENTS OR OTHERWISE INTERFERE WITH THE PROVISIONS OF
 THEIR SERVICES.
 G. PLEASE PROVIDE EVIDENCE OF THE UNIFIED CONTROL OF
 THE ENTIRE AREA.
 H. PLEASE PROVIDE THE AGREEMENTS, PROVISIONS OR
 COVENANTS WHICH GOVERN THE USE, MAINTENANCE AND
 CONTINUED PROTECTION OF THE PD AND ANY OF ITS COMMON
 AREAS OR FACILITIES.
 I. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW
 COMMENTS BELOW.
 J. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT
 INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED
 MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL.
 K. PLEASE PROVIDE COMPLETED PUBLIC NOTICE MAILER
 AFFIDAVITS WHEN MAILERS HAVE BEEN SENT OUT.
 L. PLEASE PROVIDE COMPLETED SIGN POSTING AFFIDAVITS
 WHEN SIGNS HAVE BEEN PUT UP.
  
 REVIEW COMMENTS MUST BE ADDRESSED:
 1. IN ACCORDANCE WITH THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR) SUBSECTION
 94-207(B)(9)(A)(1), PLEASE IDENTIFY/INDICATE THE NAME
 OF THE DEVELOPER ON THE ?COVER? SHEET NUMBER A-0 AND/OR
 ?SITE PLAN? SHEET NUMBER A-1.
 2. THE PROPOSAL DEMONSTRATED IS NOT IN COMPLIANCE WITH
 THE (VISIBILITY TRIANGLE AT INTERSECTIONS REQUIREMENT)
 ZLDR SUBSECTION 94-207(B)(6), THEREFORE, PLEASE REVISE
 THE DIFFERENT PLANS, ELEVATIONS, AND SECTION,
 ACCORDINGLY.
 3. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING
 AND PROPOSED EASEMENTS ON THE DIFFERENT PLANS.
 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING
 AND PROPOSED FIRE HYDRANTS (OR OPERATIONAL EQUIVALENTS)
 WITHIN 250 FEET OF THE PROPOSED STRUCTURE(S) ON THE
 ?SITE PLAN? SHEET NUMBER A-1.
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 ANY SPECIAL UTILITY STRUCTURES SUCH AS VALVES, METERS,
 BACKFLOW CONNECTIONS, PUMP STATIONS, TRANSFORMERS, AND
 ALL ABOVE GROUND APPURTENANCES ON THE ?SITE PLAN? SHEET
 NUMBER A-1.
 6. THE PROPOSED LOADING SPACES ARE NOT IN COMPLIANCE
 WITH THE MINIMUM LOADING SPACE DIMENSIONAL REQUIREMENTS
 OF THE ZLDR SUBSECTION 94-485(P), THEREFORE PLEASE
 REVISE THE DIFFERENT PLANS, ACCORDINGLY.
 7. PLEASE FURTHER EXPLAIN/CLARIFY/CONFIRM WHETHER THE
 PROPOSED LOADING SPACES ARE FOR THE PROPOSED
 SELF-STORAGE USE OR FOR ALL THE PROPOSED USES.
 8. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-485(Q),
 PLEASE IDENTIFY/INDICATE THE REQUIRED AND PROPOSED
 NUMBER OF BICYCLE PARKING SPACES IN THE ?PARKING? TABLE
 ON THE ?SITE PLAN? SHEET NUMBER A-1.
 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING
 BIKE LANE (TO REMAIN) ALONG LA KIRKSEY/15TH STREET ON
 THE ?BOUNDARY SURVEY? AND ?SITE PLAN? SHEET NUMBER A-1.
 10. IN ACCORDANCE WITH THE ZLDR SUBSECTION
 94-207(B)(9)(A)(7), PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF PROPOSED
 MASS TRANSIT FACILITIES ON THE ?SITE PLAN? SHEET NUMBER
 A-1.
 11. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE CURB
 CUTS/CONCRETE DRIVE ACCESSES REMOVED ALONG DIXIE
 HIGHWAY ON THE DIFFERENT PLANS, ACCORDINGLY, SIMILAR TO
 THE INFORMATION DISPLAYED ON THE ?SITE PLAN? SHEET
 NUMBER C-02, ?DEMOLITION PLAN? SHEET NUMBER C-03, AND
 ?PAVING, GRADING, AND DRAINAGE PLANS? SHEET NUMBER
 C-04.
 12. PLEASE DEMONSTRATE HOW THE CITY?S SANITATION
 SERVICE TRUCKS WILL ACCESS/COLLECT THE TRASH FROM THE
 PROPOSED TRASH AREA TO THE SOUTH ON THE ?AUTOTURN
 EXHIBIT? SHEET NUMBER C-07.
 13. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-443,
 PLEASE REVISE THE DIFFERENT PLANS AND ELEVATIONS,
 ACCORDINGLY, TO IDENTIFY/INDICATE/DEMONSTRATE THE
 REQUIRED PROTECTIVE SCREEN WALL ALONG THE WEST PROPERTY
 LINE ADJACENT TO THE RESIDENTIAL PROPERTY/RESIDENTIAL
 ZONING DISTRICT.
