Plan Review Notes
Plan Review Notes For Permit 99121761
Permit Number 99121761
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00A 30"X 48" CLEAR FLOOR SPACE SHALL BE
 PROVIDED PARALLEL TO THE SHOWER PER
 FEDERAL FAIR HOUSING ACT 24 CFR 100.205
 REQ.#7,PARAGRAPH (2)(A).THE WATER CLOSET
 CANNOT BE LOCATED IN THIS SPACE PER
 SPECIFICATION "A" OF THE ACT.
  
 SHOW MAX.HEIGHT TO BOTTOM OF WOOD
 BLOCKING FOR GRAB BARS.COMPLY W/FHA REQ.
 #6.
  
 THE LOCATION OF THE FIXTURES ON THE
 SANITARY RISER DOESN'T CORRELATE W/THE
 ARCH.FLOOR PLAN.COUNTYWIDE AMENDMENTS
 TO THE SPC SEC.104.2.1.