Plan Review Notes
Plan Review Notes For Permit 99121967
Permit Number 99121967
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00SHT.1-MAX.HEIGHT TO BOTTOM OF WOOD
 BLOCKING FOR SIDE OF TOILET SHALL BE 32"
 (PLANS SHOW 32"MIN)PER FHA REQ.6,FIG.#3.
  
 SUPPLY WOOD BLOCKING DETAILS FOR SHOWER.
 COMPLY W/FHA REQ.#6,FIG.#5.
  
 CLEARLY INDICATE ON THE PLANS WHICH
 DESIGN SPECIFICATION (A OR B )OF THE
 FAIR HOUSING ACT IS BEING UTILIZED.
  
 BATHROOM #2,UNIT MDL-1409,LENGTH OF THE
 BATHROOM DOESN'T HAVE THE DIMENSION
 REQUIRED FOR TYPE "A" BATH WHEN
 APPROACHED FROM THE BEDROOM.
  
 THE LOCATION OF THE PLUMBING FIXTURES ON
 THE SANITARY RISER DOESN'T MATCH THE
 ARCH.FLOOR PLAN..COUNTYWIDE AMENDMENTS
 TO SPC SEC.104.2.1.