2001-01-08 00:00:00 | ************* UNSAT ******************** | | | | 1)NOTE:NEED TO SUBMIT AIC RATING OF | | EQUIPMENT.NEEDS TO BE ABLE TO HANDLE | | AVAILABLE FAULT CURRENT. 110-9/ 230-65 | | | | 2)NOTE: NEED TO HAVE SMOKE DETECTORS | | INSIDE AND OUTSIDE ALL SLEEEPING ROOMS. | | AS REQ`D BY NFPA-72 2-2.1.1.1 | | 3)NOTE: PLEASE HAVE REQ`D BATH(S) CIRCUT | | LISTED ON PANEL SCHEDULE AND TO BE 20 A | | AND #12 AWG. AS PER 210-52D | | | | 4)NOTE:ALL OUTLETS SERVING KITCHEN | | COUNTERSPACE ARE TO BE GFI/GFI PROTECTED | | AS REQ`D BY 210-8-A-6 | | | | 5)NOTE:PLEASE SHOW AND INCLUDE ON RISER | | DIAGRARM BLDG.STEEL AS PART OF THE | | GROUNDING ELECTRODE SYSTEM. 250-81/215-5 | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL. IF THERE AREB | | ANY QUESTIONS PLEASE CALL 659-8096X 8372 |
|