Plan Review Notes For Permit 99121888 |
Permit Number |
99121888 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************** PROVISO ***************** | | | | 1)NOTE: NEED TO CORRECT OVERCURRENT | | PROTECTION FOR PANEL'B'. | | YOU SHOW 2P40 WITH A 52 AMP LOAD?? | | ALSO SHOW #8 AWG. WIRE IS TO BE SIZED | | FROM 310-16 AND FROM THE 75C COLUMN. | | | | PLEASE CORRECT THE ABOVE AND SUBMIT | | PLANS FOR REVIEW AND APPROVAL BEFORE | | ROUGH INSPECTION IS CALLED IN. IF THERE | | ARE ANY QUESTIONS PLEASE CALL. 659-8096 | | EXT 8372 |
|