Plan Review Notes For Permit 99121765 |
Permit Number |
99121765 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | EQUIPMENT MAINS AS REQ`D BY 110-9/230-65 | | AND 215-5 OF THE NEC. | | | | 2)NOTE: NEED TO SHOW SMOKE DETECTORS | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | AS REQ`D BY NFPA-72 2-2.1.1.1 | | | | 3)NOTE:PLEASE SHOW REQ`D DEDICATED | | CIRCUTS FOR BATH(S)20 AMP AND #12 AWG | | AS REQ`D BY 210-52D | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL. IF THERE ARE AN | | QUESTIONS PLEASE CALL 659-8096EXT 8372 |
|