Plan Review Notes
Plan Review Notes For Permit 99121640
Permit Number 99121640
Review Stop P
Sequence Number 6
Notes
Date Text
2001-01-08 00:00:00PLUMBING PROVISO:**NOTE**THE FOLLOWING
 ITEMS SHALL BE SUBMITTED FOR REVIEW
 PRIOR TO THE ISSUANCE OF THE PLUMBING
 PERMIT.
  
 1)SUBMIT COPY OF APPROVAL FROM CITY OF
 WEST PALM BEACH UTILITIES FOR GREASE
 TRAP.COUNTYWIDE AMENDMENTS TO SPC
 101.4.7.
  
 2)SHOW LOCATION OF GAS LINE ON CIVIL
 DRAWINGS AND CLEARLY SHOW ENTRANCE POINT
 INTO BUILDING.PIPING SHALL ONLY BE RUN
 UNDER BUILDING SLAB WHEN NO OTHER METHOD
 IS AVAILABLE.DETERMINATION SHALL BE MADE
 CONTINGENT ON ADDITIONAL INFORMATION.
 SGC.SEC.308.3,308.3.2.
  
 3)SUBMIT ISOMETRIC DRAWING FOR WATER
 PIPING TO WATER HEATERS.COUNTYWIDE AMEND
 MENTS TO SPC SEC.104.2.1.
  
 4) PH OF EFFLUENT FROM COOLING TOWER
 SHALL COMPLY W/SPC SEC.701.5.SUBMIT
 DATA FROM CHEMICAL AND/OR COOLING TOWER
 MANUF.NOTING PH OF EFFLUENT AT POINT OF
 DISCHARGE.
  
 5)SUBMIT MANUF.SHEETS FOR ALL SYSTEM
 COMPONENTS FOR THE SOVENT SYSTEM.SYSTEM
 SHALL COMPLY W/ASSE #1043.
  
 6)TWO LAVATORIES ARE REQD.FOR THE MALES
 AND FEMALES IN THE RESTAURANT.COMPLY W/
 SPC TABLE 407.
  
 7)DRAIN FOR THE DUMPSTER SHALL DISCHARGE
 THROUGH THE GREASE INTERCEPTOR.SPC SEC.
 1004.1.
  
 8)CIVIL PLANS SHOW DOMESTIC WATER AS 4"
 & PLBG.DRAWINGS SHOWS 6".
  
 9)LOCATION OF WATER LINES ON PLUMBING
 DRAWINGS DO NOT CORRELATE W/PLUMBING
 PLANS.
  
 10)JOB SPEC.15420-12-SEC.3.9-(C)(E)(F)
 (G).PIPING SUPPORTS SHALL COMPLY W/SPC
 SEC.310.3.
  
 11)JOB SPEC.15430-17-SEC.3.1(W) AND
 15430-22-SEC.3.9(A)-GREASE RECOVERY
 UNITS ARE NOT PERMITTED PER CITY ORD.
  
 12)JOB SPEC.15430--21-SEC.3.8-GREASE
 INTERCEPTOR SHALL COMPLY W/CITY OF WPB
 UTILITIES REQS.
  
 13)JOB SPEC.15486-6-SEC.3.2(G)-RELIEF
 VALVE DRAIN SHALL DISCHARGE TO EXTERIOR
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 507.6.3.
  
 NOTE:THE SANITARY FACILITIES ON THE ROOF
 ARE IN COMPLIANCE FOR THE OCCUPANT LOAD
 OF THE POOL ONLY!APPROVAL MUST BE
 OBTAINED FROM THE HEALTH DEPT.PRIOR TO A
 APPROVAL FROM THIS DEPT.. ANY OTHER USE
 SUCH AS WEDDINGS,PARTIES,ETC.CONSTITUTES
 A VIOLATION OF HE STANDARD PLUMBING CODE
 SEC.407.1.3.FOR MINIMUM NUMBER OF REQD.
 SANITARY FACILITIES.