Plan Review Notes
Plan Review Notes For Permit 99121640
Permit Number 99121640
Review Stop P
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00JOB SPEC.15420-12-SEC.3.9-(C)(E)(F)(G).
 PIPING SUPPORTS SHALL COMPLY W/SPC SEC.
 310.3.
  
 JOB SPEC.15430-17-SEC.3.1.(W) AND
 15430-22-SEC.3.9(A)-GREASE RECOVERY
 UNITS ARE NOT PERMITTED PER CITY ORD.
  
 JOB SPEC.15430-21-SEC.3.8-GREASE INTER.
 SHALL COMPLY W/CITY OF WPB UTILITIES
 REQS.CONTACT R.COMPO AT (561)835-7423.
  
 JOB SPEC.15486-6-SEC.3.2(G)-RELIEF VALVE
 DRAIN SHALL DISCHARGE TO EXTERIOR PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.507.6.3
  
 SHT.L-104-LOCATION OF BACKFLOW PREVENTER
 SHALL BE DETERMINED BY CITY OF WPB
 UTILITIES DEPT.CALL (561)659-8000.
  
 HANDICAP ACCESSIBLE ROOMS SHALL W/FACBC
 SECS.9.1-9.4 AND ALSO W/FACBC SEC.9.2.3
 (FLA.5% RULE).
  
 CLEARLY NOTE THE TOTAL NUMBER OF SLEEP-
 ING ROOMS IN THE FACILITY.
  
 SHT.A-2.1.-LOCATION OF GREASE TRAP SHALL
 COMPLY W/CITY OF WEST PALM BEACH
 UTILITIES REQS.CONTACT R.COMPO AT (561)
 835-7423.COMPLY W/SBC SEC.1803.1.3.
  
 SHT.A-2.1.-LOCATION OF BACKFLOW
 PREVENTER SHALL BE DETERMINED BY CITY
 OF WPB UTILITIES.CALL (561)659-8000
  
 THE ACCESSIBLE (HANDICAP) UNITS SHALL BE
 DISPERSED AMONG THE VARIOUS FLOORS AND
 CLASSES PER FACBC SEC.9.1.4(1).
  
 ALL PUBLIC AND COMMON USE AREA ROOMS
 SHALL BE FULLY ACCESSIBLE.
  
 SUBMIT DETAIL OF ELEC.WATER COOLER ON
 ROOF. COMPLY W/FACBC SEC.4.1.3.(10)(A),
 4.15 AND FIGURE 27.
  
 SHT.M-4 SHOWS OVERFLOW FROM COOLING
 TOWERS AND CHEMICAL FEEDER TO SANITARY.
 PH OF EFFLUENT SHALL COMPLY W/SPC SEC.
 701.5.(DATA FROM MANUF.REQD.INDICATING
 PH LEVEL OF EFFLUENT AT POINT OF
 DISCHARGE.)
  
 PANS AND PAN DRAINS ARE REQD.FOR THE
 WATER HEATERS PER COUNTYWIDE AMENDMENTS
 TO SPC SEC.507.8.1.
  
 SUBMIT COMPLETE ISOMETRIC FOR THE U/G
 SANITARY SYSTEM DRAWN IN COMPLIANCE W/
 ASSE STANDARD #1043 FOR THE SOVENT
 SYSTEM.(LOCATION OF PRL AND CONNECTIONS
 TO SYSTEM,REQD.DISTANCES FROM STACK,ETC.
  
 SHOW LOCATION OF WATER TREATMENT SYSTEM
 ON PLANS.
  
 FIXTURE REQS.FOR RESTAURANT SHALL COMPLY
 W/SPC TABLE 407 & F.S.553.141-POT.PARITY
  
 SUBMIT COMPLETE GAS DRAWING FOR REVIEW.
 SHOW ALL CUT SECTIONS OF PIPE,SIZES,COM-
 BUSTION AIR,VENT DETAIL,METER LOC.COMPLY
 W/SGC SECS.305.4,402.1,402.4,NFPA 54.
  
 CLEARLY SHOW HOW EFFLUENT FROM PUMPS IN
 ELEVATOR SHAFT WILL BE DISPOSED.
  
 DRAIN AT DUMPSTER AREA SHALL DISCHARGE
 THRU GREASE INTERCEPTOR PER SPC SEC.
 1004.1.
  
 SHT.A7.3-ROOF STRAINERS ON ROOF DRAINS
 SHALL COMPLY W/SPC SEC.1107.2.
  
 SHT.A9.4-MAX.HEIGHT OF URINAL RIM SHALL
 BE 17" AFF PER FACBC SEC.4.18.2.
  
 SHT.A9.4-LAV.IN H.C.STALL INFRINGES ON
 CLEAR FLOOR SPACE FOR WATER CLOSET.
 COMPLY W/FACBC SEC.4.17.3.
  
 MIN.OF 29"IS REQD.UNDER H.C.LAV.TO FF
 PER FACBC SEC.4.19.2.
  
 SHTS.P-002 AND P-400 NOTE TWO(2)
 DIFFERENT TYPES OF INTERCEPTORS.CLARIFY.
  
 SEE PLUMBING REVIEW STEP#4 FOR CONTIN-
 UATION OF PLUMBING COMMENTS.