 |
Plan Review Details - Project Z22080028
Plan Review Stops For Project Z22080028 |
Review Stop |
AIPP |
ART IN PUBLIC PLACES |
Rev No |
1 |
Status |
P |
Date |
08-25-2022 |
|
|
Cont ID |
|
Sent By |
scwelter |
Date |
08-25-2022 |
Time |
16:18 |
Rev Time |
0.00 |
Received By |
swelter |
Date |
02-02-2023 |
Time |
13:55 |
Sent To |
|
|
Notes |
2023-02-02 13:55:12 | | | SITE PLAN APPROVAL DOES NOT INCLUDE APPROVAL OF ARTIST | | OR PUBLIC ART CONCEPT. | | ARTIST MUST BE IDENTIFIED AND APPROVED BEFORE BUILDING | | PERMIT SUBMITTAL. | | | 2022-08-25 16:21:35 | PUBLIC ART IDENTIFIED ON SITE PLAN. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
09-07-2022 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
09-07-2022 |
Time |
14:30 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
09-07-2022 |
Time |
14:30 |
Sent To |
|
|
Notes |
2022-09-07 14:34:13 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | COMMENTS: | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | OR BY EMAIL: [email protected] | | | | 3. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY | | LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER | | APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE | | PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE | | WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF | | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION | | DISTANCE. | | | | 4. VAN ACCESSIBLE PARKING SPACES. THE PLANS DO NOT SHOW | | A VAN ACCESSIBLE PARKING SPACE. PER SECTION 208.2.4 OF | | FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX REQUIRED | | ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING | | STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN | | ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY | | CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT | | SPACE AND VEHICULAR ACCESS ROUTE) | | | | 5. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | FLORIDA BUILDING CODE. | | | | 6. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | VERIFIED. \ | | | | 7. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES | | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO | | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL | | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE | | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED | | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR | | OTHER APPROVED METHODS. | | | | 8. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | SITE IRRIGATION, ETC. | | | | 9. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | NEIGHBORING PROPERTIES. | | | | 10. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | 11. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | ROBERT BROWN | | BUILDING OFFICIAL | | TEL: 561 805 6652 | | EMAIL: [email protected] | | |
|
|
Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
Rev No |
3 |
Status |
P |
Date |
01-27-2023 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
01-27-2023 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
01-27-2023 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
Rev No |
2 |
Status |
F |
Date |
12-16-2022 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
12-16-2022 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
12-16-2022 |
Time |
|
Sent To |
|
|
Notes |
2022-12-16 11:11:26 | Z22080028 - 15TH AND LA KIRKSEY REZONING REVIEW | | 12.16.22 | | COMMENTS FOR CIVIL SUBMITTAL FROM RICK ROSSANO, SR. | | PROJECT COORDINATOR, ENGINEERING SERVICES AT | | 561-494-1098 [email protected] | | O PROVIDE CCTV VIDEO OF EXISTING STORMWATER | | INFRASTRUCTURE ALONG ENTIRE PROJECT FRONTAGE (CONDITION | | OF SITE PLAN APPROVAL). SANITARY CCTV WAS PROVIDED IN | | 12.16.22 RESUBMITTAL; NO STORMWATER CCTV OR REPORT | | FOUND. | | | | |
|
|
Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
Rev No |
1 |
Status |
F |
Date |
08-23-2022 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
08-23-2022 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
08-23-2022 |
Time |
|
Sent To |
|
|
Notes |
2022-08-23 14:03:47 | Z22080028 - 15TH AND LA KIRKSEY REZONING REVIEW 8.22.22 | | COMMENTS FOR CIVIL SUBMITTAL FROM RICK ROSSANO, SR. | | PROJECT COORDINATOR, ENGINEERING SERVICES AT | | 561-494-1098 [email protected] | | GENERAL: | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | (Z-XXXXXXXX). | | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | BELOW: | | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP | | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL | | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 | | B1960045731D3658206F27451722716EF | | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | FOUND HERE: | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | MS,-PERMITS-APPLICATIONS | | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM | | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, | | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | SERVICE FACILITIES OF THE CITY. | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | MORE INFORMATION, REFER TO THE LINK BELOW: | | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU | | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | [email protected] OR 561-494-1079 FOR FURTHER | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS | | DATA. | | | | BACKFLOW ASSEMBLY AND METERS: | | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER | | SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING | | TO THEM. | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | STRUCTURES WITHIN EASEMENT. | | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION | | OF WATER METER AND BACKFLOW | | PREVENTION. | | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY | | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER | | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO | | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE | | INSTALLED ABOVE-GROUND ONLY. | | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE | | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. | | | | WATER/WASTEWATER PLAN: | | O PROVIDE VERTICAL DATUM AND DATUM CONVERSION | | INFORMATION (NAVD 1988 AND NGVD 1929). | | O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. | | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE | | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. | | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND | | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND | | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH | | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE | | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, | | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO | | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, | | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, | | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT | | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF | | SANITARY SEWER LINES. | | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR | | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | PROFILE VIEW. | | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | VIEW FOR ALL SANITARY AND STORM SEWERS. | | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | MATERIAL. | | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | FACILITIES INCLUDING PIPE SIZE AND MATERIAL LOCATED IN | | THE RIGHT-OF-WAY. | | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER | | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD | | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. PLEASE | | INCLUDE FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION & | | TELECOMMUNICATION FACILITIES INCLUDING PIPE SIZE AND | | MATERIAL LOCATED IN THE RIGHT-OF-WAY. | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | FOR WATER. | | O PROVIDE FIRE FLOW TEST DATA. | | O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT FRONTAGE | | (CONDITION OF SITE PLAN APPROVAL). | | O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | ROW. | | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL | | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY | | PROPOSED LENGTH IN FEET. | | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | SEWER ARE REQUIRED. | | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE | | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. | | O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT | | STATION NUMBER. | | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | PROPOSED SANITARY LATERALS. | | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. | | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE | | TRAPS (IF ANY). | | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN | | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. | | | | FORMAL ENGINEERING REVIEW: | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | NOI REQUIREMENTS WILL BE ENFORCED. | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | DEVELOPMENT OR SALE; | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | OF THE 10-2 CERTIFICATION. | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | LEAD-FREE DESIGN. | | O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | PARCELS. | | O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE | | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. | | O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE | | 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER | | CITY OF WPB STANDARD DETAIL GC-8. | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR | | PROPOSED IMPROVED AREAS. | | | | QUESTIONS AND COORDINATION CONTACTS: | | O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH | | CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF | | BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT | | 561-822-2262 OR [email protected] | | O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES | | DEPARTMENT AT 561-494-1047 OR [email protected] | | O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING | | SERVICES DEPT. AT 561-494-1120 OR [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
08-29-2022 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
08-29-2022 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
08-29-2022 |
Time |
12:53 |
Sent To |
|
|
Notes |
2022-08-29 12:55:15 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | BEACH FIRE DEPARTMENT. | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | ARE SUBMITTED FOR PERMIT. | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | PROPOSED PROJECT SITE PLAN. | | | | WITH THE LIMIT BUIDING INFORMATION PROVIDED, THE | | FOLLOWING COMMENTS ARE INTENDED TO PROVIDE GUIDANCE FOR | | BUILDING PLAN SUBMITTAL. | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | PROTECTION. | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | ALL CONSTRUCTION ACTIVITIES. | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY | | WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION | | CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE | | CODES. | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE. | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | FIRE PREVENTION. | | | | THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL | | BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED | | WITH THE BUREAU OF FIRE PREVENTION. | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G | | AND SUBMITTED WITH THE MASTER PERMIT. | | | | 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE | | LOCATIONS SHALL MEET AND BE INSTALLED PER THE | | REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH | | THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS | | OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING | | AND ZONING OFFICE. | | | | 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF | | TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY | | LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | AND EQUIPMENT. | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | 12. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7 | | KEYWAY SYSTEM. | | | | ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S | | EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA | | B44, SAFETY CODE FOR ELEVATORS. | | | | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN | | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL | | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET | | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER | | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN | | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE | | IN THE HORIZONTAL POSITION. | | | | 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | RADIO ENHANCEMENT SERVICES. | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | DETERMINED BY THE AHJ. | | | | CONTACT WILL NEED TO BE MADE TO MARK FILLA, PALM BEACH | | COUNTY PUBLIC SAFETY RADIO SYSTEMS MANAGER, | | [email protected], 561-233-0837; AS OUR RADIOS OPERATE | | ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND | | INSTALLATION INSTRUCTIONS. | | | | 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
3 |
Status |
P |
Date |
02-01-2023 |
|
|
Cont ID |
|
Sent By |
rcaranci |
Date |
02-01-2023 |
Time |
10:09 |
Rev Time |
0.00 |
Received By |
rcaranci |
Date |
02-01-2023 |
Time |
10:08 |
Sent To |
|
|
Notes |
2023-02-01 10:10:01 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | 561-822-1462 | | PROJECT: 424 LA KIRKSEY Z22080028 | | FEBRUARY 1, 2023 | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON | | SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS | | SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD, | | MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS | | REPORT RATING THE CONDITION AND RELOCATION POTENTIAL | | FOR THE NATIVE TREES AND PALMS. | | | | 2. SATISFIED. SHEET L-1.1, EXISTING TREES AND PALMS TO | | REMAIN OR BE RELOCATED CANNOT BE COUNTED TOWARD ANY | | MITIGATION DUE, REMOVE CREDITS FROM THE CHART AND | | PROVIDE REVISED TOTAL OF MITIGATION DUE. CONVERT ALL | | MITIGATION DUE TO SQUARE FOOTAGE. | | | | 3. SATISFIED. SHEET L-1.1, MITIGATION CREDITS ARE NOT | | CORRECT, MUST USE THE CATEGORY LIST FOR TREE MITIGATION | | CREDITS. CATEGORY 1- 300 SQ FT CREDIT, CATEGORY - 150 | | SQ FT CREDIT, CATEGORY 3- 100 SQ FT CREDIT, CATEGORY 4- | | 50 SQ FT CREDIT. ANY SHORTFALL IN CANOPY CREDITS MUST | | BE CALCULATED FOR PAYMENT IN LIEU. | | MAKE THE FOLLOWING CORRECTIONS TO THE TREE MITIGATION | | CHART: | | ??? JACARANDA TRE#27 MITIGATION DUE IS 314 SQ FT. | | ??? TOTAL SHOULD BE 14,623 SQ FT MITIGATION DUE. | | ??? MITIGATION PROVIDED- SILVER BUTTONWOOD IS CATEGORY | | 2 AT 150 SQ FT EACH. | | ??? CHANGE WAX MYRTLE TO LIGUSTRUM | | ??? TOTAL MITIGATION PROVIDED IS 9350 SQ FT | | ??? PROVIDE PAYMENT IN LIEU AMOUNT BASED ON $500.00 PER | | 300 SQ FT CANOPY CREDIT. | | | | 4. SATISFIED. PER SECTION 94-442(B)Q. SHOW TREES AND | | PALMS ON THE ADJACENT PROPERTIES WITHIN 10 FEET OF THE | | PROPERTY LINE. | | | | 5. SATISFIED. PER SECTION 94-452, IRRIGATION MUST BE | | PROVIDED FOR THE RIGHT OF WAY LANDSCAPING. THE EXISTING | | PLANTING AREAS ALONG LA KIRKSEY WERE DESIGNED AS | | BIOSWALES TO ACCEPT STORMWATER RUNOFF. STAFF RECOMMENDS | | DESIGNING TO MAINTAIN THIS INTENT. SHADE TREES ARE | | PREFERRED TO BE ADDED TO S DIXIE RIGHT OF WAY TO | | PROVIDE SHADE FOR PEDESTRIANS. | | | | 6. CONDITIONALLY SATISFIED. PROVIDE A PRELIMINARY | | APPROVAL LETTER FROM FDOT FOR THE LANDSCAPING IN THE | | RIGHT OF WAY. | | | | 7. SATISFIED. TAG FOR QVR/2 IS NOT INDICATING THE | | CORRECT SYMBOL ON THE PLAN. INDICATE IF THE CURRENT | | TREE CANOPY WILL PROVIDE THE REQUIRED 14 FOOT CLEARANCE | | FOR TRAFFIC IF RELOCATED TO THE RIGHT OF WAY. | | | | 8. SATISFIED. PROVIDE A DETAIL AND SHOW THE LOCATIONS | | OF THE REQUIRED STRUCTURAL SOIL UNDER THE ADJACENT | | SIDEWALK OR HARDSCAPE AREAS FOR THE STREETSCAPE. | | | | STRUCTURAL SOIL SHOULD ONLY BE SHOWN IN AREAS THAT ARE | | PAVED, ALL UNPAVED AREAS WILL BE SHOWN AS PLANTING | | SOIL. | | CORRECTED SHEETS SUBMITTED 2/2/23. | | | | | | 9. SATISFIED. LANDSCAPE BUFFER OF 5 FEET IS REQUIRED ON | | THE EAST SIDE OF THE ACCESS ROAD FROM THE ALLEY WITH | | THE REQUIRED TREES. THIS IS TO PROVIDE PROTECTION FOR | | THE ADJACENT RESIDENTIAL. PALMS OR SMALLER TREES MAY BE | | USED AGAINST THE BUILDING TO PROVIDE ADDITIONAL | | SCREENING WITHOUT CAUSING MAINTENANCE ISSUES. | | | | 10. SATISFIED. SOUTH LANDSCAPE BUFFER ALONG THE ALLEY | | HAS A LARGE GAP IN THE BUFFER TREES THAT MUST BE | | CORRECTED TO MEET THE REQUIREMENTS. | | | | 11. SATISFIED. THE TERMINAL LANDSCAPE ISLANDS OUTSIDE | | THE BUILDING FOOTPRINT MUST MEET THE 8 FOOT WIDTH | | LANDSCAPE REQUIREMENT. CALCULATIONS FOR THE 75% SHADE | | TREE REQUIREMENT ARE PROVIDED, BUT DO NOT MATCH WHAT IS | | SHOWN ON THE PLAN. | | | | | | 12. SATISFIED. WATER LINES COMING INTO THE BUILDING | | FROM THE WEST SIDE NEED TO BE RELOCATED TO ALLOW THE | | REQUIRED BUFFER TREES TO BE LOCATED WITHOUT CONFLICT TO | | PROVIDE PROTECTION FOR THE ADJACENT RESIDENTIAL USE. | | | | | | 13. SATISFIED. PROVIDE SCREENING HEDGES FOR ALL GROUND | | MOUNTED VALVES AND EQUIPMENT CURRENTLY SHOWN ON THE | | LANDSCAPE PLAN. | | | | 14. SATISFIED. SHOW THE REQUIRED D CURBS FOR ALL | | LANDSCAPE AREAS ADJACENT TO VEHICULAR USE AREAS. | | | | 15. SATISFIED. WAX MYRTLES DO NOT MEET THE MINIMUM | | HEIGHT REQUIREMENT FOR TREES. | | | | CONDITIONS OF APPROVAL | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | SERVICES DEPARTMENT, PLANNING DIVISION. | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | IRRIGATION APPROVED WITH THIS PETITION. | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | RESPONSIBLE FOR THE MAINTENANCE OF THE STREET TREES AND | | RIGHT OF WAY LANDSCAPING AND IRRIGATION. THIS WILL BE | | THROUGH A SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | 4. STREETSCAPE IN FDOT RIGHT OF WAY MUST RECEIVE FDOT | | PERMIT APPROVAL PRIOR TO ISSUANCE OF THE CERTIFICATE OF | | OCCUPANCY FOR THE BUILDING. | | |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
2 |
Status |
F |
Date |
01-13-2023 |
|
|
Cont ID |
|
Sent By |
rcaranci |
Date |
01-13-2023 |
Time |
16:20 |
Rev Time |
0.00 |
Received By |
rcaranci |
Date |
01-13-2023 |
Time |
16:20 |
Sent To |
|
|
Notes |
