2001-01-08 00:00:00************* UNSAT ********************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT.NEEDS TO BE ABLE TO HANDLE
 AVAILABLE FAULT CURRENT. 110-9/ 230-65
  
 2)NOTE: NEED TO HAVE SMOKE DETECTORS
 INSIDE AND OUTSIDE ALL SLEEEPING ROOMS.
 AS REQ`D BY NFPA-72 2-2.1.1.1
 3)NOTE: PLEASE HAVE REQ`D BATH(S) CIRCUT
 LISTED ON PANEL SCHEDULE AND TO BE 20 A
 AND #12 AWG. AS PER 210-52D
  
 4)NOTE:ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE GFI/GFI PROTECTED
 AS REQ`D BY 210-8-A-6
  
 5)NOTE:PLEASE SHOW AND INCLUDE ON RISER
 DIAGRARM BLDG.STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM. 250-81/215-5
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE AREB
 ANY QUESTIONS PLEASE CALL 659-8096X 8372