Plan Review Notes For Permit 99121816
Permit Number 99121816
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00DENIED
  
 1)ADDITIONAL IMPACT FEES ARE OWED TO THE
 COUNTY FOR THE ADDITIONAL 268 SQFT UNDER
 A/C WHEN LOFT OPTION IS USED AS
 INDICATED ON PLANS. PLANS MUST BE RE-
 STAMPED BY COUNTY.
  
 2)PROVIDE FOR REQUIRED FIRE CUT PER 1997
 SBC SEC.2305.4 FOR FLOOR TRUSSES ENTER-
 ING AND TERMINATING IN MASONRY WALLS.SEE
 SHEET A-5.
  
 3)SUBMIT 2 COPIES OF REVISED STORM PANEL
 KEY PLAN AND SCHEDULE THAT CORRESPONDS
 TO THE OPTIONS THAT ARE TO BE USED.
  
 4)SPECIFICATIONS FOR GARAGE DOOR
 SUBMITTED WITH PRODUCT APPROVAL INDICATE
 A NEGATIVE DESIGN PRESSURE OF -33PSF FOR
 16'X 7' DOOR, WIND LOADS ON SHEET A-4A
 LISTS NEG. PRESSURE OF -34PSF.
 PLEASE CORRECT.
  
 5)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR EXTERIOR
 OUTSWING STEEL DOOR WITH SIDELITES AS
 SHOWN ON PLANS. PRODUCT APPROVALS ARE
 REQUIRED FOR SPECIFIC COMPONENT THAT
 WILL BE INSTALLED.