2023-01-13 16:21:13 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | 561-822-1462 | | PROJECT: 424 LA KIRKSEY Z22080028 | | JANUARY 13, 2023 | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON | | SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS | | SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD, | | MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS | | REPORT RATING THE CONDITION AND RELOCATION POTENTIAL | | FOR THE NATIVE TREES AND PALMS. | | | | 2. SATISFIED. SHEET L-1.1, EXISTING TREES AND PALMS TO | | REMAIN OR BE RELOCATED CANNOT BE COUNTED TOWARD ANY | | MITIGATION DUE, REMOVE CREDITS FROM THE CHART AND | | PROVIDE REVISED TOTAL OF MITIGATION DUE. CONVERT ALL | | MITIGATION DUE TO SQUARE FOOTAGE. | | | | 3. PARTIALLY SATISFIED. SHEET L-1.1, MITIGATION CREDITS | | ARE NOT CORRECT, MUST USE THE CATEGORY LIST FOR TREE | | MITIGATION CREDITS. CATEGORY 1- 300 SQ FT CREDIT, | | CATEGORY - 150 SQ FT CREDIT, CATEGORY 3- 100 SQ FT | | CREDIT, CATEGORY 4- 50 SQ FT CREDIT. ANY SHORTFALL IN | | CANOPY CREDITS MUST BE CALCULATED FOR PAYMENT IN LIEU. | | MAKE THE FOLLOWING CORRECTIONS TO THE TREE MITIGATION | | CHART: | | ??? JACARANDA TRE#27 MITIGATION DUE IS 314 SQ FT. | | ??? TOTAL SHOULD BE 14,623 SQ FT MITIGATION DUE. | | ??? MITIGATION PROVIDED- SILVER BUTTONWOOD IS CATEGORY | | 2 AT 150 SQ FT EACH. | | ??? CHANGE WAX MYRTLE TO LIGUSTRUM | | ??? TOTAL MITIGATION PROVIDED IS 9350 SQ FT | | ??? PROVIDE PAYMENT IN LIEU AMOUNT BASED ON $500.00 PER | | 300 SQ FT CANOPY CREDIT. | | | | 4. SATISFIED. PER SECTION 94-442(B)Q. SHOW TREES AND | | PALMS ON THE ADJACENT PROPERTIES WITHIN 10 FEET OF THE | | PROPERTY LINE. | | | | 5. SATISFIED. PER SECTION 94-452, IRRIGATION MUST BE | | PROVIDED FOR THE RIGHT OF WAY LANDSCAPING. THE EXISTING | | PLANTING AREAS ALONG LA KIRKSEY WERE DESIGNED AS | | BIOSWALES TO ACCEPT STORMWATER RUNOFF. STAFF RECOMMENDS | | DESIGNING TO MAINTAIN THIS INTENT. SHADE TREES ARE | | PREFERRED TO BE ADDED TO S DIXIE RIGHT OF WAY TO | | PROVIDE SHADE FOR PEDESTRIANS. | | | | 6. CONDITIONALLY SATISFIED. PROVIDE A PRELIMINARY | | APPROVAL LETTER FROM FDOT FOR THE LANDSCAPING IN THE | | RIGHT OF WAY. | | | | 7. TAG FOR QVR/2 IS NOT INDICATING THE CORRECT SYMBOL | | ON THE PLAN. INDICATE IF THE CURRENT TREE CANOPY WILL | | PROVIDE THE REQUIRED 14 FOOT CLEARANCE FOR TRAFFIC IF | | RELOCATED TO THE RIGHT OF WAY. | | | | 8. PARTIALLY SATISFIED. PROVIDE A DETAIL AND SHOW THE | | LOCATIONS OF THE REQUIRED STRUCTURAL SOIL UNDER THE | | ADJACENT SIDEWALK OR HARDSCAPE AREAS FOR THE | | STREETSCAPE. | | | | STRUCTURAL SOIL SHOULD ONLY BE SHOWN IN AREAS THAT ARE | | PAVED, ALL UNPAVED AREAS WILL BE SHOWN AS PLANTING | | SOIL. | | | | | | 9. SATISFIED. LANDSCAPE BUFFER OF 5 FEET IS REQUIRED ON | | THE EAST SIDE OF THE ACCESS ROAD FROM THE ALLEY WITH | | THE REQUIRED TREES. THIS IS TO PROVIDE PROTECTION FOR | | THE ADJACENT RESIDENTIAL. PALMS OR SMALLER TREES MAY BE | | USED AGAINST THE BUILDING TO PROVIDE ADDITIONAL | | SCREENING WITHOUT CAUSING MAINTENANCE ISSUES. | | | | 10. SATISFIED. SOUTH LANDSCAPE BUFFER ALONG THE ALLEY | | HAS A LARGE GAP IN THE BUFFER TREES THAT MUST BE | | CORRECTED TO MEET THE REQUIREMENTS. | | | | 11. SATISFIED. THE TERMINAL LANDSCAPE ISLANDS OUTSIDE | | THE BUILDING FOOTPRINT MUST MEET THE 8 FOOT WIDTH | | LANDSCAPE REQUIREMENT. CALCULATIONS FOR THE 75% SHADE | | TREE REQUIREMENT ARE PROVIDED, BUT DO NOT MATCH WHAT IS | | SHOWN ON THE PLAN. | | | | | | 12. SATISFIED. WATER LINES COMING INTO THE BUILDING | | FROM THE WEST SIDE NEED TO BE RELOCATED TO ALLOW THE | | REQUIRED BUFFER TREES TO BE LOCATED WITHOUT CONFLICT TO | | PROVIDE PROTECTION FOR THE ADJACENT RESIDENTIAL USE. | | | | | | 13. SATISFIED. PROVIDE SCREENING HEDGES FOR ALL GROUND | | MOUNTED VALVES AND EQUIPMENT CURRENTLY SHOWN ON THE | | LANDSCAPE PLAN. | | | | 14. SATISFIED. SHOW THE REQUIRED D CURBS FOR ALL | | LANDSCAPE AREAS ADJACENT TO VEHICULAR USE AREAS. | | | | 15. SATISFIED. WAX MYRTLES DO NOT MEET THE MINIMUM | | HEIGHT REQUIREMENT FOR TREES. | | | | CONDITIONS OF APPROVAL | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | SERVICES DEPARTMENT, PLANNING DIVISION. | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | IRRIGATION APPROVED WITH THIS PETITION. | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | RESPONSIBLE FOR THE MAINTENANCE OF THE STREET TREES AND | | RIGHT OF WAY LANDSCAPING AND IRRIGATION. THIS WILL BE | | THROUGH A SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | 4. STREETSCAPE IN FDOT RIGHT OF WAY MUST RECEIVE FDOT | | PERMIT APPROVAL PRIOR TO ISSUANCE OF THE CERTIFICATE OF | | OCCUPANCY FOR THE BUILDING. | | |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
F |
Date |
09-06-2022 |
|
|
Cont ID |
|
Sent By |
rcaranci |
Date |
09-06-2022 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
rcaranci |
Date |
09-06-2022 |
Time |
16:53 |
Sent To |
|
|
Notes |
2022-09-06 16:54:17 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | 561-822-1462 | | PROJECT: 424 LA KIRKSEY Z22080028 | | SEPTEMBER 6, 2022 | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES AND | | PALMS IN GOOD CONDITION TO BE PRESERVED ON SITE OR | | RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY | | EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR | | POOR FOR RELOCATION. PROVIDE AN ARBORISTS REPORT RATING | | THE CONDITION AND RELOCATION POTENTIAL FOR THE NATIVE | | TREES AND PALMS. | | | | 2. SHEET L-1.1, EXISTING TREES AND PALMS TO REMAIN OR | | BE RELOCATED CANNOT BE COUNTED TOWARD ANY MITIGATION | | DUE, REMOVE CREDITS FROM THE CHART AND PROVIDE REVISED | | TOTAL OF MITIGATION DUE. CONVERT ALL MITIGATION DUE TO | | SQUARE FOOTAGE. | | | | 3. SHEET L-1.1, MITIGATION CREDITS ARE NOT CORRECT, | | MUST USE THE CATEGORY LIST FOR TREE MITIGATION CREDITS. | | CATEGORY 1- 300 SQ FT CREDIT, CATEGORY - 150 SQ FT | | CREDIT, CATEGORY 3- 100 SQ FT CREDIT, CATEGORY 4- 50 SQ | | FT CREDIT. ANY SHORTFALL IN CANOPY CREDITS MUST BE | | CALCULATED FOR PAYMENT IN LIEU. | | | | 4. PER SECTION 94-442(B)Q. SHOW TREES AND PALMS ON THE | | ADJACENT PROPERTIES WITHIN 10 FEET OF THE PROPERTY | | LINE. | | | | 5. PER SECTION 94-452, IRRIGATION MUST BE PROVIDED FOR | | THE RIGHT OF WAY LANDSCAPING. THE EXISTING PLANTING | | AREAS ALONG LA KIRKSEY WERE DESIGNED AS BIOSWALES TO | | ACCEPT STORMWATER RUNOFF. STAFF RECOMMENDS DESIGNING TO | | MAINTAIN THIS INTENT. SHADE TREES ARE PREFERRED TO BE | | ADDED TO S DIXIE RIGHT OF WAY TO PROVIDE SHADE FOR | | PEDESTRIANS. | | | | 6. PROVIDE A PRELIMINARY APPROVAL LETTER FROM FDOT FOR | | THE LANDSCAPING IN THE RIGHT OF WAY. | | | | 7. TAG FOR QVR/2 IS NOT INDICATING THE CORRECT SYMBOL | | ON THE PLAN. INDICATE IF THE CURRENT TREE CANOPY WILL | | PROVIDE THE REQUIRED 14 FOOT CLEARANCE FOR TRAFFIC IF | | RELOCATED TO THE RIGHT OF WAY. | | | | 8. PROVIDE A DETAIL AND SHOW THE LOCATIONS OF THE | | REQUIRED STRUCTURAL SOIL UNDER THE ADJACENT SIDEWALK OR | | HARDSCAPE AREAS FOR THE STREETSCAPE. | | | | 9. LANDSCAPE BUFFER OF 5 FEET IS REQUIRED ON THE EAST | | SIDE OF THE ACCESS ROAD FROM THE ALLEY WITH THE | | REQUIRED TREES. THIS IS TO PROVIDE PROTECTION FOR THE | | ADJACENT RESIDENTIAL. PALMS OR SMALLER TREES MAY BE | | USED AGAINST THE BUILDING TO PROVIDE ADDITIONAL | | SCREENING WITHOUT CAUSING MAINTENANCE ISSUES. | | | | 10. SOUTH LANDSCAPE BUFFER ALONG THE ALLEY HAS A LARGE | | GAP IN THE BUFFER TREES THAT MUST BE CORRECTED TO MEET | | THE REQUIREMENTS. | | | | 11. THE TERMINAL LANDSCAPE ISLANDS OUTSIDE THE BUILDING | | FOOTPRINT MUST MEET THE 8 FOOT WIDTH LANDSCAPE | | REQUIREMENT. CALCULATIONS FOR THE 75% SHADE TREE | | REQUIREMENT ARE PROVIDED, BUT DO NOT MATCH WHAT IS | | SHOWN ON THE PLAN. | | | | | | 12. WATER LINES COMING INTO THE BUILDING FROM THE WEST | | SIDE NEED TO BE RELOCATED TO ALLOW THE REQUIRED BUFFER | | TREES TO BE LOCATED WITHOUT CONFLICT TO PROVIDE | | PROTECTION FOR THE ADJACENT RESIDENTIAL USE. | | | | | | 13. PROVIDE SCREENING HEDGES FOR ALL GROUND MOUNTED | | VALVES AND EQUIPMENT CURRENTLY SHOWN ON THE LANDSCAPE | | PLAN. | | | | 14. SHOW THE REQUIRED D CURBS FOR ALL LANDSCAPE AREAS | | ADJACENT TO VEHICULAR USE AREAS. | | | | 15. WAX MYRTLES DO NOT MEET THE MINIMUM HEIGHT | | REQUIREMENT FOR TREES. | | | | CONDITIONS OF APPROVAL | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | SERVICES DEPARTMENT, PLANNING DIVISION. | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | IRRIGATION APPROVED WITH THIS PETITION. | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | RESPONSIBLE FOR THE MAINTENANCE OF THE STREET TREES AND | | RIGHT OF WAY LANDSCAPING AND IRRIGATION. THIS WILL BE | | THROUGH A SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | |
|
|
Review Stop |
PU |
PUBLIC UTILITIES |
Rev No |
2 |
Status |
P |
Date |
01-30-2023 |
|
|
Cont ID |
|
Sent By |
mtechnow |
Date |
01-30-2023 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
mtechnow |
Date |
01-30-2023 |
Time |
11:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
PU |
PUBLIC UTILITIES |
Rev No |
1 |
Status |
F |
Date |
09-08-2022 |
|
|
Cont ID |
|
Sent By |
mtechnow |
Date |
09-08-2022 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
mtechnow |
Date |
09-08-2022 |
Time |
11:40 |
Sent To |
|
|
Notes |
2022-09-08 11:48:20 | -UTILITIES IS REVIEWING THE PROPOSED WATER SERVICE | | CONNECTIONS ON 15TH ST TO VERIFY THAT THERE IS ADEQUATE | | CAPACITY. | | -REVISE THE SERVICE CONNECTION POINT ON 14TH ST TO | | CONNECT TO THE EXISITING 8" WM ON DIXIE. |
|
|
Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
Rev No |
2 |
Status |
P |
Date |
12-19-2022 |
|
|
Cont ID |
|
Sent By |
mhurley |
Date |
12-19-2022 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-12-19 10:13:41 | -LABEL FDC OR ADD SYMBOL TO LEGEND AT ENGINEERING | | DEVELOPMENT SUBMITTAL. | | -PROVIDE CLEARANCE DISTANCE BETWEEN EXISTING HYDRANT | | AND PROPOSED STORMWATER PIPE AT ENGINEERING DEVELOPMENT | | SUBMITTAL. | | -AT ENGINEERING DEVELOPMENT SUBMITTAL, UPDATE PLANS SO | | BACKFLOW ASSEMBLIES ARE NOT IN UTILITY EASEMENTS. | | -UPON FURTHER REVIEW AT ENGINEERING DEVELOPMENT | | SUBMITTAL, MAY NEED TO REMOVE EXISTING SEWER LATERALS | | AND MAY NEED TO EXPAND LIMITS OF PAVEMENT RESTORATION | | ON DIXIE. | | --AT ENGINEERING DEVELOPMENT SUBMITTAL, SHOW EXISTING | | WATER SERVICES GOING NORTH FROM WATER MAIN ON L A | | KIRKSEY. |
|
|
Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
Rev No |
1 |
Status |
F |
Date |
09-02-2022 |
|
|
Cont ID |
|
Sent By |
mhurley |
Date |
09-02-2022 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-09-02 11:40:23 | PLEASE PROVIDE WRITTEN RESPONSES THE FOLLOWING: | | -ADD LEGEND TO EACH ENGINEERING PLAN SHEET SHOWING | | SYMBOLS AND LINES USED THAT ARE NOT OTHERWISE LABELED. | | -SHOW UTILITY EASEMENTS ON SHEET C05. BACKFLOW | | ASSEMBLIES SHOULD NOT BE IN UTILITY EASEMENTS. | | -CALLOUT THE RP BACKFLOW ASSEMBLIES FOR THE PROPOSED 1 | | INCH METERED WATER SERVICES. ENSURE LABEL HAS SIZING. | | -SHOW AND LABEL SEWER LATERAL CLEANOUTS. | | -IS THE 2 INCH METER FOR IRRIGATION? IF NOT, IS A | | METERED IRRIGATION WATER SERVICE NEEDED? | | -ON DEMO PLAN SHOW AND EXISTING METERED WATER SERVICES | | AND LABEL WHAT IS HAPPENING TO THEM. | | -PROVIDE CLEARANCE DISTANCE BETWEEN SOUTHERN BUSH AND | | BACKFLOW ASSEMBLY SHOWN ON LANDSCAPING PLAN L2.0. | | -SHOW AND LABEL FDC ON PLANS IF ANY ARE NEEDED OR | | REQUIRED. | | -SHOW AND LABEL ALL EXISTING UTILITY POLES, LIGHT | | POLES, AND GUY WIRES NEAR PROPERTY ON ENGINEERING PLAN | | SHEETS IF THEY WILL REMAIN. | | -LABEL THE STREETS ON DEMO PLAN. | | -ONE OF THE STORMWATER LINES ON DIXIE SHOWS IT IN CLOSE | | PROXIMITY TO WATER MAIN. IS THAT CORRECT? | | -VERIFY THERE IS NO UTILITY OR FPL EASEMENTS RUNNING | | ALONG ALLEY. | | -ON AUTOTURN EXHIBIT, PLEASE SHOW UTILITY VAC TRUCK 7 | | FEET WIDE, 13 FEET HIGH, AND 36 FOOT LONG CAN | | SUCCESSFULLY NAVIGATE THROUGH PROPOSED ONE WAY ALLEY | | TURN. | | -IF THERE WILL BE ANY GREASE TRAPS OUTSIDE BUILDING, | | THEN SHOW AND LABEL ON PLANS. | | -MAY HAVE TO GRANT UTILITY EASEMENT FOR PROPOSED | | SANITARY SEWER MAIN. | | -LABEL ADJACENT PROPERTY ADDRESSES ON ENGINEERING PLAN | | SHEETS. | | -SHOW EXISTING SEWER LATERALS AND LABEL WHAT IS | | HAPPENING TO THEM. | | RESPECTFULLY, | | MARK HURLEY [email protected] | | |
|
|
Review Stop |
PW |
PUBLIC WORKS |
Rev No |
3 |
Status |
P |
Date |
01-31-2023 |
|
|
Cont ID |
|
Sent By |
|
Date |
01-31-2023 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
01-31-2023 |
Time |
|
Sent To |
|
|
Notes |
2023-01-31 11:57:35 | NO FURTHER COMMENTS. |
|
|
Review Stop |
PW |
PUBLIC WORKS |
Rev No |
2 |
Status |
F |
Date |
01-18-2023 |
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
01-18-2023 |
Time |
|
Sent To |
|
|
Notes |
2023-01-18 14:20:18 | PLEASE PROVIDE A REVISED AUTOTURN EXHIBIT, SHEET C-07, | | TO REFLECT: | | 1- THE CORRECT SANITATION COLLECTION TRUCK (FRONT | | LOADER) WITH DYNAMIC ENVELOPE AND THE VEHICLE???S WHEEL | | PATH IDENTIFIED WITH DIFFERENT COLORS FOR THE | | SANITATION SERVICE, FRONT LOADER TRUCK WITH THE | | FOLLOWING SPECS: | | - DUAL AXLES | | - TRUCK LENGTH: 35 FT | | - TRUCK WIDTH: 11 FT | | - TURNING RADIUS: | | - SAE TURNING RADIUS: 32.5 FT | | - CURB-TO-CURB DIAMETER: 74 FT | | - WALL-TO-WALL DIAMETER: 86.3 FT | | 2- REVISE S.E. TURNING RADII TO PREVENT ANY POTENTIAL | | ENCROACHMENT FOR THE SANITATION COLLECTION TRUCK. | | | | | | MATT HEJAZI | | DEPT. OF PUBLIC WORKS | | [email protected] | | 5461-822-2045 |
|
|
Review Stop |
PW |
PUBLIC WORKS |
Rev No |
1 |
Status |
F |
Date |
08-25-2022 |
|
|
Cont ID |
|
Sent By |
|
Date |
08-25-2022 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
08-25-2022 |
Time |
|
Sent To |
|
|
Notes |
2022-08-25 11:32:42 | PLEASE PROVIDE THE FOLLOWINGS: | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND | | QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR) | | THAT WILL BE UTILIZED FOR THE SANITATION SERVICE. | | 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE | | CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.). FOR A | | FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE | | SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST | | PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE | | STANDARD, GC-7. (LINK TO THE LATEST REVISION OF THE | | GC-7 DOCUMENT: HTTPS://WWW.WPB.ORG/HOME/SHOWPUBLISHEDDO | | CUMENT/3690/637629060422100000) | | 3- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE?S | | WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER | | TRUCK WITH THE FOLLOWING SPECS: | | - DUAL AXLES | | - TRUCK LENGTH: 35 FT | | - TRUCK WIDTH: 11 FT | | - TURNING RADIUS: | | - SAE TURNING RADIUS: 32.5 FT | | - CURB-TO-CURB DIAMETER: 74 FT | | - WALL-TO-WALL DIAMETER: 86.3 FT | | 4- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND | | RECYCLING CONTAINERS | | 5- OWNERS AND/OR OCCUPANTS OF PROPERTY THAT REQUIRE | | GREASE HAULING SERVICES SHALL ENSURE THAT THEIR GREASE | | TANKS OR CONTAINERS REMAIN CLEAN, AND ARE ENCLOSED AND | | NOT IN PUBLIC VIEW. | | 6- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN | | THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF | | THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC | | WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND | | COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING | | MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE | | CAN(S). | | 7- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE | | CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA | | STATUES [553.5041 F.S.]. | | 8- SIGNAGE PLAN. ALL STRIPING AND SIGNAGE SHALL COMPLY | | WITH THE LATEST CITY OF WEST PALM BEACH STANDARD | | DETAILS AND MEET THE M.U.T.C.D. LATEST EDITION. | | 9- ALL PAVEMENT MARKING , SIGNING AND SIDEWALK DAMAGED | | DURING CONSTRUCTION SHALL BE RESTORED. | | | | | | | | MATT HEJAZI | | DEPT. OF PUBLIC WORKS | | [email protected] | | 561-822-2045 |
|
|
Review Stop |
STORM |
STORMWATER |
Rev No |
1 |
Status |
P |
Date |
09-08-2022 |
|
|
Cont ID |
|
Sent By |
tward |
Date |
09-08-2022 |
Time |
12:58 |
Rev Time |
0.00 |
Received By |
tward |
Date |
09-08-2022 |
Time |
12:59 |
Sent To |
|
|
Notes |
2022-09-08 12:59:10 | SEE COMMENTS UNDER Z22080027. | | | | TRACY WARD, PE | | SENIOR STORMWATER ENGINEER | | ENGINEERING SERVICES DEPARTMENT | | 561-494-1120 (O) | | 561-351-0510 (M) | | [email protected] | | |
|
|
Review Stop |
SURVEY |
SURVEYING |
Rev No |
2 |
Status |
P |
Date |
01-19-2023 |
|
|
Cont ID |
|
Sent By |
vnoel |
Date |
01-19-2023 |
Time |
06:28 |
Rev Time |
0.00 |
Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2023-01-19 06:28:09 | CONDITION OF REPLAT PRIOR TO C.O. | | SEE COMMENTS UNDER Z22080029 |
|
|
Review Stop |
SURVEY |
SURVEYING |
Rev No |
1 |
Status |
F |
Date |
09-06-2022 |
|
|
Cont ID |
|
Sent By |
vnoel |
Date |
09-06-2022 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-09-06 11:22:50 | 1. REPLAT WILL BE REQUIRED. | | 2. APPROVAL REQUIRED FROM FDOT FOR IMPROVEMENTS AND | | MANHOLES IN SIDEWALK. | | 3. ALLEY WILL BE BY EASEMENT FOR ACCESS AND UTILITIES | | WITH MAINTENANCE OBLIGATION BY APPLICANT. | | 4. CHECK DESCRIPTION OF LOT 17 ON SURVEY, S/B PLAT BOOK | | 1 , PAGE 127. |
|
|
Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
Rev No |
2 |
Status |
P |
Date |
01-31-2023 |
|
|
Cont ID |
|
Sent By |
|
Date |
01-31-2023 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
01-31-2023 |
Time |
|
Sent To |
|
|
Notes |
2023-01-31 16:17:40 | APPROVED WITH THE FOLLOWING CONDITIONS: | | 1. PROVIDE A REVISED AUTOTURN ANALYSIS, SHOWCASING A | | LEGEND AND MITIGATING THE HIGHLIGHTED ENCROACHMENTS | | 2. PROVIDE A REVISED SITE PLAN TO ADDRESS LATEST | | TRANSPORTATION COMMENTS PERTAINING SIGNAGE AND PAVEMENT | | MARKINGS | | REVISED TRANSPORTATION SITE PLAN AND AUTOTURN DRAWINGS, | | INCLUSIVE OF DETAILED CITY COMMENTS, WERE PROVIDED TO | | JOSEPH VERDONE ON 1/31/2023 VIA EMAIL. | | | | PAST TRAFFIC COMMENTS | | 1) SATISFIED. PROVIDE A FULL DETAILED TRAFFIC STUDY | | 2) SATISFIED. PROVIDE COUNTY TPS LETTER | | 3) SATISFIED. DEPENDING ON THE OUTCOME OF THE TRAFFIC | | ANALYSIS, TRANSPORTATION DEMAND MANAGEMENT (TDM) | | MEASURES MAY BE REQUIRED | | 4) SATISFIED. THE TRAFFIC ANALYSIS FOR THE LUPA | | APPLICATION HAS SIGNIFICANT TRIP GENERATION DIFFERENCES | | AND RESULTS WITH RESPECT TO THE LATEST TRAFFIC STUDY. | | PLEASE CORRECT, REVISE, AND RE-SUBMIT BOTH DOCUMENTS | | FOR SAKE OF CONSISTENCY | | 5) SATISFIED. PROVIDE A CLEAN TRANSPORTATION SPECIFIC | | SITE PLAN FOR THE GROUND FLOOR. SHOWCASING | | TRANSPORTATION RELATED FEATURES (E.G. ROADWAY WIDTHS, | | DRIVING AISLES, PARKING STALLS, SIDEWALK, CURB, GUTTER, | | DRIVEWAY, GATES, CROSSWALKS, VISIBILITY TRIANGLE, | | CORNER & DRIVEWAY SEPARATION DISTANCES, SLOPES, ETC.) | | PROPERLY LABELED AND DIMENSIONED. THE SITE PLAN SHOULD | | BE NAMED T-1.0. PROVIDE TRAVEL LANE(S) DIMENSION FOR | | 14TH AND 15TH STREETS AT THE INTERSECTION WITH DIXIE | | HWY | | 6) SATISFIED. IN THE T-1.0 SITE PLAN, PLEASE SHOWCASE | | BASIC CURB DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT | | MARKINGS, PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF | | THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT. SEVERAL | | PAVEMENT MARKINGS ALONG THE NORTHERN SIDE OF 15TH ST | | ARE MISSING | | 7) SATISFIED. PROVIDE A SIGNAGE AND PAVEMENT MARKING | | PLAN. INCLUSIVE OF ALL FEATURES WITHIN THE PROPOSED | | DEVELOPMENT AND ALONG ALL ROADS FRONTING THE SITE. THE | | SITE PLAN IS PART OF THE TRANSPORTATION REVIEW AND | | SHOULD BE NAMED ACCORDINGLY (E.G. T-1.1 OR T-2.0) | | 8) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE | | TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND OUT OF THE | | PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND | | WHEEL PATHS CLEARLY DISTINCT AND DEFINED IN DIFFERENT | | COLORS. SITE PLAN(S) CONTAINING THE ANALYSIS ARE PART | | OF THE TRANSPORTATION REVIEW AND SHOULD BE NAMED | | ACCORDINGLY (E.G. T1.2, T-3.0) | | 9) SATISFIED. PROVIDE ENGINEERING REFERENCE AND SPECS | | SHEETS FOR EACH OF THE PROPOSED TRANSPORTATION FEATURES | | (E.G. CURB, RAMP, GATE, SIGNAGE, PAVEMENT MARKING, | | SIGNAL, ETC.) | | 10) SATISFIED. IN THE PAVEMENT, MARKING & SIGN PLAN, | | PROVIDE A TABLE SHOWCASING THE NUMBER OF EXISTING AND | | PROPOSED ON-STREET PARKING STALLS. PROVIDE THE NUMBER | | OF METERED STALLS THAT ARE BEING REMOVED OR RELOCATED, | | IF ANY | | 11) SATISFIED. ARE THERE ANY GATES PROPOSED? IF SO, | | CLEARLY SHOWCASE THE REQUIRED 20 FEET SETBACK DISTANCE | | FROM THE BACK