Date |
Text |
2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| 1-FLOOD ZONE "A0". PROVIDE ELEVATION |
| CERTIFICATE AFTER SLAB IS POURED. |
| 2-PRODUCT APPROVALS: |
| -PROVIDE PRODUCT APPROVAL FOR TWO HOUR |
| FIRE RATED CONCRETE BLOCK, EXTERIOR |
| FRENCH DOOR WITH SIDELITES ASSEMBLY, |
| EXTERIOR DOUBLE FRENCH DOOR, AND |
| WINDOW MULLIONS. |
| -DRAWINGS IN PRODUCT APPROVAL FOR THE |
| SLIDING GLASS DOORS ARE NOT LEGIBLE. |
| 3-PROVIDE BUCK DETAIL FOR SLIDING GLASS |
| DOORS. SEC. 104.2.2 CITY AMENDMENTS. |
| 4-PRODUCT APPROVAL FOR SINGLE HUNG |
| WINDOWS REQUIRES A 2X BUCK. REVISE |
| WINDOW BUCK DETAIL AS REQUIRED. |
| 5-STORM PANELS: |
| -INSTALLATION SCHEDULE AND KEY PLAN |
| DON'T MATCH ARCHITECT'S PLANS. SEE |
| SIZES OF OPENINGS. ALSO, INSTALLATION |
| SCHEDULE AND KEY PLAN TO INCLUDE ALL |
| OPTIONS SHOWN BY THE ARCHITECT. |
| -CLEARLY INDICATE ON DRAWINGS MOUNTING |
| CONDITIONS AND ANCHOR TYPE AND SPACING |
| NOTE: TAKE INTO CONSIDERATION TABLES |
| ON SHEET 4 OF 4 OF DRAWING 97-404P AND |
| BUILDING CONSTRUCTION. THE MEAN ROOF |
| HEIGHT FOR THIS BUILDING IS PLUS OR |
| MINUS AT 16'-0" AND THE BUILDING CONST |
| IS MASONRY, NOT CONCRETE. |
| 6-REVISE ENERGY CALCULATIONS: |
| -OWNER INFORMATION IS INCORRECT. |
| -LOCATION IS INCORRECT. |
| -DON'T FORGET OWNER' SIGNATURE AND DATE |
| 7-PROVIDE COMPLETE CALCULATIONS FOR |
| ATTIC CROSS VENTILATION AT EACH UNIT |
| AND CLEARLY INDICATE ON ROOF PLAN THE |
| VENT SIZES AND LOCATION.SEC 2309.7 SBC |
| 8-PROVIDE COMPLETE DETAIL/SPECIFICATIONS |
| FOR CEILING CONSTRUCTION AT ENTRY AND |
| BACK PORCHES OF EACH UNIT. INCLUDE |
| FASTENER TYPE AND SPACING.SEC 2504 SBC |
| 9-WALK-IN-CLOSET IN UNITS 1527 TO HAVE |
| THE SHELF ONLY (NO ROD) ON EITHER SIDE |
| IN ORDER TO COMPLY WITH THE CLEARANCES |
| ON THE FAIR HOUSING ACT, CHAPTER THREE |