2001-01-08 00:00:00*************UNSAT********************
  
 1)NOTE:NEED TO SUBMTI AIC RATING OF ALL
 EQUIPMENT MAINS. 110-9/230-65
  
 2)NOTE: NEED TO COMPLY WIHT REQ`MENTS
 OF SMOKE DETECTORS INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS. AS PER 1993/1996
 NFPA-72 2-2.1.1.1
  
 3)NOTE:AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED. PLEASE SHOW.
  
 4)NOTE:PLEASE LIST REQ`D BATH(S) CIRCUT
 ON PANEL SCHDULE. AS PER 210-52D
  
 5)NOTE:PLEASE INCLUDE BLDG.STEEL ON
 RISER DIAGRAM AS PART OF THE GROUNDING
 ELECTRODE SYSTEM.250-81/215-5
  
 6)NOTE:AS PER 110-16 A/C DISC.
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 65908096 EXT 8372