OF THE SIDEWALK | | 12) SATISFIED. FOR SAFETY AND OPERATIONAL PURPOSES, NO | | NEW ON-STREET PARKING STALLS ADJACENT TO THE BIKE LANE | | AND IN THE PROXIMITY OF AN INTERSECTION SHALL BE | | ALLOWED. PLEASE REVISE THE SITE PLANS ACCORDINGLY | | 13) SATISFIED. PLEASE PROVIDE A COMPLETE PARKING TABLE, | | SHOWCASING THE NUMBER OF REQUIRED AND PROVIDED PARKING | | STALLS, INCLUSIVE OF ADA AND BICYCLE ONES. PROVIDE CITY | | CODE REFERENCE FOR THE CALCULATION | | 14) SATISFIED. THE PROPOSED FULL-ACCESS DRIVEWAY ON | | 15TH ST SHOULD BE EXIT-ONLY, WHILE CONVERTING THE | | PROPOSED WESTERN EXIT-ONLY DRIVEWAY TO A FULL-ACCESS | | ONE. MOREOVER, THE EASTERN DRIVEWAY NEEDS TO BE 125 | | FEET AWAY FROM THE INTERSECTION, PER FDOT CORNER | | CLEARANCE REQUIREMENT. PLEASE SHOWCASE SUCH DISTANCE IN | | THE TRANSPORTATION PLAN. LATEST RESUBMISSION DOES NOT | | SHOW THE REQUIRED (AND REQUESTED) 125 FEET CORNER | | CLEARANCE DISTANCE | | 15) SATISFIED. THE ALLEY MUST BE DESIGNATED ONE-WAY | | ONLY. CORRESPONDING SIGNAGE AND PAVEMENT MARKING | | INSTALLED AND SHOWN ON THE PLANS. PLEASE COORDINATE | | WITH PUBLIC WORKS PERTAINING THE DIRECTIONALITY AND | | NOTIFY TRAFFIC ENGINEERING ABOUT THE FINAL DECISION. | | PLEASE DESIGNATE THE ALLEY EAST/SOUTHBOUND, AND PROVIDE | | ACKNOWLEDGMENT THAT IT WILL BE RE-PAVED, PAVEMENT | | MARKED, AND SIGNED ACCORDINGLY THROUGHOUT | | 16) SATISFIED. PROPOSED ON-STREET PARKING STALLS ON | | 14TH ST MAY NOT MEET CORNER CLEARANCE REQUIREMENT (125 | | FEET). PLEASE SHOWCASE SUCH DISTANCE IN THE | | TRANSPORTATION PLAN | | 17) PARTIALLY SATISFIED. PROVIDE AUTOTURN SHOWCASING AN | | SUV SIZED VEHICLE TRAVERSING THE ALLEYWAY, SO TO VERIFY | | THE FEASIBILITY OF ITS RE-ALIGNMENT (I.E. TURNING | | POINT) | | 18) SATISFIED. PLEASE VERIFY DIMENSIONS AND | | CONFIGURATION OF THE WESTERN LEG AT THE 15TH AND DIXIE | | HWY INTERSECTION. EXISTING PAVEMENT MARKINGS ARE | | SHOWING A SLIGHT KINK TO ACCOMMODATE 10-FEET TRAVEL | | LANES. PROPOSED SITE PLANS SHOW A STRAIGHTENING OF THE | | DOUBLE-YELLOW LINES, WHICH MAY NOT BE FEASIBLE DUE TO | | GEOMETRIC AND DRAINAGE CONSTRAINTS | | | | VALERIO ORICCHIO | | CITY TRANSPORTATION ENGINEER | | 561-494-1092 | | [email protected] | | |
|
|
Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
Rev No |
1 |
Status |
F |
Date |
09-07-2022 |
|
|
Cont ID |
|
Sent By |
|
Date |
09-07-2022 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
09-07-2022 |
Time |
|
Sent To |
|
|
Notes |
2022-09-07 23:34:51 | TRAFFIC COMMENTS | | 1) PROVIDE A FULL DETAILED TRAFFIC STUDY | | 2) PROVIDE COUNTY TPS LETTER | | 3) DEPENDING ON THE OUTCOME OF THE TRAFFIC ANALYSIS, | | TRANSPORTATION DEMAND MANAGEMENT (TDM) MEASURES MAY BE | | REQUIRED | | | | SITE COMMENTS | | 4) PROVIDE A CLEAN TRANSPORTATION SPECIFIC SITE PLAN | | FOR THE GROUND FLOOR. SHOWCASING TRANSPORTATION RELATED | | FEATURES (E.G. ROADWAY WIDTHS, DRIVING AISLES, PARKING | | STALLS, SIDEWALK, CURB, GUTTER, DRIVEWAY, GATES, | | CROSSWALKS, VISIBILITY TRIANGLE, CORNER & DRIVEWAY | | SEPARATION DISTANCES, SLOPES, ETC.) PROPERLY LABELED | | AND DIMENSIONED. THE SITE PLAN SHOULD BE NAMED T-1.0 | | 5) IN THE T-1.0 SITE PLAN, PLEASE SHOWCASE BASIC CURB | | DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT MARKINGS, | | PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF THE ROADS | | SURROUNDING THE PROPOSED DEVELOPMENT | | 6) PROVIDE A SIGNAGE AND PAVEMENT MARKING PLAN. | | INCLUSIVE OF ALL FEATURES WITHIN THE PROPOSED | | DEVELOPMENT AND ALONG ALL ROADS FRONTING THE SITE. THE | | SITE PLAN IS PART OF THE TRANSPORTATION REVIEW AND | | SHOULD BE NAMED ACCORDINGLY (E.G. T-1.1 OR T-2.0) | | 7) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR | | SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED | | DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL | | PATHS CLEARLY DISTINCT AND DEFINED IN DIFFERENT COLORS. | | SITE PLAN(S) CONTAINING THE ANALYSIS ARE PART OF THE | | TRANSPORTATION REVIEW AND SHOULD BE NAMED ACCORDINGLY | | (E.G. T1.2, T-3.0) | | 8) PROVIDE ENGINEERING REFERENCE AND SPECS SHEETS FOR | | EACH OF THE PROPOSED TRANSPORTATION FEATURES (E.G. | | CURB, RAMP, GATE, SIGNAGE, PAVEMENT MARKING, SIGNAL, | | ETC.) | | 9) IN THE PAVEMENT, MARKING & SIGN PLAN, PROVIDE A | | TABLE SHOWCASING THE NUMBER OF EXISTING AND PROPOSED | | ON-STREET PARKING STALLS. PROVIDE THE NUMBER OF METERED | | STALLS THAT ARE BEING REMOVED OR RELOCATED, IF ANY | | 10) ARE THERE ANY GATES PROPOSED? IF SO, CLEARLY | | SHOWCASE THE REQUIRED 20 FEET SETBACK DISTANCE FROM THE | | BACK OF THE SIDEWALK | | 11) FOR SAFETY AND OPERATIONAL PURPOSES, NO NEW | | ON-STREET PARKING STALLS ADJACENT TO THE BIKE LANE AND | | IN THE PROXIMITY OF AN INTERSECTION SHALL BE ALLOWED. | | PLEASE REVISE THE SITE PLANS ACCORDINGLY | | 12) PLEASE PROVIDE A COMPLETE PARKING TABLE, SHOWCASING | | THE NUMBER OF REQUIRED AND PROVIDED PARKING STALLS, | | INCLUSIVE OF ADA AND BICYCLE ONES. PROVIDE CITY CODE | | REFERENCE FOR THE CALCULATION | | 13) THE PROPOSED FULL-ACCESS DRIVEWAY ON 15TH ST SHOULD | | BE EXIT-ONLY, WHILE CONVERTING THE PROPOSED WESTERN | | EXIT-ONLY DRIVEWAY TO A FULL-ACCESS ONE. MOREOVER, THE | | EASTERN DRIVEWAY NEEDS TO BE 125 FEET AWAY FROM THE | | INTERSECTION, PER FDOT CORNER CLEARANCE REQUIREMENT. | | PLEASE SHOWCASE SUCH DISTANCE IN THE TRANSPORTATION | | PLAN | | 14) THE ALLEY MUST BE DESIGNATED ONE-WAY ONLY. | | CORRESPONDING SIGNAGE AND PAVEMENT MARKING INSTALLED | | AND SHOWN ON THE PLANS. PLEASE COORDINATE WITH PUBLIC | | WORKS PERTAINING THE DIRECTIONALITY AND NOTIFY TRAFFIC | | ENGINEERING ABOUT THE FINAL DECISION | | 15) PROPOSED ON-STREET PARKING STALLS ON 14TH ST MAY | | NOT MEET CORNER CLEARANCE REQUIREMENT (125 FEET). | | PLEASE SHOWCASE SUCH DISTANCE IN THE TRANSPORTATION | | PLAN | | | | VALERIO ORICCHIO | | CITY TRANSPORTATION ENGINEER | | 561-494-1092 | | [email protected] | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
02-02-2023 |
|
|
Cont ID |
|
Sent By |
kdefranc |
Date |
02-02-2023 |
Time |
14:07 |
Rev Time |
0.00 |
Received By |
kdefranc |
Date |
02-02-2023 |
Time |
14:05 |
Sent To |
|
|
Notes |
2023-02-02 14:06:27 | 2/2/23 ??? FAILED | | | | | | PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN | | RESUBMITTING: | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED | | MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG | | WITH ONE (1) REDUCED COPY (11 IN X 17 IN). | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | ADDITIONAL COMMENTS. | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1) | | RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF | | 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED | | AFTER THE FIRST RESUBMITTAL. | | | | REQUIRED MATERIALS MUST BE PROVIDED: | | F. PLEASE PROVIDE CONFIRMATION LETTERS FROM PUBLIC | | UTILITIES (AT&T TELECOMMUNICATION, FLORIDA PUBLIC | | UTILITIES, AND COMCAST CABLE COMMUNICATIONS) CONFIRMING | | THAT THE PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR | | EASEMENTS OR OTHERWISE INTERFERE WITH THE PROVISIONS OF | | THEIR SERVICES. [SATISFIED] | | G. PLEASE PROVIDE EVIDENCE OF THE UNIFIED CONTROL OF | | THE ENTIRE AREA. [SATISFIED] | | H. PLEASE PROVIDE THE AGREEMENTS, PROVISIONS OR | | COVENANTS WHICH GOVERN THE USE, MAINTENANCE AND | | CONTINUED PROTECTION OF THE PD AND ANY OF ITS COMMON | | AREAS OR FACILITIES. [SATISFIED SUBJECT TO THIS BE | | PROVIDED PRIOR TO BUILDING PERMIT APPLICATION] | | I. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW | | COMMENTS BELOW. [PARTIALLY SATISFIED] | | J. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT | | INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED | | MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL. | | [NOT SATISFIED] | | K. PLEASE PROVIDE COMPLETED PUBLIC NOTICE MAILER | | AFFIDAVITS WHEN MAILERS HAVE BEEN SENT OUT. [SATISFIED | | SUBJECT TO THESE BE PROVIDED PRIOR TO THE DEADLINES FOR | | THE PLANNING BOARD AND CITY COMMISSION MEETINGS] | | L. PLEASE PROVIDE COMPLETED SIGN POSTING AFFIDAVITS | | WHEN SIGNS HAVE BEEN PUT UP. [SATISFIED SUBJECT TO | | THESE BE PROVIDED PRIOR TO THE DEADLINES FOR THE | | PLANNING BOARD AND CITY COMMISSION MEETINGS] | | | | PREVIOUS REVIEW COMMENTS MUST BE ADDRESSED: | | 1. IN ACCORDANCE WITH THE CITY???S ZONING AND LAND | | DEVELOPMENT REGULATIONS (ZLDR) SUBSECTION | | 94-207(B)(9)(A)(1), PLEASE IDENTIFY/INDICATE THE NAME | | OF THE DEVELOPER ON THE ???COVER??? SHEET NUMBER A-0 | | AND/OR ???SITE PLAN??? SHEET NUMBER A-1. [SATISFIED] | | 2. THE PROPOSAL DEMONSTRATED IS NOT IN COMPLIANCE WITH | | THE (VISIBILITY TRIANGLE AT INTERSECTIONS REQUIREMENT) | | ZLDR SUBSECTION 94-207(B)(6), THEREFORE, PLEASE REVISE | | THE DIFFERENT PLANS, ELEVATIONS, AND SECTION, | | ACCORDINGLY. [SATISFIED] | | 3. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING | | AND PROPOSED EASEMENTS ON THE DIFFERENT PLANS. | | [PARTIALLY SATISFIED] | | 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING | | AND PROPOSED FIRE HYDRANTS (OR OPERATIONAL EQUIVALENTS) | | WITHIN 250 FEET OF THE PROPOSED STRUCTURE(S) ON THE | | ???SITE PLAN??? SHEET NUMBER A-1. [SATISFIED] | | 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF | | ANY SPECIAL UTILITY STRUCTURES SUCH AS VALVES, METERS, | | BACKFLOW CONNECTIONS, PUMP STATIONS, TRANSFORMERS, AND | | ALL ABOVE GROUND APPURTENANCES ON THE ???SITE PLAN??? | | SHEET NUMBER A-1. [SATISFIED] | | 6. THE PROPOSED LOADING SPACES ARE NOT IN COMPLIANCE | | WITH THE MINIMUM LOADING SPACE DIMENSIONAL REQUIREMENTS | | OF THE ZLDR SUBSECTION 94-485(P), THEREFORE PLEASE | | REVISE THE DIFFERENT PLANS, ACCORDINGLY. [NOT SATISFIED | | - HOWEVER, WAIVER REQUEST ACKNOWLEDGED] | | 7. PLEASE FURTHER EXPLAIN/CLARIFY/CONFIRM WHETHER THE | | PROPOSED LOADING SPACES ARE FOR THE PROPOSED | | SELF-STORAGE USE OR FOR ALL THE PROPOSED USES. | | [RESPONSE PROVIDED] | | 8. