2001-01-08 00:00:00 | JOB SPEC.15420-12-SEC.3.9-(C)(E)(F)(G). |
| PIPING SUPPORTS SHALL COMPLY W/SPC SEC. |
| 310.3. |
| |
| JOB SPEC.15430-17-SEC.3.1.(W) AND |
| 15430-22-SEC.3.9(A)-GREASE RECOVERY |
| UNITS ARE NOT PERMITTED PER CITY ORD. |
| |
| JOB SPEC.15430-21-SEC.3.8-GREASE INTER. |
| SHALL COMPLY W/CITY OF WPB UTILITIES |
| REQS.CONTACT R.COMPO AT (561)835-7423. |
| |
| JOB SPEC.15486-6-SEC.3.2(G)-RELIEF VALVE |
| DRAIN SHALL DISCHARGE TO EXTERIOR PER |
| COUNTYWIDE AMENDMENTS TO SPC SEC.507.6.3 |
| |
| SHT.L-104-LOCATION OF BACKFLOW PREVENTER |
| SHALL BE DETERMINED BY CITY OF WPB |
| UTILITIES DEPT.CALL (561)659-8000. |
| |
| HANDICAP ACCESSIBLE ROOMS SHALL W/FACBC |
| SECS.9.1-9.4 AND ALSO W/FACBC SEC.9.2.3 |
| (FLA.5% RULE). |
| |
| CLEARLY NOTE THE TOTAL NUMBER OF SLEEP- |
| ING ROOMS IN THE FACILITY. |
| |
| SHT.A-2.1.-LOCATION OF GREASE TRAP SHALL |
| COMPLY W/CITY OF WEST PALM BEACH |
| UTILITIES REQS.CONTACT R.COMPO AT (561) |
| 835-7423.COMPLY W/SBC SEC.1803.1.3. |
| |
| SHT.A-2.1.-LOCATION OF BACKFLOW |
| PREVENTER SHALL BE DETERMINED BY CITY |
| OF WPB UTILITIES.CALL (561)659-8000 |
| |
| THE ACCESSIBLE (HANDICAP) UNITS SHALL BE |
| DISPERSED AMONG THE VARIOUS FLOORS AND |
| CLASSES PER FACBC SEC.9.1.4(1). |
| |
| ALL PUBLIC AND COMMON USE AREA ROOMS |
| SHALL BE FULLY ACCESSIBLE. |
| |
| SUBMIT DETAIL OF ELEC.WATER COOLER ON |
| ROOF. COMPLY W/FACBC SEC.4.1.3.(10)(A), |
| 4.15 AND FIGURE 27. |
| |
| SHT.M-4 SHOWS OVERFLOW FROM COOLING |
| TOWERS AND CHEMICAL FEEDER TO SANITARY. |
| PH OF EFFLUENT SHALL COMPLY W/SPC SEC. |
| 701.5.(DATA FROM MANUF.REQD.INDICATING |
| PH LEVEL OF EFFLUENT AT POINT OF |
| DISCHARGE.) |
| |
| PANS AND PAN DRAINS ARE REQD.FOR THE |
| WATER HEATERS PER COUNTYWIDE AMENDMENTS |
| TO SPC SEC.507.8.1. |
| |
| SUBMIT COMPLETE ISOMETRIC FOR THE U/G |
| SANITARY SYSTEM DRAWN IN COMPLIANCE W/ |
| ASSE STANDARD #1043 FOR THE SOVENT |
| SYSTEM.(LOCATION OF PRL AND CONNECTIONS |
| TO SYSTEM,REQD.DISTANCES FROM STACK,ETC. |
| |
| SHOW LOCATION OF WATER TREATMENT SYSTEM |
| ON PLANS. |
| |
| FIXTURE REQS.FOR RESTAURANT SHALL COMPLY |
| W/SPC TABLE 407 & F.S.553.141-POT.PARITY |
| |
| SUBMIT COMPLETE GAS DRAWING FOR REVIEW. |
| SHOW ALL CUT SECTIONS OF PIPE,SIZES,COM- |
| BUSTION AIR,VENT DETAIL,METER LOC.COMPLY |
| W/SGC SECS.305.4,402.1,402.4,NFPA 54. |
| |
| CLEARLY SHOW HOW EFFLUENT FROM PUMPS IN |
| ELEVATOR SHAFT WILL BE DISPOSED. |
| |
| DRAIN AT DUMPSTER AREA SHALL DISCHARGE |
| THRU GREASE INTERCEPTOR PER SPC SEC. |
| 1004.1. |
| |
| SHT.A7.3-ROOF STRAINERS ON ROOF DRAINS |
| SHALL COMPLY W/SPC SEC.1107.2. |
| |
| SHT.A9.4-MAX.HEIGHT OF URINAL RIM SHALL |
| BE 17" AFF PER FACBC SEC.4.18.2. |
| |
| SHT.A9.4-LAV.IN H.C.STALL INFRINGES ON |
| CLEAR FLOOR SPACE FOR WATER CLOSET. |
| COMPLY W/FACBC SEC.4.17.3. |
| |
| MIN.OF 29"IS REQD.UNDER H.C.LAV.TO FF |
| PER FACBC SEC.4.19.2. |
| |
| SHTS.P-002 AND P-400 NOTE TWO(2) |
| DIFFERENT TYPES OF INTERCEPTORS.CLARIFY. |
| |
| SEE PLUMBING REVIEW STEP#4 FOR CONTIN- |
| UATION OF PLUMBING COMMENTS. |