Plan Review Notes
Plan Review Notes For Permit 99121998
Permit Number 99121998
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "A0". PROVIDE ELEVATION
 CERTIFICATE AFTER SLAB IS POURED.
 2-PRODUCT APPROVALS:
 -PROVIDE PRODUCT APPROVAL FOR TWO HOUR
 FIRE RATED CONCRETE BLOCK, EXTERIOR
 FRENCH DOOR WITH SIDELITES ASSEMBLY,
 EXTERIOR DOUBLE FRENCH DOOR, AND
 WINDOW MULLIONS.
 -DRAWINGS IN PRODUCT APPROVAL FOR THE
 SLIDING GLASS DOORS ARE NOT LEGIBLE.
 3-PROVIDE BUCK DETAIL FOR SLIDING GLASS
 DOORS. SEC. 104.2.2 CITY AMENDMENTS.
 4-PRODUCT APPROVAL FOR SINGLE HUNG
 WINDOWS REQUIRES A 2X BUCK. REVISE
 WINDOW BUCK DETAIL AS REQUIRED.
 5-STORM PANELS:
 -INSTALLATION SCHEDULE AND KEY PLAN
 DON'T MATCH ARCHITECT'S PLANS. SEE
 SIZES OF OPENINGS. ALSO, INSTALLATION
 SCHEDULE AND KEY PLAN TO INCLUDE ALL
 OPTIONS SHOWN BY THE ARCHITECT.
 -CLEARLY INDICATE ON DRAWINGS MOUNTING
 CONDITIONS AND ANCHOR TYPE AND SPACING
 NOTE: TAKE INTO CONSIDERATION TABLES
 ON SHEET 4 OF 4 OF DRAWING 97-404P AND
 BUILDING CONSTRUCTION. THE MEAN ROOF
 HEIGHT FOR THIS BUILDING IS PLUS OR
 MINUS AT 16'-0" AND THE BUILDING CONST
 IS MASONRY, NOT CONCRETE.
 6-REVISE ENERGY CALCULATIONS:
 -OWNER INFORMATION IS INCORRECT.
 -LOCATION IS INCORRECT.
 -DON'T FORGET OWNER' SIGNATURE AND DATE
 7-PROVIDE COMPLETE CALCULATIONS FOR
 ATTIC CROSS VENTILATION AT EACH UNIT
 AND CLEARLY INDICATE ON ROOF PLAN THE
 VENT SIZES AND LOCATION.SEC 2309.7 SBC
 8-PROVIDE COMPLETE DETAIL/SPECIFICATIONS
 FOR CEILING CONSTRUCTION AT ENTRY AND
 BACK PORCHES OF EACH UNIT. INCLUDE
 FASTENER TYPE AND SPACING.SEC 2504 SBC
 9-WALK-IN-CLOSET IN UNITS 1527 TO HAVE
 THE SHELF ONLY (NO ROD) ON EITHER SIDE
 IN ORDER TO COMPLY WITH THE CLEARANCES
 ON THE FAIR HOUSING ACT, CHAPTER THREE


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved