Plan Review Notes For Permit 99121640 |
Permit Number |
99121640 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1- THE CITY STILL WOULD LIKE A LOAD CALC | | PER 220ESTIMATES ON USE ARE NOT | | PER CODE!!!!! | | | | 2- PANEL PPRA SHOWS A LOAD OF 295.68KVA | | THIS WOULD BE TO LARGE FOR A BUSS OF | | ONLY 800 AMPERES! | | | | 3- PANEL DP1B SHOWS A DEMAND LOAD OF | | 245.68KVA FOR PANEL PPRA WHICH IS 50 | | KVA SMALLER THAN SHOWN ON PPRA LOAD | | CALCULATION.WHEN YOU ADD THE 50KVA | | TO THE TOTAL FOR DP1B IT EXCEEDS THE | | 1200 AMPERES THAT DP1B IS RATED FOR! | | | | 4- DP1A AND DP1B I THINK SHOW THAT THEY | | HAVE 1000 AMPERE MAINS NO WIRE SIZES | | ARE SHOWN TO EACH, AND THE WIRE THAT | | IS BEING TAPED FOR THESE TWO MAINS IS | | NOT 2000 AMPERE RATED!!! |
|