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-485(Q), | | PLEASE IDENTIFY/INDICATE THE REQUIRED AND PROPOSED | | NUMBER OF BICYCLE PARKING SPACES IN THE ???PARKING??? | | TABLE ON THE ???SITE PLAN??? SHEET NUMBER A-1. | | [SATISFIED] | | 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING | | BIKE LANE (TO REMAIN) ALONG LA KIRKSEY/15TH STREET ON | | THE ???BOUNDARY SURVEY??? AND ???SITE PLAN??? SHEET | | NUMBER A-1. [SATISFIED] | | 10. IN ACCORDANCE WITH THE ZLDR SUBSECTION | | 94-207(B)(9)(A)(7), PLEASE | | IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF PROPOSED | | MASS TRANSIT FACILITIES ON THE ???SITE PLAN??? SHEET | | NUMBER A-1. [RESPONSE PROVIDED] | | 11. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE CURB | | CUTS/CONCRETE DRIVE ACCESSES REMOVED ALONG DIXIE | | HIGHWAY ON THE DIFFERENT PLANS, ACCORDINGLY, SIMILAR TO | | THE INFORMATION DISPLAYED ON THE ???SITE PLAN??? SHEET | | NUMBER C-02, ???DEMOLITION PLAN??? SHEET NUMBER C-03, | | AND ???PAVING, GRADING, AND DRAINAGE PLANS??? SHEET | | NUMBER C-04. [SATISFIED] | | 12. PLEASE DEMONSTRATE HOW THE CITY???S SANITATION | | SERVICE TRUCKS WILL ACCESS/COLLECT THE TRASH FROM THE | | PROPOSED TRASH AREA TO THE SOUTH ON THE ???AUTOTURN | | EXHIBIT??? SHEET NUMBER C-07. [SATISFIED] | | 13. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-443, | | PLEASE REVISE THE DIFFERENT PLANS AND ELEVATIONS, | | ACCORDINGLY, TO IDENTIFY/INDICATE/DEMONSTRATE THE | | REQUIRED PROTECTIVE SCREEN WALL ALONG THE WEST PROPERTY | | LINE ADJACENT TO THE RESIDENTIAL PROPERTY/RESIDENTIAL | | ZONING DISTRICT. [SATISFIED] | | 14. IT HAS BEEN IDENTIFIED THAT THERE ARE | | INCONSISTENCIES BETWEEN THE PLANS AND ELEVATIONS | | REGARDING THE PROPOSED FIVE-FOOT-HIGH SECURITY/ALUMINUM | | FENCE, THEREFORE PLEASE REVISE, ACCORDINGLY. | | [SATISFIED] | | 15. PLEASE PROVIDE AN | | ILLUMINATION/LIGHTING/PHOTOMETRICS PLAN DEMONSTRATING | | COMPLIANCE WITH THE ZLDR SUBSECTION 94-207(D)(8). | | [SATISFIED] | | 16. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-409, | | PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE PROPOSED | | BUILDING FA??ADE SIZE, PERCENT SIGNAGE PERMITTED, AND | | PERMITTED SIGN SIZE FOR THE PROPOSED WALL MOUNTED SIGNS | | ON THE ???COLOR ELEVATIONS??? SHEET NUMBERS A-3 TO A-4. | | [PARTIALLY SATISFIED] | | 17. THE PROPOSED ???WEST ELEVATION??? WALL MOUNTED SIGN | | IS NOT IN COMPLIANCE WITH THE ZLDR SUBSECTION | | 94-402(B)(2)(7), THEREFORE PLEASE REVISE THE ???COLOR | | ELEVATION??? SHEET NUMBER A-4, ACCORDINGLY. [SATISFIED] | | 18. PLEASE PROVIDE THE STANDARD CITY DETAILS OF | | VEHICLE/BICYCLE PARKING (STANDARD, COMPACT, ADA), | | LOADING, ADA RAMPS, DRIVEWAYS, DUMPSTERS AND SIGNS. | | [SATISFIED] | | 19. PLEASE UPDATE THE ???SITE DATA??? ON THE ???SITE | | PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE | | CORRESPONDING DATA FOR THE ???ALLOWED??? INFORMATION | | WITHIN THE EXISTING MF14 AND GC ZONING DISTRICTS. | | [PARTIALLY SATISFIED] | | 20. PLEASE UPDATE THE ???SITE DATA??? ON THE ???SITE | | PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE | | MAXIMUM AND PROPOSED LOT COVERAGE BY BUILDINGS AND | | IMPERMEABLE SURFACE ACCORDING TO THE ZLDR SECTIONS | | 94-241 AND 94-243. [SATISFIED] | | 21. PLEASE CORRECT THE ???SITE DATA??? ON THE ???SITE | | PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE | | MAXIMUM BUILDING HEIGHTS (???ALLOWED???) INFORMATION | | ACCORDING TO THE ZLDR SUBSECTIONS 94-241 AND 94-243 FOR | | THE EXISTING MF14 AND GC ZONING DISTRICTS AND ADD THE | | PROPOSED HEIGHT ???TO THE TOP OF THE PARAPET??? | | INFORMATION TO REFLECT THE SAME INFORMATION | | DEMONSTRATED IN THE ELEVATIONS. [PARTIALLY SATISFIED] | | 22. PLEASE CORRECT THE ???SITE DATA??? ON THE ???SITE | | PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE | | PROPOSED ???FRONT (EAST SIDE)??? SETBACK TO REFLECT THE | | SAME INFORMATION DEMONSTRATED IN THE GRAPHIC/PLAN. | | [SATISFIED] | | 23. PLEASE CORRECT THE ???PARKING??? TABLE ON THE | | ???SITE PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE | | THE PROPOSED NUMBER OF PARKING SPACES IN WHOLE NUMBERS | | ACCORDING TO THE ZLDR SUBSECTION 94-485(H); TO | | IDENTIFY/INDICATE CORRECT INFORMATION FOR THE MINIMUM | | NUMBER OF REQUIRED ???STORAGE OFFICE??? PARKING SPACES | | ACCORDING TO THE ZLDR SECTION 94-486; TO | | IDENTIFY/INDICATE THE CORRECT INFORMATION FOR THE TOTAL | | MINIMUM NUMBER OF REQUIRED PARKING SPACES; AND TO | | IDENTIFY/INDICATE THE MINIMUM REQUIRED NUMBER OF | | ???H.C. (INCLUSIVE)??? PARKING SPACES ACCORDING TO THE | | ZLDR SUBSECTION 94-485(O). [PARTIALLY SATISFIED] | | 24. PLEASE CORRECT THE ???LOADING??? TABLE ON THE | | ???SITE PLAN??? SHEET NUMBER A-1 TO INDICATE THE | | MINIMUM LOADING SPACE DIMENSIONAL REQUIREMENTS | | ACCORDING TO THE ZLDR SUBSECTION 94-485(P). [SATISFIED] | | 25. IT HAS BEEN IDENTIFIED THAT THERE ARE | | INCONSISTENCIES BETWEEN THE ???SITEPLAN??? SHEET NUMBER | | A-1, ???SITE PLAN??? SHEET NUMBER C-02, AND | | ???LANDSCAPE PLAN??? SHEET NUMBER L-2.0 REGARDING THE | | SITE DATA INFORMATION, THEREFORE PLEASE REVISE, | | ACCORDINGLY. [PARTIALLY SATISFIED] | | | | ADDITIONAL REVIEW COMMENTS MUST BE ADDRESSED: | | 26. IN REFERENCE TO REQUIRED MATERIALS COMMENT F., | | PLEASE PROVIDE THE CONFIRMATION LETTER FROM FLORIDA | | PUBLIC UTILITIES. [SATISFIED] | | 27. IN REFERENCE TO PREVIOUS REVIEW COMMENT 3., PLEASE | | IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT PROPOSED | | EASEMENTS ON SHEET NUMBERS A-1, C-02, AND L-2.0. [NOT | | SATISFIED] | | 28. IN REFERENCE TO PREVIOUS REVIEW COMMENT 5., PLEASE | | IDENTIFY/INDICATE/DEMONSTRATE ALL ABOVE GROUND | | APPURTENANCES ON SHEET NUMBER A-1. [SATISFIED] | | 29. IN REFERENCE TO PREVIOUS REVIEW COMMENT 11., PLEASE | | IDENTIFY/INDICATE/DEMONSTRATE THE CURB CUTS/CONCRETE | | DRIVE ACCESSES REMOVED ALONG DIXIE HIGHWAY ON SHEET | | NUMBER A-1. [SATISFIED] | | 30. IN REFERENCE TO PREVIOUS REVIEW COMMENT 15., PLEASE | | PROVIDE EXPLANATION/CLARIFICATION ON THE DIFFERENCE | | BETWEEN THE HORIZONTAL PL AND THE VERTICAL PL PROVIDED. | | THE VERTICAL PL IDENTIFIES/INDICATES/DEMONSTRATES | | INFORMATION THAT IS NOT IN COMPLIANCE WITH THE ZLDR | | SUBSECTION 94-207(D)(8), PRIMARILY ALONG THE SOUTH | | PROPERTY LINE, THEREFORE, REVISE ACCORDINGLY. | | [SATISFIED] | | 31. IN REFERENCE TO PREVIOUS REVIEW COMMENT 16., PLEASE | | IDENTIFY/INDICATE/DEMONSTRATE THE DIMENSIONS OF THE | | PROPOSED SIGNAGE ON THE EAST AND NORTH ELEVATIONS AND | | CORRECT THE ???MAX SIGNAGE AREAS??? ON THE EAST AND | | NORTH ELEVATIONS. [PARTIALLY SATISFIED] | | 32. IN REFERENCE TO PREVIOUS REVIEW COMMENT 19., PLEASE | | IDENTIFY/INDICATE THE CORRESPONDING DATA FOR THE | | ???ALLOWED??? INFORMATION WITHIN THE EXISTING MF14 | | ZONING DISTRICT ON SHEET NUMBER A-1. [PARTIALLY | | SATISFIED] | | 33. IN REFERENCE TO PREVIOUS REVIEW COMMENT 20., PLEASE | | IDENTIFY/INDICATE THE MAXIMUM AND PROPOSED LOT COVERAGE | | BY IMPERMEABLE SURFACE ON SHEET NUMBER A-1. [SATISFIED] | | 34. IN REFERENCE TO PREVIOUS REVIEW COMMENT 21., PLEASE | | IDENTIFY/INDICATE THE MAXIMUM BUILDING HEIGHT | | ???ALLOWED??? INFORMATION FOR THE EXISTING MF14 ZONING | | DISTRICT AND ADD THE PROPOSED HEIGHT ???TO THE TOP OF | | THE PARAPET??? INFORMATION, TO REFLECT THE SAME | | INFORMATION DEMONSTRATED IN THE ELEVATIONS, ON SHEET | | NUMBER A-1. [PARTIALLY SATISFIED] | | 35. IN REFERENCE TO PREVIOUS REVIEW COMMENT 23., PLEASE | | CORRECT THE ???PARKING??? TABLE ON SHEET NUMBER A-1 TO | | IDENTIFY/INDICATE CORRECT INFORMATION FOR THE MINIMUM | | NUMBER OF REQUIRED ???STORAGE OFFICE??? PARKING SPACES | | ACCORDING TO THE ZLDR SECTION 94-486 AND TO | | IDENTIFY/INDICATE THE CORRECT INFORMATION FOR THE TOTAL | | MINIMUM NUMBER OF REQUIRED PARKING SPACES. [PARTIALLY | | SATISFIED] | | 36. IN REFERENCE TO PREVIOUS REVIEW COMMENT 25., PLEASE | | IDENTIFY/INDICATE THE IMPERVIOUS AND PERVIOUS | | INFORMATION ON SHEET NUMBER A-1, AS REFLECTED ON SHEET | | NUMBER C-02. [PARTIALLY SATISFIED] | | 37. IT HAS BEEN CONFIRMED BY THE CITY???S SENIOR | | LANDSCAPE PLANNER, RAY CARANCI, THAT THE MINIMUM | | LANDSCAPE AREA REQUIREMENT WITHIN THE GC PDD IS 15%. | | THE LANDSCAPE AREA PROPOSED EXCEEDS THAT MINIMUM | | REQUIREMENT. THEREFORE, THE WAIVER REQUEST FROM THE | | MINIMUM LANDSCAPE AREA REQUIREMENT IS NOT NEEDED. | | | | CONDITION OF APPROVAL: (IN ADDITION TO THE OTHER CITY | | STAFF REVIEWERS??? CONDITIONS OF APPROVAL) | | 1. PRIOR TO STAFF SCHEDULING THE SUBJECT CASE FOR CITY | | COMMISSION, REVISED PLANS | | IDENTIFYING/INDICATING/DEMONSTRATING CONSISTENT | | INFORMATION AND CORRECTED SITE DATA INFORMATION SHALL | | BE PROVIDED. | | | | | | | | KEVIE DEFRANC | | SENIOR PLANNER - PLANNING DIVISION | | [email protected] | | 561-822-1449 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
01-10-2023 |
|
|
Cont ID |
|
Sent By |
kdefranc |
Date |
01-10-2023 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
kdefranc |
Date |
01-10-2023 |
Time |
10:01 |
Sent To |
|
|
Notes |
