2001-01-08 00:00:00*************** PROVISO **************
  
 1)NOTE:PLEASE NOTE THAT YOU HAVE A 52AMP
 LOAD ON PANEL B AND YOU SHOW A 2P-40
 FEEDING THAT PANLE.ALSO PLEASE NOTE THAT
 AS PER 310-16 #8 IN THE 75C COLUMN IS
 ONLY RATED FOR 50 AMPS. CANNOT USE THE
 90C RATING.
  
 PLEASE CORRECT THE ABOVE AND SUBMIT FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372