 14. IT HAS BEEN IDENTIFIED THAT THERE ARE
 INCONSISTENCIES BETWEEN THE PLANS AND ELEVATIONS
 REGARDING THE PROPOSED FIVE-FOOT-HIGH SECURITY/ALUMINUM
 FENCE, THEREFORE PLEASE REVISE, ACCORDINGLY.
 15. PLEASE PROVIDE AN
 ILLUMINATION/LIGHTING/PHOTOMETRICS PLAN DEMONSTRATING
 COMPLIANCE WITH THE ZLDR SUBSECTION 94-207(D)(8).
 16. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-409,
 PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE PROPOSED
 BUILDING FA?ADE SIZE, PERCENT SIGNAGE PERMITTED, AND
 PERMITTED SIGN SIZE FOR THE PROPOSED WALL MOUNTED SIGNS
 ON THE ?COLOR ELEVATIONS? SHEET NUMBERS A-3 TO A-4.
 17. THE PROPOSED ?WEST ELEVATION? WALL MOUNTED SIGN IS
 NOT IN COMPLIANCE WITH THE ZLDR SUBSECTION
 94-402(B)(2)(7), THEREFORE PLEASE REVISE THE ?COLOR
 ELEVATION? SHEET NUMBER A-4, ACCORDINGLY.
 18. PLEASE PROVIDE THE STANDARD CITY DETAILS OF
 VEHICLE/BICYCLE PARKING (STANDARD, COMPACT, ADA),
 LOADING, ADA RAMPS, DRIVEWAYS, DUMPSTERS AND SIGNS.
 19. PLEASE UPDATE THE ?SITE DATA? ON THE ?SITE PLAN?
 SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE CORRESPONDING
 DATA FOR THE ?ALLOWED? INFORMATION WITHIN THE EXISTING
 MF14 AND GC ZONING DISTRICTS.
 20. PLEASE UPDATE THE ?SITE DATA? ON THE ?SITE PLAN?
 SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE MAXIMUM AND
 PROPOSED LOT COVERAGE BY BUILDINGS AND IMPERMEABLE
 SURFACE ACCORDING TO THE ZLDR SECTIONS 94-241 AND
 94-243.
 21. PLEASE CORRECT THE ?SITE DATA? ON THE ?SITE PLAN?
 SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE MAXIMUM
 BUILDING HEIGHTS (?ALLOWED?) INFORMATION ACCORDING TO
 THE ZLDR SUBSECTIONS 94-241 AND 94-243 FOR THE EXISTING
 MF14 AND GC ZONING DISTRICTS AND ADD THE PROPOSED
 HEIGHT ?TO THE TOP OF THE PARAPET? INFORMATION TO
 REFLECT THE SAME INFORMATION DEMONSTRATED IN THE
 ELEVATIONS.
 22. PLEASE CORRECT THE ?SITE DATA? ON THE ?SITE PLAN?
 SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE PROPOSED
 ?FRONT (EAST SIDE)? SETBACK TO REFLECT THE SAME
 INFORMATION DEMONSTRATED IN THE GRAPHIC/PLAN.
 23. PLEASE CORRECT THE ?PARKING? TABLE ON THE ?SITE
 PLAN? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE
 PROPOSED NUMBER OF PARKING SPACES IN WHOLE NUMBERS
 ACCORDING TO THE ZLDR SUBSECTION 94-485(H); TO
 IDENTIFY/INDICATE CORRECT INFORMATION FOR THE MINIMUM
 NUMBER OF REQUIRED ?STORAGE OFFICE? PARKING SPACES
 ACCORDING TO THE ZLDR SECTION 94-486; TO
 IDENTIFY/INDICATE THE CORRECT INFORMATION FOR THE TOTAL
 MINIMUM NUMBER OF REQUIRED PARKING SPACES; AND TO
 IDENTIFY/INDICATE THE MINIMUM REQUIRED NUMBER OF ?H.C.
 (INCLUSIVE)? PARKING SPACES ACCORDING TO THE ZLDR
 SUBSECTION 94-485(O).
 24. PLEASE CORRECT THE ?LOADING? TABLE ON THE ?SITE
 PLAN? SHEET NUMBER A-1 TO INDICATE THE MINIMUM LOADING
 SPACE DIMENSIONAL REQUIREMENTS ACCORDING TO THE ZLDR
 SUBSECTION 94-485(P).
 25. IT HAS BEEN IDENTIFIED THAT THERE ARE
 INCONSISTENCIES BETWEEN THE ?SITEPLAN? SHEET NUMBER
 A-1, ?SITE PLAN? SHEET NUMBER C-02, AND ?LANDSCAPE
 PLAN? SHEET NUMBER L-2.0 REGARDING THE SITE DATA
 INFORMATION, THEREFORE PLEASE REVISE, ACCORDINGLY.
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  