2001-01-08 00:00:00PROVISO;
 REVISE A/C DRAWINGS BEFORE ROUGH A/C
 INSPECTION.
 1. A/H UNITS NOT CAPABLE OF PUSHING CFMS
 INDICATED, BOTH UNITS.
 2. RETURN AIR AH#2, RETURN AIR CANNOT
 BE IN BATHROOM. R/A SHOULD BE SPLIT
 TO BEDROOMS WHICH ARE OVER 300CFMS.