Plan Review Notes
Plan Review Notes For Permit 99121731
Permit Number 99121731
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS. NEEDS TO BE ABLE TO
 HANDLE AVAILABLE FAULT CURRENT. 110-9/
 230-65
  
 2)NOTE: NEED TO HAVE SMOKE DETECTORS
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 AS REQ`D BY NFPA-72 2-2.1.1.1
  
 3)NOTE: NEED TO SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECTE
 -D. AS REQ`D BY 210-8-A-6
  
 4)NOTE:PLEASE INCLUDE BLDG.STEEL AS PART
 OF THE GROUNDING ELECTRODE SYSTEM.
 AS PER 250-81
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REIVEW AND APPROVAL.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 X 8372