Notes
Date Text
2001-01-08 00:00:00COMPLY W/ALL PREVIOUS COMMENTS DATED
 3/2/00 IN ADDITION TO THE FOLLOWING:
  
 SUBMIT COPY OF APPROVAL FORM FROM CITY
 OF WPB FOR SIZE OF GREASE INTERCEPTOR.
 CONTACT R.COMPO AT (561)835-7423.
  
 SHOW LOCATION OF THE GAS LINE ON CIVIL
 DRAWINGS AND CLEARLY SHOW ENTRANCE POINT
 INTO BUILDING.PIPING SHALL ONLY BE RUN
 UNDER BUILDING SLAB WHEN NO OTHER METHOD
 IS AVAILABLE.DETERMINATION SHALL BE MADE
 CONTINGENT ON ADDITIONAL INFORMATION.
 SGC SEC.308.3,308.3.2.
  
 TWO WAY CLEANOUTS SHALL BE INSTALLED ON
 THE WASTE LINES LEADING TO AND FROM THE
 GREASE INTERCEPTOR.SPC 710.4.
  
 WATER RISER CONTROL VALVES SHALL BE
 ACCESSIBLE AND NOT LOCATED IN ROOMS PER
 SPC SEC.610.4.2.
  
 MANUFACTURER'S DATA SHEETS FOR SOVENT
 SYSTEM COMPONENTS SHALL BE SUBMITTED FOR
 REVIEW PRIOR TO ROUGH PLUMBING INSPECT-
 ION PER SPC SEC.923.3,COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 SHT.P-002 SUBMIT PIPNG DETAILS FOR WATER
 HEATER PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.INCLUDE FLUE DETAILS .
  
 OVERFLOW DRAINS FOR ROOF SHALL TERMINATE
 ABOVE GRADE AT AN OBSERVABLE POINT PER
 SPC SEC.1109.2.
  
 SHT.A-9.4-FLOOR PLAN OF RESTROOM ON ROOF
 DOESN'T CORRELATE W/ELEVATION DETAIL
 #16.
  
 SHT.A-9.4-HEIGHT OF ACCESSIBLE LAV.SHALL
 COMPLY W/FACBC SEC.4.19.2.
  
 FLUSH CONTROLS FOR WATER CLOSETS SHALL
 BE INSTALLED ON THE WIDE SIDE OF TOILET
 AREA PER FACBC SEC.4.16.5.AND URINALS
 SHALL COMPLY W/FACBC SEC.4.18.4.
  
 PLEASE CALL (561)659-8096,EXT.8377 IF
 YOU HAVE ANY QUESTIONS.
 TIMOTHY LARGE-PLUMBING PLANS EXAMINER.