2001-01-08 00:00:00PASSED WITH PROVISOS:
 PASSED WITH PROVISOS:
 1.A TEE MUST BE PLACED BETWEEN THE METER
 AND THE EXISTING DOMESTIC BACKFLOW
 PREVENTER.THEN AN APPROVED DOUBLE
 CHECK BACKFLOW PREVENTER ASSEMBLY (DCA)
 CAN BE PLACED ON THE END OF THE TEE TO
 SERVE THE SPRINKLERS, THEN THE FIRE
 DEPARTMENT CONNECTION (FDC) CAN BE
 INSTALLED AFTER THE DCA SO THE WATER
 WILL NOT CONTAMINATE THE CITY OR
 BUILDING DRINKING WATER AS WELL AS NOT
 HAVING THE WATER FOR THE SPRINKLER
 SYSTEM GOING THROUGH TWO BACKFLOW
 PREVENTERS.
 2.THE SPRINKLER FLOWS SUPPLIED CALL FOR
 24 GALLONS PER MINUTE(GPM) FOR FIRE
 FLOW.A MINIMUM OF A 1" METER IS
 REQUIRED FOR THESE FLOWS.