2001-01-08 00:00:00 | COMPLY W/ALL PREVIOUS COMMENTS DATED |
| 3/2/00 IN ADDITION TO THE FOLLOWING: |
| |
| SUBMIT COPY OF APPROVAL FORM FROM CITY |
| OF WPB FOR SIZE OF GREASE INTERCEPTOR. |
| CONTACT R.COMPO AT (561)835-7423. |
| |
| SHOW LOCATION OF THE GAS LINE ON CIVIL |
| DRAWINGS AND CLEARLY SHOW ENTRANCE POINT |
| INTO BUILDING.PIPING SHALL ONLY BE RUN |
| UNDER BUILDING SLAB WHEN NO OTHER METHOD |
| IS AVAILABLE.DETERMINATION SHALL BE MADE |
| CONTINGENT ON ADDITIONAL INFORMATION. |
| SGC SEC.308.3,308.3.2. |
| |
| TWO WAY CLEANOUTS SHALL BE INSTALLED ON |
| THE WASTE LINES LEADING TO AND FROM THE |
| GREASE INTERCEPTOR.SPC 710.4. |
| |
| WATER RISER CONTROL VALVES SHALL BE |
| ACCESSIBLE AND NOT LOCATED IN ROOMS PER |
| SPC SEC.610.4.2. |
| |
| MANUFACTURER'S DATA SHEETS FOR SOVENT |
| SYSTEM COMPONENTS SHALL BE SUBMITTED FOR |
| REVIEW PRIOR TO ROUGH PLUMBING INSPECT- |
| ION PER SPC SEC.923.3,COUNTYWIDE AMEND- |
| MENTS TO SPC SEC.104.2.1. |
| |
| SHT.P-002 SUBMIT PIPNG DETAILS FOR WATER |
| HEATER PER COUNTYWIDE AMENDMENTS TO SPC |
| SEC.104.2.1.INCLUDE FLUE DETAILS . |
| |
| OVERFLOW DRAINS FOR ROOF SHALL TERMINATE |
| ABOVE GRADE AT AN OBSERVABLE POINT PER |
| SPC SEC.1109.2. |
| |
| SHT.A-9.4-FLOOR PLAN OF RESTROOM ON ROOF |
| DOESN'T CORRELATE W/ELEVATION DETAIL |
| #16. |
| |
| SHT.A-9.4-HEIGHT OF ACCESSIBLE LAV.SHALL |
| COMPLY W/FACBC SEC.4.19.2. |
| |
| FLUSH CONTROLS FOR WATER CLOSETS SHALL |
| BE INSTALLED ON THE WIDE SIDE OF TOILET |
| AREA PER FACBC SEC.4.16.5.AND URINALS |
| SHALL COMPLY W/FACBC SEC.4.18.4. |
| |