Plan Review Notes
Plan Review Notes For Permit 99121650
Permit Number 99121650
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*******CORRECTED BY REVISION************
  
 1. EXISTING METER DOES NOT HAVE THE
 CAPACITY TO PROVIDE ENGINEER'S REQUIRE-
 MENT OF 24 GPM @ 42.8 PSI.
 A MINIMUM OF A 1" METER IS REQUIRED TO
 OBTAIN THESE FLOWS. (SEE ENGINEERING PG)
 2. CORRECT METER SHALL BE INSTALLED
 PRIOR TO FIRE SPRINKLER PERMIT BEING
 APPROVED.
 3. PROVIDE PLANS SHOWING COMPLIANCE WITH
 PROVISO 1 OF ENGINEERING REQUIREMENTS.
 PER NKM