Plan Review Details - Project Z20110013
Plan Review Stops For Project Z20110013
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 12-09-2020 Cont ID  
Sent By llouie Date 12-09-2020 Time 21:31 Rev Time 0.00
Received By rbrown Date 12-09-2020 Time 21:31 Sent To  
Notes
2020-12-09 21:39:40DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE
 RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD
 ZONE AE, WITH A BASE FLOOD ELEVATION OF 12.7 FT NAVD.
 THE FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED
 MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL
 BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD
 ELEVATION. THE PROPOSED FINISHED FLOOR ELEVATION OF
 20.25 NAVD IS NOTED, AND WILL MEET THE REQUIREMENT.
  
 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 4. GREASE/OIL INTERCEPTOR. A GREASE/OIL INTERCEPTOR
 WILL BE REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE,
 SIZE AND LOCATION, PLEASE CONTACT TIM LARGE, CHIEF
 PLUMBING INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT
 (561) 805-6692, OR BY EMAIL: [email protected]
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 6. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 7. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 8. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 12-30-2020 Cont ID  
Sent By rrossano Date 12-30-2020 Time   Rev Time 0.00
Received By rrossano Date 12-30-2018 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 12-03-2020 Cont ID  
Sent By rrossano Date 12-03-2020 Time   Rev Time  
Received By rrossano Date 12-03-2020 Time   Sent To  
Notes
2020-12-03 10:22:351. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 2. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 3. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 4. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
 5. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
 -LETTER OF AVAILABILITY STATES THAT WATER AND
 WASTEWATER SERVICE SHOULD BE FROM PALM BEACH COUNTY
 UTILITIES. PLEASE USE COUNTY?S STANDARD DETAILS FOR
 WATER AND SEWER INSTEAD OF CITY?S.
  
 THANKS,
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL
 33401
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 12-02-2020 Cont ID  
Sent By pleduc Date 12-02-2020 Time 16:22 Rev Time 0.00
Received By pleduc Date 12-02-2020 Time 14:58 Sent To  
Notes
2020-12-02 16:21:21THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT
 ADEQUATE WATER SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 9. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 10. IT IS RECOMMENDED, NOT REQUIRED, THAT A KNOX BOX
 WITH KEYS FOR ENTRY DOOR LOCKS BE PROVIDED FOR FIRE
 DEPARTMENT 24 HOUR EMERGENCY ACCESS.
  
 11. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 12. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 01-27-2021 Cont ID  
Sent By rcaranci Date 01-27-2021 Time 14:27 Rev Time 0.00
Received By rcaranci Date 01-27-2021 Time 14:27 Sent To  
Notes
2021-01-27 14:27:44FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: PALMS GATEWAY PD LOT 2 CAR WASH Z20110013
 JANUARY 19, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. INCLUDE ALL CALCULATIONS FOR THE NORTH
 BUFFER PORTION ON THE LANDSCAPE REQUIREMENT CHART.
  
 2. SATISFIED. INCLUDE ANY EXISTING TREES OR LANDSCAPE
 ON THE PLANT LIST IDENTIFYING THE SPECIES AND SHOW AS
 EXISTING. THIS INCLUDES THE NORTH BUFFER. ALL MATERIAL
 WITHIN THE PROPERTY LINE MUST BE INCLUDED.
  
 EXISTING TREES AND SHRUBS WITHIN THE PROPERTY LINE NEED
 TO BE INTEGRATED INTO THE PLANT SCHEDULE ON SHEET L-2.1
 AND LABELED AS EXISTING ON SITE.
 REMOVE ALL LISTING OF PLANT MATERIAL OUTSIDE THE
 PROPERTY LINE FROM THE LANDSCAPE PLAN. THE WEST AND
 SOUTH BUFFERS ARE NOT REQUIRED PER THE APPROVED PD
 WAIVER FOR INTERNAL PROPERTY LINE BUFFERS.
  
