Plan Review Notes
Plan Review Notes For Permit 99121998
Permit Number 99121998
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00SHT.1-MAX.HEIGHT TO BOTTOM OF WOOD
 BLOCKING FOR SIDE OF TOILET SHALL BE 32"
 (PLANS SHOW 32" MIN.)PER FHA REQ.#6,FIG.
 #3.
  
 CLEARLY INDICATE ON THE PLANS WHICH
 DESIGN SPECIFICATION (A OR B)OF THE FAIR
 HOUSING ACT IS BEING UTILIZED.
  
 BATHROOM #2,UNIT MDL-1409-LENGTH OF THE
 BATHROOM DOESN'T HAVE THE DIMENSION
 REQUIRED FOR TYPE "A"BATH WHEN
 APPROACHED FROM THE BEDROOM.
  
 THE LOCATION OF THE PLUMBING FIXTURES ON
 THE SANITARY RISERS SHALL CORRELATE W/
 THE ARCH.FLOOR PLAN.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.