2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT AND NEEDS TO BE ABLE TO HANDLE
 THE AVAILABLE FAULT CURRENT.
  
 2)NOTE: SMOKE DETECTORS INSIDE AND OUT-
 -SIDE ALL SLEEPING ROOMS.
  
 3)NOTE: NEED TO HAVE CIRCUT FOR BATH(S)
 LISTED ON PANEL SCHEDULE AS PER 210-52D
 20 AMP AND #12 AWG.
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEAS CALL 659-8096 EXT-
 8372