2001-01-08 00:00:001- THE CITY STILL WOULD LIKE A LOAD CALC
 PER 220ESTIMATES ON USE ARE NOT
 PER CODE!!!!!
  
 2- PANEL PPRA SHOWS A LOAD OF 295.68KVA
 THIS WOULD BE TO LARGE FOR A BUSS OF
 ONLY 800 AMPERES!
  
 3- PANEL DP1B SHOWS A DEMAND LOAD OF
 245.68KVA FOR PANEL PPRA WHICH IS 50
 KVA SMALLER THAN SHOWN ON PPRA LOAD
 CALCULATION.WHEN YOU ADD THE 50KVA
 TO THE TOTAL FOR DP1B IT EXCEEDS THE
 1200 AMPERES THAT DP1B IS RATED FOR!
  
 4- DP1A AND DP1B I THINK SHOW THAT THEY
 HAVE 1000 AMPERE MAINS NO WIRE SIZES
 ARE SHOWN TO EACH, AND THE WIRE THAT
 IS BEING TAPED FOR THESE TWO MAINS IS
 NOT 2000 AMPERE RATED!!!