Plan Review Notes For Permit 99121650 |
Permit Number |
99121650 |
|
Review Stop |
ENG |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | PASSED WITH PROVISOS: | | PASSED WITH PROVISOS: | | 1.A TEE MUST BE PLACED BETWEEN THE METER | | AND THE EXISTING DOMESTIC BACKFLOW | | PREVENTER.THEN AN APPROVED DOUBLE | | CHECK BACKFLOW PREVENTER ASSEMBLY (DCA) | | CAN BE PLACED ON THE END OF THE TEE TO | | SERVE THE SPRINKLERS, THEN THE FIRE | | DEPARTMENT CONNECTION (FDC) CAN BE | | INSTALLED AFTER THE DCA SO THE WATER | | WILL NOT CONTAMINATE THE CITY OR | | BUILDING DRINKING WATER AS WELL AS NOT | | HAVING THE WATER FOR THE SPRINKLER | | SYSTEM GOING THROUGH TWO BACKFLOW | | PREVENTERS. | | 2.THE SPRINKLER FLOWS SUPPLIED CALL FOR | | 24 GALLONS PER MINUTE(GPM) FOR FIRE | | FLOW.A MINIMUM OF A 1" METER IS | | REQUIRED FOR THESE FLOWS. |
|