Plan Review Notes
Plan Review Notes For Permit 99121759
Permit Number 99121759
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED;
 1. 4 TON UNIT IS NOT CAPABLE OF
 PROVIDING 2040 CFM. AS SHOWN ON
 DRAWING. REVISE DRAWINGS.
 2. ELECTRIC EXHAUST FAN IS REQUIRED
 IN MASTER SUITE TOILET ROOM.
 3APPROV:99121739 JW