2023-01-10 10:02:04 | 1/10/23 ??? FAILED | | | | | | PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN | | RESUBMITTING: | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED | | MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG | | WITH ONE (1) REDUCED COPY (11 IN X 17 IN). | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | ADDITIONAL COMMENTS. | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1) | | RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF | | 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED | | AFTER THE FIRST RESUBMITTAL. | | | | REQUIRED MATERIALS MUST BE PROVIDED: | | F. PLEASE PROVIDE CONFIRMATION LETTERS FROM PUBLIC | | UTILITIES (AT&T TELECOMMUNICATION, FLORIDA PUBLIC | | UTILITIES, AND COMCAST CABLE COMMUNICATIONS) CONFIRMING | | THAT THE PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR | | EASEMENTS OR OTHERWISE INTERFERE WITH THE PROVISIONS OF | | THEIR SERVICES. [PARTIALLY SATISFIED] | | G. PLEASE PROVIDE EVIDENCE OF THE UNIFIED CONTROL OF | | THE ENTIRE AREA. [SATISFIED] | | H. PLEASE PROVIDE THE AGREEMENTS, PROVISIONS OR | | COVENANTS WHICH GOVERN THE USE, MAINTENANCE AND | | CONTINUED PROTECTION OF THE PD AND ANY OF ITS COMMON | | AREAS OR FACILITIES. [SATISFIED SUBJECT TO THIS BE | | PROVIDED PRIOR TO BUILDING PERMIT APPLICATION] | | I. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW | | COMMENTS BELOW. [PARTIALLY SATISFIED] | | J. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT | | INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED | | MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL. | | [NOT SATISFIED] | | K. PLEASE PROVIDE COMPLETED PUBLIC NOTICE MAILER | | AFFIDAVITS WHEN MAILERS HAVE BEEN SENT OUT. [SATISFIED | | SUBJECT TO THESE BE PROVIDED PRIOR TO THE DEADLINES FOR | | THE PLANNING BOARD AND CITY COMMISSION MEETINGS] | | L. PLEASE PROVIDE COMPLETED SIGN POSTING AFFIDAVITS | | WHEN SIGNS HAVE BEEN PUT UP. [SATISFIED SUBJECT TO | | THESE BE PROVIDED PRIOR TO THE DEADLINES FOR THE | | PLANNING BOARD AND CITY COMMISSION MEETINGS] | | | | PREVIOUS REVIEW COMMENTS MUST BE ADDRESSED: | | 1. IN ACCORDANCE WITH THE CITY???S ZONING AND LAND | | DEVELOPMENT REGULATIONS (ZLDR) SUBSECTION | | 94-207(B)(9)(A)(1), PLEASE IDENTIFY/INDICATE THE NAME | | OF THE DEVELOPER ON THE ???COVER??? SHEET NUMBER A-0 | | AND/OR ???SITE PLAN??? SHEET NUMBER A-1. [SATISFIED] | | 2. THE PROPOSAL DEMONSTRATED IS NOT IN COMPLIANCE WITH | | THE (VISIBILITY TRIANGLE AT INTERSECTIONS REQUIREMENT) | | ZLDR SUBSECTION 94-207(B)(6), THEREFORE, PLEASE REVISE | | THE DIFFERENT PLANS, ELEVATIONS, AND SECTION, | | ACCORDINGLY. [SATISFIED] | | 3. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING | | AND PROPOSED EASEMENTS ON THE DIFFERENT PLANS. | | [PARTIALLY SATISFIED] | | 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING | | AND PROPOSED FIRE HYDRANTS (OR OPERATIONAL EQUIVALENTS) | | WITHIN 250 FEET OF THE PROPOSED STRUCTURE(S) ON THE | | ???SITE PLAN??? SHEET NUMBER A-1. [SATISFIED] | | 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF | | ANY SPECIAL UTILITY STRUCTURES SUCH AS VALVES, METERS, | | BACKFLOW CONNECTIONS, PUMP STATIONS, TRANSFORMERS, AND | | ALL ABOVE GROUND APPURTENANCES ON THE ???SITE PLAN??? | | SHEET NUMBER A-1. [PARTIALLY SATISFIED] | | 6. THE PROPOSED LOADING SPACES ARE NOT IN COMPLIANCE | | WITH THE MINIMUM LOADING SPACE DIMENSIONAL REQUIREMENTS | | OF THE ZLDR SUBSECTION 94-485(P), THEREFORE PLEASE | | REVISE THE DIFFERENT PLANS, ACCORDINGLY. [NOT SATISFIED | | - HOWEVER, WAIVER REQUEST ACKNOWLEDGED] | | 7. PLEASE FURTHER EXPLAIN/CLARIFY/CONFIRM WHETHER THE | | PROPOSED LOADING SPACES ARE FOR THE PROPOSED | | SELF-STORAGE USE OR FOR ALL THE PROPOSED USES. | | [RESPONSE PROVIDED] | | 8. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-485(Q), | | PLEASE IDENTIFY/INDICATE THE REQUIRED AND PROPOSED | | NUMBER OF BICYCLE PARKING SPACES IN THE ???PARKING??? | | TABLE ON THE ???SITE PLAN??? SHEET NUMBER A-1. [NOT | | SATISFIED] | | 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING | | BIKE LANE (TO REMAIN) ALONG LA KIRKSEY/15TH STREET ON | | THE ???BOUNDARY SURVEY??? AND ???SITE PLAN??? SHEET | | NUMBER A-1. [SATISFIED] | | 10. IN ACCORDANCE WITH THE ZLDR SUBSECTION | | 94-207(B)(9)(A)(7), PLEASE | | IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF PROPOSED | | MASS TRANSIT FACILITIES ON THE ???SITE PLAN??? SHEET | | NUMBER A-1. [RESPONSE PROVIDED] | | 11. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE CURB | | CUTS/CONCRETE DRIVE ACCESSES REMOVED ALONG DIXIE | | HIGHWAY ON THE DIFFERENT PLANS, ACCORDINGLY, SIMILAR TO | | THE INFORMATION DISPLAYED ON THE ???SITE PLAN??? SHEET | | NUMBER C-02, ???DEMOLITION PLAN??? SHEET NUMBER C-03, | | AND ???PAVING, GRADING, AND DRAINAGE PLANS??? SHEET | | NUMBER C-04. [NOT SATISFIED] | | 12. PLEASE DEMONSTRATE HOW THE CITY???S SANITATION | | SERVICE TRUCKS WILL ACCESS/COLLECT THE TRASH FROM THE | | PROPOSED TRASH AREA TO THE SOUTH ON THE ???AUTOTURN | | EXHIBIT??? SHEET NUMBER C-07. [SATISFIED] | | 13. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-443, | | PLEASE REVISE THE DIFFERENT PLANS AND ELEVATIONS, | | ACCORDINGLY, TO IDENTIFY/INDICATE/DEMONSTRATE THE | | REQUIRED PROTECTIVE SCREEN WALL ALONG THE WEST PROPERTY | | LINE ADJACENT TO THE RESIDENTIAL PROPERTY/RESIDENTIAL | | ZONING DISTRICT. [SATISFIED] | | 14. IT HAS BEEN IDENTIFIED THAT THERE ARE | | INCONSISTENCIES BETWEEN THE PLANS AND ELEVATIONS | | REGARDING THE PROPOSED FIVE-FOOT-HIGH SECURITY/ALUMINUM | | FENCE, THEREFORE PLEASE REVISE, ACCORDINGLY. | | [SATISFIED] | | 15. PLEASE PROVIDE AN | | ILLUMINATION/LIGHTING/PHOTOMETRICS PLAN DEMONSTRATING | | COMPLIANCE WITH THE ZLDR SUBSECTION 94-207(D)(8). | | [PARTIALLY SATISFIED] | | 16. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-409, | | PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE PROPOSED | | BUILDING FA??ADE SIZE, PERCENT SIGNAGE PERMITTED, AND | | PERMITTED SIGN SIZE FOR THE PROPOSED WALL MOUNTED SIGNS | | ON THE ???COLOR ELEVATIONS??? SHEET NUMBERS A-3 TO A-4. | | [PARTIALLY SATISFIED] | | 17. THE PROPOSED ???WEST ELEVATION??? WALL MOUNTED SIGN | | IS NOT IN COMPLIANCE WITH THE ZLDR SUBSECTION | | 94-402(B)(2)(7), THEREFORE PLEASE REVISE THE ???COLOR | | ELEVATION??? SHEET NUMBER A-4, ACCORDINGLY. [SATISFIED] | | 18. PLEASE PROVIDE THE STANDARD CITY DETAILS OF | | VEHICLE/BICYCLE PARKING (STANDARD, COMPACT, ADA), | | LOADING, ADA RAMPS, DRIVEWAYS, DUMPSTERS AND SIGNS. | | [SATISFIED] | | 19. PLEASE UPDATE THE ???SITE DATA??? ON THE ???SITE | | PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE | | CORRESPONDING DATA FOR THE ???ALLOWED??? INFORMATION | | WITHIN THE EXISTING MF14 AND GC ZONING DISTRICTS. | | [PARTIALLY SATISFIED] | | 20. PLEASE UPDATE THE ???SITE DATA??? ON THE ???SITE | | PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE | | MAXIMUM AND PROPOSED LOT COVERAGE BY BUILDINGS AND | | IMPERMEABLE SURFACE ACCORDING TO THE ZLDR SECTIONS | | 94-241 AND 94-243. [PARTIALLY SATISFIED] | | 21. PLEASE CORRECT THE ???SITE DATA??? ON THE ???SITE | | PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE | | MAXIMUM BUILDING HEIGHTS (???ALLOWED???) INFORMATION | | ACCORDING TO THE ZLDR SUBSECTIONS 94-241 AND 94-243 FOR | | THE EXISTING MF14 AND GC ZONING DISTRICTS AND ADD THE | | PROPOSED HEIGHT ???TO THE TOP OF THE PARAPET??? | | INFORMATION TO REFLECT THE SAME INFORMATION | | DEMONSTRATED IN THE ELEVATIONS. [PARTIALLY SATISFIED] | | 22. PLEASE CORRECT THE ???SITE DATA??? ON THE ???SITE | | PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE | | PROPOSED ???FRONT (EAST SIDE)??? SETBACK TO REFLECT THE | | SAME INFORMATION DEMONSTRATED IN THE GRAPHIC/PLAN. | | [SATISFIED] | | 23. PLEASE CORRECT THE ???PARKING??? TABLE ON THE | | ???SITE PLAN??? SHEET NUMBER A-1 TO IDENTIFY/INDICATE | | THE PROPOSED NUMBER OF PARKING SPACES IN WHOLE NUMBERS | | ACCORDING TO THE ZLDR SUBSECTION 94-485(H); TO | | IDENTIFY/INDICATE CORRECT INFORMATION FOR THE MINIMUM | | NUMBER OF REQUIRED ???STORAGE OFFICE??? PARKING SPACES | | ACCORDING TO THE ZLDR SECTION 94-486; TO | | IDENTIFY/INDICATE THE CORRECT INFORMATION FOR THE TOTAL | | MINIMUM NUMBER OF REQUIRED PARKING SPACES; AND TO | | IDENTIFY/INDICATE THE MINIMUM REQUIRED NUMBER OF | | ???H.C. (INCLUSIVE)??? PARKING SPACES ACCORDING TO THE | | ZLDR SUBSECTION 94-485(O). [PARTIALLY SATISFIED] | | 24. PLEASE CORRECT THE ???LOADING??? TABLE ON THE | | ???SITE PLAN??? SHEET NUMBER A-1 TO INDICATE THE | | MINIMUM LOADING SPACE DIMENSIONAL REQUIREMENTS | | ACCORDING TO THE ZLDR SUBSECTION 94-485(P). [SATISFIED] | | 25. IT HAS BEEN IDENTIFIED THAT THERE ARE | | INCONSISTENCIES BETWEEN THE ???SITEPLAN??? SHEET NUMBER | | A-1, ???SITE PLAN??? SHEET NUMBER C-02, AND | | ???LANDSCAPE PLAN??? SHEET NUMBER L-2.0 REGARDING THE | | SITE DATA INFORMATION, THEREFORE PLEASE REVISE, | | ACCORDINGLY. [PARTIALLY SATISFIED] | | | | ADDITIONAL REVIEW COMMENTS MUST BE ADDRESSED: | | 26. IN REFERENCE TO REQUIRED MATERIALS COMMENT F., | | PLEASE PROVIDE THE CONFIRMATION LETTER FROM FLORIDA | | PUBLIC UTILITIES. | | 27. IN REFERENCE TO PREVIOUS REVIEW COMMENT 3., PLEASE | | IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT PROPOSED | | EASEMENTS ON SHEET NUMBERS A-1, C-02, AND L-2.0. | | 28. IN REFERENCE TO PREVIOUS REVIEW COMMENT 5., PLEASE | | IDENTIFY/INDICATE/DEMONSTRATE ALL ABOVE GROUND | | APPURTENANCES ON SHEET NUMBER A-1. | | 29. IN REFERENCE TO PREVIOUS REVIEW COMMENT 11., PLEASE | | IDENTIFY/INDICATE/DEMONSTRATE THE CURB CUTS/CONCRETE | | DRIVE ACCESSES REMOVED ALONG DIXIE HIGHWAY ON SHEET | | NUMBER A-1. | | 30. IN REFERENCE TO PREVIOUS REVIEW COMMENT 15., PLEASE | | PROVIDE EXPLANATION/CLARIFICATION ON THE DIFFERENCE | | BETWEEN THE HORIZONTAL PL AND THE VERTICAL PL PROVIDED. | | THE VERTICAL PL IDENTIFIES/INDICATES/DEMONSTRATES | | INFORMATION THAT IS NOT IN COMPLIANCE WITH THE ZLDR | | SUBSECTION 94-207(D)(8), PRIMARILY ALONG THE SOUTH | | PROPERTY LINE, THEREFORE, REVISE ACCORDINGLY. | | 31. IN REFERENCE TO PREVIOUS REVIEW COMMENT 16., PLEASE | | IDENTIFY/INDICATE/DEMONSTRATE THE DIMENSIONS OF THE | | PROPOSED SIGNAGE ON THE EAST AND NORTH ELEVATIONS AND | | CORRECT THE ???MAX SIGNAGE AREAS??? ON THE EAST AND | | NORTH