 3. SATISFIED. PROVIDE EXPLANATION FOR TAKING POINTS FOR
 EXTRA TREES IN PARKING AREA. STAFF DOES NOT FIND THE
 ADDITIONAL TREES ADJACENT TO PARKING SPACES. UPDATE THE
 FLORIDA FRIENDLY LANDSCAPE CHART. USE ANY NATIVE TREES
 TO GAIN POINTS.
 ADDITIONAL COMMENT 12/30/20:
 4. SATISFIED. REMOVE REFERENCES TO PB COUNTY CODE AND
 ALL CALIPER AND CANOPY REFERENCES FROM THE EXISTING
 TREE DISPOSITION CHART ON SHEET L-1.01. ALSO CHANGE
 STREET TREE IN THE COMMENTS COLUMN TO BUFFER TREE FOR
 TREES 2 THROUGH 7. TREE #1 IS OFF SITE SO SHOULD BE
 LABELED AS SUCH.
  
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 12-31-2020 Cont ID  
Sent By rcaranci Date 12-31-2020 Time 09:20 Rev Time 0.00
Received By rcaranci Date 12-31-2020 Time 09:20 Sent To  
Notes
2020-12-31 09:21:08FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: PALMS GATEWAY PD LOT 2 CAR WASH Z20110013
 DECEMBER 30, 2020
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. INCLUDE ALL CALCULATIONS FOR THE NORTH
 BUFFER PORTION ON THE LANDSCAPE REQUIREMENT CHART.
  
 2. PARTIALLY SATISFIED. INCLUDE ANY EXISTING TREES OR
 LANDSCAPE ON THE PLANT LIST IDENTIFYING THE SPECIES AND
 SHOW AS EXISTING. THIS INCLUDES THE NORTH BUFFER. ALL
 MATERIAL WITHIN THE PROPERTY LINE MUST BE INCLUDED.
  
 EXISTING TREES AND SHRUBS WITHIN THE PROPERTY LINE NEED
 TO BE INTEGRATED INTO THE PLANT SCHEDULE ON SHEET L-2.1
 AND LABELED AS EXISTING ON SITE.
 REMOVE ALL LISTING OF PLANT MATERIAL OUTSIDE THE
 PROPERTY LINE FROM THE LANDSCAPE PLAN. THE WEST AND
 SOUTH BUFFERS ARE NOT REQUIRED PER THE APPROVED PD
 WAIVER FOR INTERNAL PROPERTY LINE BUFFERS.
  
 3. SATISFIED. PROVIDE EXPLANATION FOR TAKING POINTS FOR
 EXTRA TREES IN PARKING AREA. STAFF DOES NOT FIND THE
 ADDITIONAL TREES ADJACENT TO PARKING SPACES. UPDATE THE
 FLORIDA FRIENDLY LANDSCAPE CHART. USE ANY NATIVE TREES
 TO GAIN POINTS.
 ADDITIONAL COMMENT 12/30/20:
 4. REMOVE REFERENCES TO PB COUNTY CODE AND ALL CALIPER
 AND CANOPY REFERENCES FROM THE EXISTING TREE
 DISPOSITION CHART ON SHEET L-1.01. ALSO CHANGE STREET
 TREE IN THE COMMENTS COLUMN TO BUFFER TREE FOR TREES 2
 THROUGH 7. TREE #1 IS OFF SITE SO SHOULD BE LABELED AS
 SUCH.
  
  
 CONDITIONS OF APPROVAL:
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 12-08-2020 Cont ID  
Sent By rcaranci Date 12-08-2020 Time 17:23 Rev Time 0.00
Received By rcaranci Date 12-08-2020 Time 17:23 Sent To  
Notes
2020-12-08 17:23:27FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: PALMS GATEWAY PD LOT 2 CAR WASH Z20110013
 DECEMBER 8, 2020
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. INCLUDE ALL CALCULATIONS FOR THE NORTH BUFFER
 PORTION ON THE LANDSCAPE REQUIREMENT CHART.
  
 2. INCLUDE ANY EXISTING TREES OR LANDSCAPE ON THE PLANT
 LIST IDENTIFYING THE SPECIES AND SHOW AS EXISTING. THIS
 INCLUDES THE NORTH BUFFER. ALL MATERIAL WITHIN THE
 PROPERTY LINE MUST BE INCLUDED.
  
 3. PROVIDE EXPLANATION FOR TAKING POINTS FOR EXTRA
 TREES IN PARKING AREA. STAFF DOES NOT FIND THE
 ADDITIONAL TREES ADJACENT TO PARKING SPACES. UPDATE THE
 FLORIDA FRIENDLY LANDSCAPE CHART. USE ANY NATIVE TREES
 TO GAIN POINTS.
  
  
 CONDITIONS OF APPROVAL:
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 01-05-2021 Cont ID  
Sent By   Date 01-05-2021 Time   Rev Time 0.00
Received By   Date 01-05-2021 Time   Sent To  
Notes
2021-01-05 09:16:58NO FURTHER COMMENTS FROM PUBLIC WORKS.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 12-21-2020 Cont ID  
Sent By   Date 12-21-2020 Time   Rev Time  
Received By   Date 12-21-2020 Time   Sent To  
Notes
2020-12-21 08:50:37PLEASE PROVIDE:
 1- REVISED SHEET A1.2 TO REFELCT DUMPSTER ENCDOSRE SPEC
 THAT COMPLIES WITH OUR LATEST SPECIFICATION. FOR A
 FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE
 SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST
 PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE
 STANDARD, GC-7.
 2- AUTO TURN (DYNAMIC ENVELOPE AND THE TIRES PATH) FOR
 THE SANITATION SERVICE, FRONT LOADER TRUCK WITH THE
 FOLLOWING SPECS:
 - TRUCK LENGTH: 35 FT
 - TRUCK WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop STORM STORMWATER
Rev No 3 Status P Date 01-15-2021 Cont ID  
Sent By tward Date 01-15-2021 Time 09:15 Rev Time 0.00
Received By tward Date 01-15-2021 Time 09:15 Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status F Date 01-06-2021 Cont ID  
Sent By tward Date 01-05-2021 Time 16:57 Rev Time 0.00
Received By tward Date 01-06-2021 Time 07:55 Sent To  
Notes
2021-01-06 07:53:11THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 12/29/2020 SUBMITTAL PACKAGE AND ARE CONDITIONS FOR
 SITE PLAN APPROVAL.
  
 1. WHAT IS THE PURPOSE OF THE TRENCH DRAIN ON THE EAST
 SIDE OF THE BUILDING. THE PAVEMENT SLOPES AWAY FROM THE
 BUILDING.
  
 2. HOW WAS THE FINISHED FLOOR ELEVATION OF 20.25 NAVD
 DETERMINED? IT APPEARS IF THE FFE ELEVATION IS LOWERED,
 THE PAVEMENT SLOPES CAN BE FLATTENED. THE LONGITUDINAL
 SLOPE AT THE CAR WASH EXIT IS 6%, AND THE CROSS SLOPE
 ALONG THE WEST EDGE IS OVER 4%.
  
 3. ADD A CATCH BASIN NEAR THE DUMPSTER TO CAPTURE MORE
 ONSITE STORMWATER RUNOFF.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)

Review Stop STORM STORMWATER
Rev No 1 Status F Date 12-10-2020 Cont ID  
Sent By tward Date 12-10-2020 Time 13:20 Rev Time 0.00
Received By tward Date 12-10-2020 Time 13:22 Sent To  
Notes
2020-12-10 13:21:48THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. DRAINAGE SYSTEM TO BE DESIGNED PER THE MASTER ERP
 PERMIT FOR THE SITE.
  
 2. PROVIDE THE VERTICAL SEPARATION BETWEEN THE PROPOSED
 STORM PIPE AND THE EXISTING STORM PIPE IN THE DRIVE
 AISLE ALONG THE EAST SIDE OF THE SITE.
  
 3. CAR WASH WATER IS NOT TO BE INTRODUCED INTO THE
 DRAINAGE SYSTEM.
 4. SITE IS LOCATED WITHIN A SPECIAL FLOOD HAZARD AREA
 (SFHA). STRUCTURES WITHIN A SFHA ARE TO PROVIDE MINIMUM
 TWO FEET OF FREEBOARD ABOVE THE BASE FLOOD ELEVATION.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE FDEP ERP MODIFICATION AND
 DRAINAGE CALCULATIONS PRIOR TO STARTING CONSTRUCTION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 12-07-2020 Cont ID  
Sent By vnoel Date 12-07-2020 Time 08:55 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2020-12-07 08:55:35NO COMMENTS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date 01-05-2021 Cont ID  
Sent By   Date 01-05-2021 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-01-05 15:49:20ALL PRIOR COMMENTS HAVE BEEN SATISFIED. NO FURTHER
 COMMENTS.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 12-10-2020 Cont ID  
Sent By   Date 12-10-2020 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2020-12-10 12:30:48TRAFFIC COMMENTS:
 1. PROVIDE AN ESTIMATE FOR THE VACUUM STALLS OCCUPANCY
 RATE
 2. WHAT PRECLUDES VEHICLES NOT COMING FROM THE CARWASH
 TO USE THE VACUUM STATIONS?
 3. CONSIDER CHARGING FOR VACUUM STALLS OR MONITOR USAGE
 AND OCCUPANCY
 4. POTENTIAL PARKING OVERFLOW TO NEARBY PROPERTIES,
 WITH VEHICLES PARKED BY THE OPPOSITE SIDE STALLS
 WAITING TO VACUUM
 5. ARE THERE ANY PARKING AGREEMENTS WITH THE STORAGE
 FACILITY?
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 04-05-2021 Cont ID  
Sent By llouie Date 04-05-2021 Time   Rev Time 0.00
Received By llouie Date 04-05-2021 Time   Sent To  
Notes
2021-04-08 11:26:03SUBJECT TO THE OUTSTANDING CONDITIONS PROVIDED IN
 RESOLUTION NO. 57-21, APPROVED BY THE CITY COMMISION ON
 4/5/2021.
  
 RESOLUTION NO. 57-21 AND FINAL SITE PLAN APPROVAL
 LETTER ATTACHED.

Review Stop Z ZONING
Rev No 2 Status F Date 01-04-2021 Cont ID  
Sent By llouie Date 01-04-2021 Time   Rev Time 0.00
Received By llouie Date 01-04-2021 Time   Sent To  
Notes
2021-01-04 12:33:05MASTER DEVELOPMENT PLAN (SHEET MP-1):
  
 1.) THE APPROVED BUILDING (111,502 SQ. FT.) FOR THE
 SELF-STORAGE FACILITY HAS NOT BEEN CHANGED IN THE
 CONCURRENCY SUMMARY TABLE. [12/9/2020 REPEAT COMMENT:
 NOT ADDRESSED. CONCURRENCY SUMMARY STILL SHOWS 115,000
 SQ. FT. FOR THE SELF-STORAGE FACILITY. PLEASE ADDRESS
 FOR CONSISTENCY WITH THE TPS APPROVAL LETTER.]
  
  
 SITE PLAN COMMENTS:
  
 1.) PLEASE ELIMINATE ANY REPETITIVE CALCULATIONS IN THE
 SITE DATA TABULAR (CONTACT STAFF FOR CLARIFICATION).
  
 2.) THE BICYCLE PARKING CALCULATIONS INDICATE THAT 3
 BICYCLE PARKING SPACES ARE PROVIDED AND THE BICYCLE
 RACK DETAIL ON SHEET A1.2 INDICATES A "WAVE STYLE BIKE
 RACK (IN GROUND)' TO BE INSTALLED. WAVE STYLE RACKS ARE
 NOT PERMITTED PER THE CITY'S BICYCLE PARKING STANDARDS.
 IT IS RECOMMENDED THAT AN INVERTED U RACK IS INSTALLED
 FOR THE PROJECT (ACCOMMODATES A MAXIMUM OF 2 BICYCLES).
 PLEASE ADDRESS FOR CONSISTENCY WITH THE CITY'S
 STANDARDS.
  
 3.) THERE SEEMS TO BE TWO SHEET A1.2 IN THE PLAN SET.
 PLEASE CLARIFY.
  
 4.) WHY IS THERE A "SITE DETAILS 2" SHEET? IS THERE
 SUPPOSED TO BE A "SITE DETAILS 1" SHEET?
  
 5.) A DETAIL ON SHEET A1.2 SHOWS THAT THE VACUUM AREA
 "MAY" HAVE AN AWNING. A DECISION MUST BE MADE AT THIS
 POINT, AS THE DETAILS SHEET MUST BE CONSISTENT WITH THE
 SITE PLAN (I.E. SHOWN IN THE SITE PLAN OR ELIMINATE
 DETAIL ON SHEET A1.2).
  
 6.) THERE IS A NOTE ON SHEET A1.2, DUMPSTER AND VACUUM
 ENCLOSURE THAT MAKES A REFERENCE TO SHEET A3.0;
 HOWEVER, THERE IS NO SHEET A3.0 IN THE SITE PLAN SET.
 PLEASE ADDRESS FOR CONSISTENCY.
  
 7.) THE PARKING STRIPING DETAIL FOR THE EMPLOYEE
 PARKING ON SHEET A1.2 IS INCONSISTENT WITH THE PARKING
 STALL STRIPING REQUIREMENTS OF ZLDR S.94-485 (I.E.
 STRIPING DIMENSIONS DOES NOT MEET THE MINIMUM
 REQUIREMENTS). PLEASE ADDRESS FOR CONSISTENCY.
  
 8.) A STALL STRIPING AND SIGNAGE DETAIL FOR ACCESSIBLE
 PARKING IS REQUIRED ON SHEET A1.2.
  
  
 ARCHITECTURAL DRAWINGS:
  
 1.) REAR ELEVATION (SOUTH) INDICATES A SIGN AND A METAL
 SCUPPER; HOWEVER, THESE DETAILS ARE NOT SHOWN IN THE
 ARCHITECTURAL DRAWINGS ON SHEET A7.1.
  
  
 SIGNAGE COMMENTS:
  
 1.) SIGN CALCULATIONS SEEM TO BE INCORRECT AND EXCEED
 THE MAXIMUM ALLOWABLE SIGN AREA. PLEASE ADDRESS FOR
 CONSISTENCY WITH ARTICLE XIII OF THE ZLDRS.
  
 2.) PER ZLDR SEC. 94-405, THE SIGN AREA SHALL BE
 CALCULATED BY THE SMALLEST AREA WHICH CONTAINS ALL
 CONTENT, BACKGROUND, STRUCTURAL ELEMENTS OF THE SIGN.
 ACCORDING TO SHEET A7.0 AND SHEET A7.1, THE SIGN AREA
 SEEMS TO BE BROKEN INTO THREE COMPONENTS ON THE NORTH
 ELEVATION WHICH IS INCORRECT AND DOES NOT ACCOUNT FOR
 THE FLAMINGO LOGO WHICH IS PART OF THE SIGN AREA.
 ADDITIONALLY, THE SIGN AREA SEEMS TO EXCEED THE MAXIMUM
 ALLOWABLE SIGN AREA. PLEASE ADDRESS FOR CONSISTENCY.
  
  
 LANDSCAPE PLAN:
  
 1.) LANDSCAPE CALCULATIONS SEEM TO BE INCONSISTENT WITH
 THE INFORMATION PROVIDED IN THE MASTER DEVELOPMENT PLAN
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * ANY CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES, ONE (1) REDUCED COPY IN 11 INCHES X
 17 INCHES AND AN ELECTRONIC COPY OF ALL PLANS AND
 DOCUMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE
 ($600.00).
  

Review Stop Z ZONING
Rev No 1 Status F Date 12-09-2020 Cont ID  
Sent By llouie Date 12-09-2020 Time   Rev Time  
Received By llouie Date 12-09-2020 Time   Sent To  
Notes
2020-12-09 14:34:26GENERAL COMMENTS:
  
 1.) RESPONSES TO SECTION 94-35(C), SITE DESIGN
 QUALITATIVE DEVELOPMENT STANDARDS ARE MISSING FROM THE
 APPLICATION. PLEASE PROVIDE.
  
 2.) THE LOCATION MAP ON THE SURVEY IS INCORRECT. PLEASE
 ADDRESS FOR CONSISTENCY.
  
  
 MASTER DEVELOPMENT PLAN (SHEET MP-1):
  
 1.) PLEASE MAKE THE FOLLOWING CORRECTIONS TO THE MASTER
 DEVELOPMENT PLAN: A) THE LAND USE AND ZONING TO THE
 WEST IS C AND CPD (NOT CS AND CS). B) THE FOLLOWING
 USES HAVE BEEN "APPROVED" (NOT "PROPOSED"): TRACT #3:
 MOTOR VEHICLE SALES AND SERVICE AND TRACT #4
 SELF-STORAGE FACILITY. C) PLEASE CHANGE THE PROPOSED
 USE FOR TRACT #2 FROM "CAR WASH" TO "CAR WASH
 (SELF-SERVICE)" FOR ACCURACY.
  
 2.) PLEASE MAKE THE FOLLOWING CORRECTIONS TO THE MASTER
 DEVELOPMENT PLAN FOR CONSISTENCY WITH THE AS-BUILTS
 AND/OR THE TPS LETTER: A) TRACT #2: PROPOSED CAR WASH
 (SELF-SERVICE): 3,708 SQUARE FEET (NOT 3,725 SQUARE
 FEET). B) TRACT #3: NEW CAR SALES: 14,683 SQUARE FEET
 (VESTED IN TPS; NOT 14,709 SQUARE FEET). C) TRACT #4:
 SELF-STORAGE FACILITY: 111,502 SQUARE FEET (NOT 115,000
 SQUARE FEET).
  
 3.) PLEASE ADDRESS THE FOLLOWING IN THE LAND USE AND
 ZONING INFORMATION AND NOTES FOR TRACT #2 (CAR WASH
 (SELF-SERVICE): A) BUILDING HEIGHT INFORMATION IS
 INCONSISTENT WITH THE HEIGHT IN THE ARCHITECTURAL
 PLANS. PLEASE ADDRESS FOR CONSISTENCY. B) DATA PROVIDED
 FOR: IMPERVIOUS AREA, OPEN SPACE AND LANDSCAPING SEEMS
 TO BE INCONSISTENT WITH THE DATA PROVIDED IN THE SITE
 PLAN FOR THE CAR WASH. PLEASE CHECK CALCULATIONS AND
 ADDRESS FOR CONSISTENCY. C) NUMBERS PROVIDED FOR:
 IMPERVIOUS AREA, OPEN SPACE AND LANDSCAPING SEEMS TO BE
 INCONSISTENT WITH THE DATA PROVIDED IN THE MASTER PLAN
  
 4.) ADJUST THE FOLLOWING INFORMATION FOR TRACT #3: NEW
 CAR SALES FOR BUILDING AREA: UP TO 14,683 SF-GFA + 26
 SF FOR EQUIPMENT ROOM AND ASSOCIATED PARKING (TO
 CLARIFY THE 14,709 SQUARE FEET BUILDING).
  
 5.) TOTAL BUILDING SIZE FOR TRACT #3 (NEW CAR SALES)
 SHALL ALSO BE CHANGED TO REFLECT THE ABOVE (TO CLARIFY
 THE 14,709 SQUARE FEET BUILDING SIZE AND VESTED
 BUILDING IN THE TPS LETTER).
  
  
 SITE PLAN COMMENTS:
  
 1.) WHEN THE DEL TACO SITE PLAN WAS APPROVED FOR THE
 CPD, AN ADA ACCESS POINT CONNECTING THE SIDEWALK ON
 BELVEDERE ROAD TO THE INTERIOR PEDESTRIAN CONNECTION
 WITHIN THE DEVELOPMENT/RESTAURANT WAS REQUIRED BY THE
 BUILDING DEPARTMENT. THIS IS NO LONGER DEPICTED IN THE
 PROPOSED SITE PLAN FOR THE CAR WASH. THE BUILDING
 OFFICIAL SHALL DETERMINE IF AN ADA CONNECTION IS
 REQUIRED
  
 2.) THE LOCATION MAP PROVIDED ON SHEET A1.0 IS
 INCORRECT. PLEASE CORRECT FOR CONSISTENCY.
  
 3.) PLEASE ADDRESS THE FOLLOWING IN THE PROJECT DATA
 TABULAR: A) THE BUILDING HEIGHT INFORMATION IS
 INACCURATE WITH THE BUILDING HEIGHT PROVIDED IN THE
 ARCHITECTURAL DRAWINGS. PLEASE ADDRESS FOR CONSISTENCY.
  
 4.) WHERE IS THE LOADING ZONE? THE USE REQUIRES ONE 10
 FT. X 25 FT. LOADING ZONE. [ZLDR S.94-485(P)]
  
 5.) PLEASE PROVIDE MORE INFORMATION ON MANUEVERING OF
 LOADING VEHICLES TO AND FROM THE LOADING ZONE. IS THERE
 SUFFICIENT CLEARANCE FOR LOADING VEHICLES?
  
 6.) WHERE DID THE REQUIRED PARKING CALCULATIONS COME
 FROM (I.E. 3 PARKING SPACES PER 1,000 SQ. FT.)? THIS
 SEEMS TO BE INCONSISTENT WITH THE PARKING REQUIREMENTS
 OF THE CITY'S ZLDRS. PLEASE CLARIFY.
  
 7.) PLEASE CLARIFY THE NUMBER OF VACUUM SPACES. THE
 PLAN STATES THERE ARE 12 VACUUM SPACES; STAFF HAS
 COUNTED 13 SPACES.
  
 8.) PROVIDE A STALL STRIPING DETAIL THAT IS CONSISTENT
 WITH THE CONFIGURATION AND DIMENSIONS PROVIDED IN THE
 SITE PLAN. STALL PAINTING DIMENSIONS SHALL ALSO BE
 CONSISTENT WITH THE CITY'S STALL STRIPING STANDARDS.
 [ZLDR S.94-485(J)]
  
 9.) THE SITE DATA TABULAR STATES THERE ARE 5 BICYCLE
 PARKING SPACES PROVIDED; HOWEVER, STAFF CAN ONLY DETECT
 ONE RACK (= 2 BICYCLE PARKING) IN THE SITE PLAN. PLEASE
 ADDRESS.
  
 10.) PLEASE RELOCATE THE BICYCLE RACK LOCATED ON THE
 SOUTH SIDE OF THE PROPOSED CAR WASH BUILDING. THE RACK
 IS LOCATED IN THE MIDDLE OF THE PEDESTRIAN WALKWAY,
 WHICH IS NOT ACCEPTABLE.
  
 11.) DETAIL OF THE BICYCLE RACK IS MISSING FROM THE
 PLANS. PLEASE NOTE THAT THE BICYCLE RACK MUST BE
 CONSISTENT WITH THE BICYCLE PARKING DESIGN AND
 STANDARDS OF THE CITY.
  
  
 PHOTOMETRIC PLAN:
  
 1.) ANY SOURCE OF ILLUMINATION LOCATED WITHIN A
 COMMERCIAL PLANNED DEVELOPMENT DISTRICT SHALL NOT
 EXCEED ONE-FOOT CANDLE AT OR BEYOND THE BOUNDARY OF
 SUCH DEVELOPMENT. PLEASE ILLUSTRATE ILLUMINATION
 SPILLOVER AT THE BOUNDARIES OF THE CPD TO DEMONSTRATE
 COMPLIANCE. [ZLDR S.94-207(D)(8)]
  
 2.) PLEASE PROVIDE THE FOLLOWING NOT IN THE PLAN: ALL
 OUTDOOR LIGHTING SHALL BE SHIELDED TO REDUCE GLARE AND
 SHALL BE ARRANGED TO REFLECT LIGHT OR GLARE AWAY FROM
 ALL ADJACENT PUBLIC THROUGHFARES. [ZLDR S.94-309(A)]
  
  
 SIGNAGE COMMENTS:
  
 1.) IT IS NOT CLEAR IF THE PROJECT WALL SIGNAGE WILL
 COMPLY WITH THE SIGN REQUIREMENTS OF ARTICLE XIII OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS). IF
 SO, A NOTE IN THE PLANS MUST CLEARLY STATE SO. PLEASE
 NOTE THAT THE SIGNAGE IN THE ARCHITECTURAL ELEVATIONS
 IS DIFFERENT FROM THE ARCHITECTURAL RENDERINGS, AND
 STAFF HAS CONCERNS THAT THE MAXIMUM ALLOWABLE SIGN AREA
 IN THE ARCHITECTURAL RENDERINGS HAVE BEEN EXCEEDED.
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * ANY CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES, ONE (1) REDUCED COPY IN 11 INCHES X
 17 INCHES AND AN ELECTRONIC COPY OF ALL PLANS AND
 DOCUMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE
 ($600.00).
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  