Plan Review Notes For Permit 99122062 |
Permit Number |
99122062 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | 1)NOTE:PLEASE CORRECT GROUNDING | | ELECTRODE SYSTEM. NEEDS TO SHOW GROUND | | GOING TO BLDG.STEEL AND COLD WATER PIPE. | | AS REQ`D BY ARTS;250-81/215-5 FO THE NEC | | | | 2)NOTE:PLEASE GIVE COMPLETE SIZE FOR | | JUNCTION BOX TO INCLUDE DEPTH. CHECK | | ART;370 OF THE NEC FOR SIZING. | | | | 3)NOTE: PLEASE SUBMIT PANEL SCHEDULES | | FOR THE PANELS THAT ARE GOING TO HAVE | | LOADS ON THEM INCLUDING A/C`S AND RECEPT | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL. IF THERE ARE | | ANY QUESTIONS; 659-8096 EXT 8372 |
|