ELEVATIONS. | | 32. IN REFERENCE TO PREVIOUS REVIEW COMMENT 19., PLEASE | | IDENTIFY/INDICATE THE CORRESPONDING DATA FOR THE | | ???ALLOWED??? INFORMATION WITHIN THE EXISTING MF14 | | ZONING DISTRICT ON SHEET NUMBER A-1. | | 33. IN REFERENCE TO PREVIOUS REVIEW COMMENT 20., PLEASE | | IDENTIFY/INDICATE THE MAXIMUM AND PROPOSED LOT COVERAGE | | BY IMPERMEABLE SURFACE ON SHEET NUMBER A-1. | | 34. IN REFERENCE TO PREVIOUS REVIEW COMMENT 21., PLEASE | | IDENTIFY/INDICATE THE MAXIMUM BUILDING HEIGHT | | ???ALLOWED??? INFORMATION FOR THE EXISTING MF14 ZONING | | DISTRICT AND ADD THE PROPOSED HEIGHT ???TO THE TOP OF | | THE PARAPET??? INFORMATION, TO REFLECT THE SAME | | INFORMATION DEMONSTRATED IN THE ELEVATIONS, ON SHEET | | NUMBER A-1. | | 35. IN REFERENCE TO PREVIOUS REVIEW COMMENT 23., PLEASE | | CORRECT THE ???PARKING??? TABLE ON SHEET NUMBER A-1 TO | | IDENTIFY/INDICATE CORRECT INFORMATION FOR THE MINIMUM | | NUMBER OF REQUIRED ???STORAGE OFFICE??? PARKING SPACES | | ACCORDING TO THE ZLDR SECTION 94-486 AND TO | | IDENTIFY/INDICATE THE CORRECT INFORMATION FOR THE TOTAL | | MINIMUM NUMBER OF REQUIRED PARKING SPACES. | | 36. IN REFERENCE TO PREVIOUS REVIEW COMMENT 25., PLEASE | | IDENTIFY/INDICATE THE IMPERVIOUS AND PERVIOUS | | INFORMATION ON SHEET NUMBER A-1, AS REFLECTED ON SHEET | | NUMBER C-02. | | | | | | | | KEVIE DEFRANC | | SENIOR PLANNER - PLANNING DIVISION | | [email protected] | | 561-822-1449 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
09-06-2022 |
|
|
Cont ID |
|
Sent By |
kdefranc |
Date |
09-06-2022 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
kdefranc |
Date |
09-06-2022 |
Time |
15:28 |
Sent To |
|
|
Notes |
2022-09-06 15:29:29 | 9/6/22 ? FAILED | | | | | | PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN | | RESUBMITTING: | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED | | MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG | | WITH ONE (1) REDUCED COPY (11 IN X 17 IN). | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | ADDITIONAL COMMENTS. | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1) | | RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF | | 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED | | AFTER THE FIRST RESUBMITTAL. | | | | REQUIRED MATERIALS MUST BE PROVIDED: | | F. PLEASE PROVIDE CONFIRMATION LETTERS FROM PUBLIC | | UTILITIES (AT&T TELECOMMUNICATION, FLORIDA PUBLIC | | UTILITIES, AND COMCAST CABLE COMMUNICATIONS) CONFIRMING | | THAT THE PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR | | EASEMENTS OR OTHERWISE INTERFERE WITH THE PROVISIONS OF | | THEIR SERVICES. | | G. PLEASE PROVIDE EVIDENCE OF THE UNIFIED CONTROL OF | | THE ENTIRE AREA. | | H. PLEASE PROVIDE THE AGREEMENTS, PROVISIONS OR | | COVENANTS WHICH GOVERN THE USE, MAINTENANCE AND | | CONTINUED PROTECTION OF THE PD AND ANY OF ITS COMMON | | AREAS OR FACILITIES. | | I. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW | | COMMENTS BELOW. | | J. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT | | INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED | | MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL. | | K. PLEASE PROVIDE COMPLETED PUBLIC NOTICE MAILER | | AFFIDAVITS WHEN MAILERS HAVE BEEN SENT OUT. | | L. PLEASE PROVIDE COMPLETED SIGN POSTING AFFIDAVITS | | WHEN SIGNS HAVE BEEN PUT UP. | | | | REVIEW COMMENTS MUST BE ADDRESSED: | | 1. IN ACCORDANCE WITH THE CITY?S ZONING AND LAND | | DEVELOPMENT REGULATIONS (ZLDR) SUBSECTION | | 94-207(B)(9)(A)(1), PLEASE IDENTIFY/INDICATE THE NAME | | OF THE DEVELOPER ON THE ?COVER? SHEET NUMBER A-0 AND/OR | | ?SITE PLAN? SHEET NUMBER A-1. | | 2. THE PROPOSAL DEMONSTRATED IS NOT IN COMPLIANCE WITH | | THE (VISIBILITY TRIANGLE AT INTERSECTIONS REQUIREMENT) | | ZLDR SUBSECTION 94-207(B)(6), THEREFORE, PLEASE REVISE | | THE DIFFERENT PLANS, ELEVATIONS, AND SECTION, | | ACCORDINGLY. | | 3. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING | | AND PROPOSED EASEMENTS ON THE DIFFERENT PLANS. | | 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING | | AND PROPOSED FIRE HYDRANTS (OR OPERATIONAL EQUIVALENTS) | | WITHIN 250 FEET OF THE PROPOSED STRUCTURE(S) ON THE | | ?SITE PLAN? SHEET NUMBER A-1. | | 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF | | ANY SPECIAL UTILITY STRUCTURES SUCH AS VALVES, METERS, | | BACKFLOW CONNECTIONS, PUMP STATIONS, TRANSFORMERS, AND | | ALL ABOVE GROUND APPURTENANCES ON THE ?SITE PLAN? SHEET | | NUMBER A-1. | | 6. THE PROPOSED LOADING SPACES ARE NOT IN COMPLIANCE | | WITH THE MINIMUM LOADING SPACE DIMENSIONAL REQUIREMENTS | | OF THE ZLDR SUBSECTION 94-485(P), THEREFORE PLEASE | | REVISE THE DIFFERENT PLANS, ACCORDINGLY. | | 7. PLEASE FURTHER EXPLAIN/CLARIFY/CONFIRM WHETHER THE | | PROPOSED LOADING SPACES ARE FOR THE PROPOSED | | SELF-STORAGE USE OR FOR ALL THE PROPOSED USES. | | 8. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-485(Q), | | PLEASE IDENTIFY/INDICATE THE REQUIRED AND PROPOSED | | NUMBER OF BICYCLE PARKING SPACES IN THE ?PARKING? TABLE | | ON THE ?SITE PLAN? SHEET NUMBER A-1. | | 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE EXISTING | | BIKE LANE (TO REMAIN) ALONG LA KIRKSEY/15TH STREET ON | | THE ?BOUNDARY SURVEY? AND ?SITE PLAN? SHEET NUMBER A-1. | | 10. IN ACCORDANCE WITH THE ZLDR SUBSECTION | | 94-207(B)(9)(A)(7), PLEASE | | IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF PROPOSED | | MASS TRANSIT FACILITIES ON THE ?SITE PLAN? SHEET NUMBER | | A-1. | | 11. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE CURB | | CUTS/CONCRETE DRIVE ACCESSES REMOVED ALONG DIXIE | | HIGHWAY ON THE DIFFERENT PLANS, ACCORDINGLY, SIMILAR TO | | THE INFORMATION DISPLAYED ON THE ?SITE PLAN? SHEET | | NUMBER C-02, ?DEMOLITION PLAN? SHEET NUMBER C-03, AND | | ?PAVING, GRADING, AND DRAINAGE PLANS? SHEET NUMBER | | C-04. | | 12. PLEASE DEMONSTRATE HOW THE CITY?S SANITATION | | SERVICE TRUCKS WILL ACCESS/COLLECT THE TRASH FROM THE | | PROPOSED TRASH AREA TO THE SOUTH ON THE ?AUTOTURN | | EXHIBIT? SHEET NUMBER C-07. | | 13. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-443, | | PLEASE REVISE THE DIFFERENT PLANS AND ELEVATIONS, | | ACCORDINGLY, TO IDENTIFY/INDICATE/DEMONSTRATE THE | | REQUIRED PROTECTIVE SCREEN WALL ALONG THE WEST PROPERTY | | LINE ADJACENT TO THE RESIDENTIAL PROPERTY/RESIDENTIAL | | ZONING DISTRICT. | | 14. IT HAS BEEN IDENTIFIED THAT THERE ARE | | INCONSISTENCIES BETWEEN THE PLANS AND ELEVATIONS | | REGARDING THE PROPOSED FIVE-FOOT-HIGH SECURITY/ALUMINUM | | FENCE, THEREFORE PLEASE REVISE, ACCORDINGLY. | | 15. PLEASE PROVIDE AN | | ILLUMINATION/LIGHTING/PHOTOMETRICS PLAN DEMONSTRATING | | COMPLIANCE WITH THE ZLDR SUBSECTION 94-207(D)(8). | | 16. IN ACCORDANCE WITH THE ZLDR SUBSECTION 94-409, | | PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE PROPOSED | | BUILDING FA?ADE SIZE, PERCENT SIGNAGE PERMITTED, AND | | PERMITTED SIGN SIZE FOR THE PROPOSED WALL MOUNTED SIGNS | | ON THE ?COLOR ELEVATIONS? SHEET NUMBERS A-3 TO A-4. | | 17. THE PROPOSED ?WEST ELEVATION? WALL MOUNTED SIGN IS | | NOT IN COMPLIANCE WITH THE ZLDR SUBSECTION | | 94-402(B)(2)(7), THEREFORE PLEASE REVISE THE ?COLOR | | ELEVATION? SHEET NUMBER A-4, ACCORDINGLY. | | 18. PLEASE PROVIDE THE STANDARD CITY DETAILS OF | | VEHICLE/BICYCLE PARKING (STANDARD, COMPACT, ADA), | | LOADING, ADA RAMPS, DRIVEWAYS, DUMPSTERS AND SIGNS. | | 19. PLEASE UPDATE THE ?SITE DATA? ON THE ?SITE PLAN? | | SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE CORRESPONDING | | DATA FOR THE ?ALLOWED? INFORMATION WITHIN THE EXISTING | | MF14 AND GC ZONING DISTRICTS. | | 20. PLEASE UPDATE THE ?SITE DATA? ON THE ?SITE PLAN? | | SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE MAXIMUM AND | | PROPOSED LOT COVERAGE BY BUILDINGS AND IMPERMEABLE | | SURFACE ACCORDING TO THE ZLDR SECTIONS 94-241 AND | | 94-243. | | 21. PLEASE CORRECT THE ?SITE DATA? ON THE ?SITE PLAN? | | SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE MAXIMUM | | BUILDING HEIGHTS (?ALLOWED?) INFORMATION ACCORDING TO | | THE ZLDR SUBSECTIONS 94-241 AND 94-243 FOR THE EXISTING | | MF14 AND GC ZONING DISTRICTS AND ADD THE PROPOSED | | HEIGHT ?TO THE TOP OF THE PARAPET? INFORMATION TO | | REFLECT THE SAME INFORMATION DEMONSTRATED IN THE | | ELEVATIONS. | | 22. PLEASE CORRECT THE ?SITE DATA? ON THE ?SITE PLAN? | | SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE PROPOSED | | ?FRONT (EAST SIDE)? SETBACK TO REFLECT THE SAME | | INFORMATION DEMONSTRATED IN THE GRAPHIC/PLAN. | | 23. PLEASE CORRECT THE ?PARKING? TABLE ON THE ?SITE | | PLAN? SHEET NUMBER A-1 TO IDENTIFY/INDICATE THE | | PROPOSED NUMBER OF PARKING SPACES IN WHOLE NUMBERS | | ACCORDING TO THE ZLDR SUBSECTION 94-485(H); TO | | IDENTIFY/INDICATE CORRECT INFORMATION FOR THE MINIMUM | | NUMBER OF REQUIRED ?STORAGE OFFICE? PARKING SPACES | | ACCORDING TO THE ZLDR SECTION 94-486; TO | | IDENTIFY/INDICATE THE CORRECT INFORMATION FOR THE TOTAL | | MINIMUM NUMBER OF REQUIRED PARKING SPACES; AND TO | | IDENTIFY/INDICATE THE MINIMUM REQUIRED NUMBER OF ?H.C. | | (INCLUSIVE)? PARKING SPACES ACCORDING TO THE ZLDR | | SUBSECTION 94-485(O). | | 24. PLEASE CORRECT THE ?LOADING? TABLE ON THE ?SITE | | PLAN? SHEET NUMBER A-1 TO INDICATE THE MINIMUM LOADING | | SPACE DIMENSIONAL REQUIREMENTS ACCORDING TO THE ZLDR | | SUBSECTION 94-485(P). | | 25. IT HAS BEEN IDENTIFIED THAT THERE ARE | | INCONSISTENCIES BETWEEN THE ?SITEPLAN? SHEET NUMBER | | A-1, ?SITE PLAN? SHEET NUMBER C-02, AND ?LANDSCAPE | | PLAN? SHEET NUMBER L-2.0 REGARDING THE SITE DATA | | INFORMATION, THEREFORE PLEASE REVISE, ACCORDINGLY. | | | | | | KEVIE DEFRANC | | PLANNER - PLANNING DIVISION | | [email protected] | | 561-822-1449 | | |
|
|
|
Print |
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |