2001-01-08 00:00:00******************PROVISO***************
 THESE ITEMS MUST BE CORRECTED PRIOR TO
 ISSUANCE OF THE PLUMBING PERMIT:
  
 1)CIVIL PLANS SHOW DOMESTIC WATER AS 4"
 AND PLUMBING DRAWINGS SHOW 6".CLARIFY.
  
 2)SUBMIT COPY OF APPROVAL FOR GREASE
 INTERCEPTORS FROM CITY OF WEST PALM
 BEACH UTILITIES.CONTACT R.COMPO AT
 (561)835-7423.
  
 3)GAS LINE SHALL BE SHOWN ON CIVIL
 DRAWINGS AND CLEARLY IDENTIFY GAS LINE
 ON SHT.P-100.PIPING SHALL ONLY BE RUN
 UNDER BUILDING SLAB WHEN NO OTHER
 METHOD IS AVAILABLE.DETERMINATION SHALL
 BE MADE CONTINGENT UPON SUBMITTAL OF
 ADDITIONAL INFORMATION .SGC SEC.308.3,
 308.3.2.
  
 4)PH OF EFFLUENT FROM COOLING TOWER
 SHALL COMPLY W/SPC SEC.701.5.SUBMIT DATA
 FROM CHEMICAL AND/OR COOLING TOWER
 MANUFACTURER NOTING PH LEVEL OF EFFLUENT
 AT POINT OF DISCHARGE.
  
 SUBMIT MANUF.SHEETS AND INSTALLATION
 GUIDELINES FOR SOVENT SYSTEM.INSTALL-
 ATION SHALL COMPLY W/ASSE STANDARD #1043
  
 WATER SUPPLY CONTROL VALVES FOR THE
 WATER RISERS CANNOT BE INSTALLED INSIDE
 THE OCCUPIABLE ROOMS.VALVES SHALL BE
 IN A ACCESSIBLE LOCATION PER SPC SEC.
 610.4.2.
  
 FLUSH CONTROLS FOR THE ACCESSIBLE WATER
 CLOSETS SHALL BE LOCATED ON THE WIDE
 SIDE OF THE WATER CLOSET.SEE FACBC SEC.
 4.18.4.
  
 URINAL IN ROOFTOP RESTROOM SHALL COMPLY
 W/FACBC SECS.4.18.2- 4.18.4.SHOW URINAL
 ON ELEVATION #16 ON SHT.A9.4.
  
 THE DRAINS TO THE GREASE TRAPS CANNOT BE
 INSTALLED AS DRAWN.THIS DESIGN WILL
 CREATE FLOW PROBLEMS AND STOPPAGES.
 COMPLY W/SPC SEC.307.1.1.,307.5.
  
 SHT.P504-SHOW SIZES FOR THE HORIZONTAL
 DRAIN SECTIONS ON THE ISOMETRICS AND
 SHOW HOW THE HORIZONTAL SECTIONS CONNECT
 TO THE DRAINAGE SYSTEM.
  
 SHT.P504-THE PRL FOR STACK #R4 SHALL
 CONNECTTO THE SOVENT BUILDING DRAIN.
  
 CONSOLIDATE ALL REVISIONS,ADDENDUMS,ETC.
 INTO COMPLETE SETS OF PLANS.AT PRESENT
 THESE DOCUMENTS ARE TOO EXPANDED AND A
 PROPER REVIEW IS DIFFICULT.