Date |
Text |
2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| 1-FLOOD ZONE "AO". PROVIDE ELEVATION |
| CERTIFICATE AFTER SLAB IS POURED. |
| 2-PRODUCT APPROVALS: |
| -PROVIDE PRODUCT APPROVAL FOR TWO HOUR |
| FIRE RATED CONCRETE BLOCK, EXTERIOR |
| FRENCH DOOR WITH SIDELITES ASSEMBLY, |
| EXTERIOR DOUBLE FRENCH DOOR, WINDOW |
| MULLIONS. |
| -DRAWINGS IN PRODUCT APPROVAL FOR THE |
| SLIDING GLASS DOORS ARE NOT LEGIBLE. |
| 3-PROVIDE BUCK DETAIL FOR SLIDING GLASS |
| DOORS. SEC 104.2.2 CITY AMENDMENTS. |
| 4-PRODUCT APPROVAL FOR SINGLE HUNG |
| WINDOWS REQUIRES A 2X BUCK.REVISE |
| WINDOW BUCK DETAIL AS REQUIRED. |
| 5-STORM PANELS: |
| -INSTALLATION SCHEDULE AND KEY PLAN |
| DON'T MATCH ARCHITECT'S LAYOUT. SEE |
| SIZES OF OPENINGS. ALSO, INSTALLATION |
| SCHEDULE AND KEY PLAN TO INCLUDE ALL |
| THE OPTIONS SHOWN IN ARCHITECT'S PLANS |
| -CLEARLY INDICATE ON DRAWINGS MOUNTING |
| CONDITIONS AND ANCHOR TYPE AND SPACING |
| NOTE: TAKE INTO CONSIDERATION TABLES |
| ON SHEET 4 OF 4 OF DRAWING 97-404P AND |
| BUILDING CONSTRUCTION. THE MEAN ROOF |
| HEIGHT FOR THIS BUILDING IS PLUS OR |
| MINUS AT 16'-0" AND THE BUILDING |
| CONSTRUCTION IS REINFORCED MASONRY |
| NOT CONCRETE. |
| 6-REVISE ENERGY CALCULATIONS: |
| -OWNER'S INFORMATION IS INCORRECT. |
| -LOCATION OF BUILDING IS NOT IN BOYNTON |
| -DON'T FORGET TO ASK OWNER TO SIGN AND |
| DATE FORM AFTER CORRECTIONS ARE DONE. |
| 7-PROVIDE COMPLETE CALCULATIONS FOR |
| ATTIC CROSS VENTILATION AT EACH UNIT |
| AND CLEARLY INDICATE ON ROOF PLAN THE |
| VENTS SIZES AND LOCATION. 2309.7 SBC. |
| 8-PROVIDE COMPLETE DETAIL/SPECS FOR |
| CEILING CONSTRUCTION AT ENTRY AND BACK |
| PORCH. INCLUDE FASTENER TYPE AND |
| SPACING. SEC 2504 SBC 1997. |
| 9-WALK-IN-CLOSET IN UNITS 1527 TO HAVE |
| THE SHELF ONLY (NO ROD) ON EITHER SIDE |
| IN ORDER TO COMPLY WITH THE CLEARANCES |
| ON THE FAIR HOUSING ACT, CHAPTER THREE |