Plan Review Notes For Permit 99121650 |
Permit Number |
99121650 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *******CORRECTED BY REVISION************ | | | | 1. EXISTING METER DOES NOT HAVE THE | | CAPACITY TO PROVIDE ENGINEER'S REQUIRE- | | MENT OF 24 GPM @ 42.8 PSI. | | A MINIMUM OF A 1" METER IS REQUIRED TO | | OBTAIN THESE FLOWS. (SEE ENGINEERING PG) | | 2. CORRECT METER SHALL BE INSTALLED | | PRIOR TO FIRE SPRINKLER PERMIT BEING | | APPROVED. | | 3. PROVIDE PLANS SHOWING COMPLIANCE WITH | | PROVISO 1 OF ENGINEERING REQUIREMENTS. | | PER NKM |
|